LIBERTY HEIGHTS Nursing Home


LIBERTY HEIGHTS (CCN: 065305) is a For profit - Limited Liability company facility located in COLORADO SPRINGS, CO (80921). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 5/5. It offers 42 certified beds and maintains an average of 39.0 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.64851 total hours per resident per day. It has been certified since October 15, 1992 and the last listed health inspection was on September 13, 2023, The facility is located in El Paso county and provides senior and nursing home care.

LIBERTY HEIGHTS Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Liberty Heights below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: LIBERTY HEIGHTS

Address: 12205 GUNSTOCK DR, COLORADO SPRINGS, CO 80921

Phone: (719) 481-9494

County: El Paso (200)

Ownership Type: For profit - Limited Liability company

Certified Beds: 42

Average Residents Per Day: 39.0 ()

Provider Type: Medicare, Resides in Hospital: No

Legal Business Name: GA HC REIT II LIBERTY TRS SUB, LLC

First Approved Date: October 15, 1992

Affiliated Entity: SENIOR LIFESTYLE (621)

Retirement Community: Y, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Both

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 5 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 4 ()

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.36237, LPN Staff Hours Per Day: 1.1284, RN Staff Hours Per Day: 1.1576, Licensed Staff Hours Per Day: 2.2861

Total Nurse Staff Hours Per Day, per resident: 4.64851

Weekend Nurse Staff Hours: 4.20507, Weekend RN Staff Hours: 0.8460

PT Staff Hours Per Day, per resident: 0.1528

Nurse Staff Turnover: 48.4, Nurse Turnover Note:

RN Turnover: 46.7, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1631, Case Mix LPN Hours Per Day: 0.7248, Case Mix RN Hours Per Day: 0.3304

Adjusted Nurse Aide Hours Per Day, per resident: 2.22484, Adjusted LPN Hours Per Day: 1.1490, Adjusted RN Hours Per Day: 1.3200

Total Adjusted Nurse Hours Per Day, per resident: 4.55259

Adjusted Weekend Nurse Hours Per Day, per resident: 4.11830

Health Survey Dates and Scores: Cycle 1: 2023-09-13 (Score: 8), Cycle 2: 2019-12-19 (Score: 4), Cycle 3: 2018-12-20 (Score: 16)

Total Weighted Health Score: 8.000

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 650.00, Payment Denials Number: 0, Total Penalties Number: 1

Location and GPS: 12205 GUNSTOCK DR,COLORADO SPRINGS,CO,80921 (39.0075, -104.794)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-09-13

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-04

Citation on 2023-09-13

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-13

Citation on 2019-12-19

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-01-21

Citation on 2018-12-20

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-24


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-10-06

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2023-10-06

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2023-10-06

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2023-10-06

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2023-10-06

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2023-10-06

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2023-10-06

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2023-10-06

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2023-10-06

Type: Fire Safety, Tag: 0927, Version: New

Description: Have proper fire barriers, ventilation and signs for the transfilling of oxygen.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-14

Citation on 2020-01-09

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-01-27

Citation on 2020-01-09

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-01-14

Citation on 2020-01-09

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-01-30

Citation on 2020-01-09

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-05

Citation on 2019-01-18

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-18

Citation on 2019-01-18

Type: Fire Safety, Tag: 0226, Version: New

Description: Have horizontal exits used in accordance with safety requirements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-18

Citation on 2019-01-18

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-26

Citation on 2019-01-18

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-06

Citation on 2019-01-18

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-15

Citation on 2019-01-18

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-15

Citation on 2019-01-18

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-18