HANCEVILLE NURSING & REHAB CENTER, INC Nursing Home


HANCEVILLE NURSING & REHAB CENTER, INC (CCN: 015073) is a For profit - Corporation facility located in HANCEVILLE, AL (35077). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 4/5. It offers 208 certified beds and maintains an average of 191. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.94163 total hours per resident per day. It has been certified since March 17, 1967 and the last listed health inspection was on October 3, 2019, The facility is located in Cullman county and provides senior and nursing home care.

HANCEVILLE NURSING & REHAB CENTER, INC Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Hanceville Nursing & Rehab Center, Inc below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: HANCEVILLE NURSING & REHAB CENTER, INC

Address: 420 MAIN STREET NE, HANCEVILLE, AL 35077

Phone: (256) 352-6481

County: Cullman (210)

Ownership Type: For profit - Corporation

Certified Beds: 208

Average Residents Per Day: 191. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: HANCEVILLE NURSING & REHAB CENTER INC.

First Approved Date: March 17, 1967

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Both

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 3 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: 3 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.47802, LPN Staff Hours Per Day: 0.8939, RN Staff Hours Per Day: 0.5696, Licensed Staff Hours Per Day: 1.4636

Total Nurse Staff Hours Per Day, per resident: 3.94163

Weekend Nurse Staff Hours: 3.25474, Weekend RN Staff Hours: 0.2645

PT Staff Hours Per Day, per resident: 0.0154

Nurse Staff Turnover: 39.2, Nurse Turnover Note:

RN Turnover: 15.0, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.0470, Case Mix LPN Hours Per Day: 0.6408, Case Mix RN Hours Per Day: 0.2911

Adjusted Nurse Aide Hours Per Day, per resident: 2.46617, Adjusted LPN Hours Per Day: 1.0293, Adjusted RN Hours Per Day: 0.7374

Total Adjusted Nurse Hours Per Day, per resident: 4.17057

Adjusted Weekend Nurse Hours Per Day, per resident: 3.44379

Health Survey Dates and Scores: Cycle 1: 2019-10-03 (Score: 4), Cycle 2: 2018-08-23 (Score: 0), Cycle 3: 2017-07-13 (Score: 24)

Total Weighted Health Score: 6.000

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 420 MAIN STREET NE,HANCEVILLE,AL,35077 (34.0618, -86.771)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2019-10-03

Type: Health, Deficiency: Provide pharmaceutical services to meet the needs of each resident and employ or obtain the services of a licensed pharmacist.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-21

Citation on 2017-07-13

Type: Health, Deficiency: Ensure services provided by the nursing facility meet professional standards of quality.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2017-08-10

Citation on 2017-07-13

Type: Health, Deficiency: Dispose of garbage and refuse properly.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2017-08-10

Citation on 2017-07-13

Type: Health, Deficiency: Have a program that investigates, controls and keeps infection from spreading.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2017-08-10


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2019-10-10

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-11-14

Citation on 2019-10-10

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-11-06

Citation on 2019-10-10

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-11-06

Citation on 2018-08-29

Type: Fire Safety, Tag: 0018, Version: New

Description: Establish procedures for tracking staff and patients during an emergency.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0030, Version: New

Description: List the names and contact information of those in the facility.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0232, Version: New

Description: Have corridors or aisles that are unobstructed and are at least 8 feet in width.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0346, Version: New

Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0500, Version: New

Description: Meet other general requirements that are deficient.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0751, Version: New

Description: Have restrictions on the use of flammable curtains.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0916, Version: New

Description: Have a battery powered remote alarm panel in a location accessible by operating personnel.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2018-08-29

Type: Fire Safety, Tag: 0921, Version: New

Description: Ensure that testing and maintenance of electrical equipment is performed.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-02

Citation on 2017-07-20

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2017-08-20

Citation on 2017-07-20

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2017-08-20

Citation on 2017-07-20

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2017-08-20

Citation on 2017-07-20

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2017-08-20