MAPLETON POST ACUTE Nursing Home


MAPLETON POST ACUTE (CCN: 065097) is a For profit - Corporation facility located in LAKEWOOD, CO (80226). The facility has an overall rating of 2/5, health inspection rating of 2/5, and a staffing rating of 2/5. It offers 90 certified beds and maintains an average of 67.9 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.38068 total hours per resident per day. It has been certified since April 1, 1968 and the last listed health inspection was on June 29, 2023, The facility is located in Jefferson county and provides senior and nursing home care.

MAPLETON POST ACUTE Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Mapleton Post Acute below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: MAPLETON POST ACUTE

Address: 115 INGALLS ST, LAKEWOOD, CO 80226

Phone: (303) 237-1325

County: Jefferson (290)

Ownership Type: For profit - Corporation

Certified Beds: 90

Average Residents Per Day: 67.9 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: CASTLE ROCK HEALTHCARE, INC.

First Approved Date: April 1, 1968

Affiliated Entity: THE ENSIGN GROUP (507)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: Y

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 2 ()

Health Inspection Rating: 2 ()

QM Rating: 3 ()

Long Stay QM Rating: 3 ()

Short Stay QM Rating: (2)

Staffing Rating: 2 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.13021, LPN Staff Hours Per Day: 0.7120, RN Staff Hours Per Day: 0.5384, Licensed Staff Hours Per Day: 1.2504

Total Nurse Staff Hours Per Day, per resident: 3.38068

Weekend Nurse Staff Hours: 3.07744, Weekend RN Staff Hours: 0.4284

PT Staff Hours Per Day, per resident: 0.1466

Nurse Staff Turnover: 95.2, Nurse Turnover Note:

RN Turnover: 100., RN Turnover Note:

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 1.8757, Case Mix LPN Hours Per Day: 0.6581, Case Mix RN Hours Per Day: 0.2913

Adjusted Nurse Aide Hours Per Day, per resident: 2.31364, Adjusted LPN Hours Per Day: 0.7984, Adjusted RN Hours Per Day: 0.6963

Total Adjusted Nurse Hours Per Day, per resident: 3.77182

Adjusted Weekend Nurse Hours Per Day, per resident: 3.43349

Health Survey Dates and Scores: Cycle 1: 2023-06-29 (Score: 116), Cycle 2: 2019-08-29 (Score: 20), Cycle 3: 2018-07-26 (Score: 0)

Total Weighted Health Score: 64.667

Reported Incidents: 0, Substantiated Complaints: 3

Infection Control Citations: 1

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 115 INGALLS ST,LAKEWOOD,CO,80226 (39.7187, -105.064)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-04-19

Type: Health, Deficiency: Honor the resident's right to and the facility must promote and facilitate resident self-determination through support of resident choice.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-12

Citation on 2023-04-19

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-17

Citation on 2023-04-19

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-17

Citation on 2023-06-29

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Provide enough food/fluids to maintain a resident's health.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Provide enough nursing staff every day to meet the needs of every resident; and have a licensed nurse in charge on each shift.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Ensure medication error rates are not 5 percent or greater.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Ensure each resident receives and the facility provides food that accommodates resident allergies, intolerances, and preferences, as well as appealing options.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Arrange for the provision of hospice services or assist the resident in transferring to a facility that will arrange for the provision of hospice services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Electronically submit to CMS complete and accurate direct care staffing information, based on payroll and other verifiable and auditable data.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2023-06-29

Type: Health, Deficiency: Set up an ongoing quality assessment and assurance group to review quality deficiencies and develop corrective plans of action.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-24

Citation on 2019-08-29

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-20

Citation on 2019-08-29

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-20

Citation on 2019-08-29

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-26

Citation on 2019-08-29

Type: Health, Deficiency: Arrange for the provision of hospice services or assist the resident in transferring to a facility that will arrange for the provision of hospice services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-09


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-25

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-07-25

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2019-09-24

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2020-04-17

Citation on 2019-09-24

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-18

Citation on 2019-09-24

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-18

Citation on 2019-09-24

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-10

Citation on 2019-09-24

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-18

Citation on 2019-09-24

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-18

Citation on 2019-09-24

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-18

Citation on 2019-09-24

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2019-10-18

Citation on 2019-09-24

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-18

Citation on 2019-09-24

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-11-01

Citation on 2019-09-24

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-10-18

Citation on 2018-08-08

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0751, Version: New

Description: Have restrictions on the use of flammable curtains.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0912, Version: New

Description: Have power receptacles that are properly grounded.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22

Citation on 2018-08-08

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-08-22