ELMHURST EXTENDED CARE CENTER Nursing Home


ELMHURST EXTENDED CARE CENTER (CCN: 145111) is a For profit - Corporation facility located in ELMHURST, IL (60126). The facility has an overall rating of 2/5, health inspection rating of 3/5, and a staffing rating of 4/5. It offers 108 certified beds and maintains an average of 32.6 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.34408 total hours per resident per day. It has been certified since January 10, 1967 and the last listed health inspection was on November 29, 2023, The facility is located in Du Page county and provides senior and nursing home care.

ELMHURST EXTENDED CARE CENTER Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Elmhurst Extended Care Center below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: ELMHURST EXTENDED CARE CENTER

Address: 200 EAST LAKE STREET, ELMHURST, IL 60126

Phone: (630) 516-5000

County: Du Page (250)

Ownership Type: For profit - Corporation

Certified Beds: 108

Average Residents Per Day: 32.6 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: SBNB, INC.

First Approved Date: January 10, 1967

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 2 ()

Health Inspection Rating: 3 ()

QM Rating: 1 ()

Long Stay QM Rating: 1 ()

Short Stay QM Rating: 1 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.66274, LPN Staff Hours Per Day: 0.5128, RN Staff Hours Per Day: 1.1684, Licensed Staff Hours Per Day: 1.6813

Total Nurse Staff Hours Per Day, per resident: 4.34408

Weekend Nurse Staff Hours: 4.23908, Weekend RN Staff Hours: 1.0092

PT Staff Hours Per Day, per resident: 0.2921

Nurse Staff Turnover: 52.4, Nurse Turnover Note:

RN Turnover: 58.3, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1564, Case Mix LPN Hours Per Day: 0.7062, Case Mix RN Hours Per Day: 0.3086

Adjusted Nurse Aide Hours Per Day, per resident: 2.51560, Adjusted LPN Hours Per Day: 0.5359, Adjusted RN Hours Per Day: 1.4263

Total Adjusted Nurse Hours Per Day, per resident: 4.31765

Adjusted Weekend Nurse Hours Per Day, per resident: 4.21329

Health Survey Dates and Scores: Cycle 1: 2023-11-29 (Score: 68), Cycle 2: 2022-11-17 (Score: 56), Cycle 3: 2021-08-19 (Score: 40)

Total Weighted Health Score: 68.667

Reported Incidents: 0, Substantiated Complaints: 7

Infection Control Citations:

Fines and Penalties: Number of Fines: 53, Total Fines in Dollars: 349543.02, Payment Denials Number: 2, Total Penalties Number: 55

Location and GPS: 200 EAST LAKE STREET,ELMHURST,IL,60126 (41.9112, -87.936)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-11-29

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-05

Citation on 2023-11-29

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-05

Citation on 2023-11-29

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-05

Citation on 2023-11-29

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-05

Citation on 2023-11-29

Type: Health, Deficiency: Have a registered nurse on duty 8 hours a day; and select a registered nurse to be the director of nurses on a full time basis.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-05

Citation on 2023-11-29

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-05

Citation on 2023-11-29

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-05

Citation on 2023-11-29

Type: Health, Deficiency: Designate a qualified infection preventionist to be responsible for the infection prevent and control program in the nursing home.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-05

Citation on 2022-09-26

Type: Health, Deficiency: Honor the resident's right to and the facility must promote and facilitate resident self-determination through support of resident choice.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2022-09-26

Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2022-09-26

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2022-07-14

Type: Health, Deficiency: Report COVID19 data to residents and families.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-26

Citation on 2022-11-17

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2022-11-17

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2022-11-17

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2021-08-19

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-03

Citation on 2021-08-19

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-08

Citation on 2021-08-19

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-11

Citation on 2021-08-19

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-15

Citation on 2021-08-19

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-11

Citation on 2021-08-19

Type: Health, Deficiency: Designate a qualified infection preventionist to be responsible for the infection prevent and control program in the nursing home.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-03


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-12-05

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-12-05

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0342, Version: New

Description: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0541, Version: New

Description: Install properly constructed and protected linen or trash chutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2023-12-05

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-06

Citation on 2022-11-17

Type: Fire Safety, Tag: 0018, Version: New

Description: Establish procedures for tracking staff and patients during an emergency.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0022, Version: New

Description: Establish policies and procedures for sheltering.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2022-11-17

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-09

Citation on 2022-11-17

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-09

Citation on 2022-11-17

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0916, Version: New

Description: Have a battery powered remote alarm panel in a location accessible by operating personnel.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-17

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-29

Citation on 2022-11-17

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-11-17

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2021-09-29

Type: Fire Safety, Tag: 0004, Version: New

Description: Develop and maintain an Emergency Preparedness Program (EP).

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-17

Citation on 2021-09-29

Type: Fire Safety, Tag: 0013, Version: New

Description: Develop Emergency Preparedness policies and procedures.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-17

Citation on 2021-09-29

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-30

Citation on 2021-09-29

Type: Fire Safety, Tag: 0018, Version: New

Description: Establish procedures for tracking staff and patients during an emergency.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-17

Citation on 2021-09-29

Type: Fire Safety, Tag: 0022, Version: New

Description: Establish policies and procedures for sheltering.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-17

Citation on 2021-09-29

Type: Fire Safety, Tag: 0029, Version: New

Description: Develop a communication plan.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-17

Citation on 2021-09-29

Type: Fire Safety, Tag: 0032, Version: New

Description: Provide primary/alternate means for communication.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-17

Citation on 2021-09-29

Type: Fire Safety, Tag: 0035, Version: New

Description: Provide family notifications of emergency plan.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-30

Citation on 2021-09-29

Type: Fire Safety, Tag: 0036, Version: New

Description: Establish emergency prep training and testing.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-30

Citation on 2021-09-29

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-30

Citation on 2021-09-29

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-30

Citation on 2021-09-29

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-01

Citation on 2021-09-29

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-01

Citation on 2021-09-29

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-01

Citation on 2021-09-29

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-30