PAVILION OF WAUKEGAN Nursing Home


PAVILION OF WAUKEGAN (CCN: 145621) is a For profit - Limited Liability company facility located in WAUKEGAN, IL (60085). The facility has an overall rating of 3/5, health inspection rating of 3/5, and a staffing rating of 2/5. It offers 112 certified beds and maintains an average of 83.1 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 2.79083 total hours per resident per day. It has been certified since July 1, 1989 and the last listed health inspection was on July 27, 2023, The facility is located in Lake county and provides senior and nursing home care.

PAVILION OF WAUKEGAN Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Pavilion Of Waukegan below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: PAVILION OF WAUKEGAN

Address: 2217 WASHINGTON STREET, WAUKEGAN, IL 60085

Phone: (847) 244-4100

County: Lake (570)

Ownership Type: For profit - Limited Liability company

Certified Beds: 112

Average Residents Per Day: 83.1 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: PAVILION OF WAUKEGAN, LLC

First Approved Date: July 1, 1989

Affiliated Entity: CROSSROADS CARE CENTER (171)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 3 ()

QM Rating: 2 ()

Long Stay QM Rating: 3 ()

Short Stay QM Rating: 1 ()

Staffing Rating: 2 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 1.65815, LPN Staff Hours Per Day: 0.4701, RN Staff Hours Per Day: 0.6625, Licensed Staff Hours Per Day: 1.1326

Total Nurse Staff Hours Per Day, per resident: 2.79083

Weekend Nurse Staff Hours: 2.49397, Weekend RN Staff Hours: 0.6282

PT Staff Hours Per Day, per resident: 0.0470

Nurse Staff Turnover: 61.0, Nurse Turnover Note:

RN Turnover: 27.3, RN Turnover Note:

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 1.9481, Case Mix LPN Hours Per Day: 0.7076, Case Mix RN Hours Per Day: 0.3076

Adjusted Nurse Aide Hours Per Day, per resident: 1.73399, Adjusted LPN Hours Per Day: 0.4903, Adjusted RN Hours Per Day: 0.8115

Total Adjusted Nurse Hours Per Day, per resident: 2.96850

Adjusted Weekend Nurse Hours Per Day, per resident: 2.65273

Health Survey Dates and Scores: Cycle 1: 2023-07-27 (Score: 92), Cycle 2: 2022-10-26 (Score: 64), Cycle 3: 2021-11-03 (Score: 40)

Total Weighted Health Score: 74.000

Reported Incidents: 2, Substantiated Complaints: 5

Infection Control Citations: 2

Fines and Penalties: Number of Fines: 5, Total Fines in Dollars: 37963.06, Payment Denials Number: 0, Total Penalties Number: 5

Location and GPS: 2217 WASHINGTON STREET,WAUKEGAN,IL,60085 (42.3595, -87.860)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-12-22

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-30

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-15

Citation on 2023-11-15

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-27

Citation on 2023-11-15

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-27

Citation on 2023-04-25

Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-17

Citation on 2023-07-27

Type: Health, Deficiency: Ensure that each resident is free from the use of physical restraints, unless needed for medical treatment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-16

Citation on 2023-07-27

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-16

Citation on 2023-07-27

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-16

Citation on 2023-07-27

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-16

Citation on 2023-07-27

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-16

Citation on 2023-07-27

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-16

Citation on 2022-10-26

Type: Health, Deficiency: Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decline/room, etc.) that affect the resident.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-19

Citation on 2022-10-26

Type: Health, Deficiency: Ensure that each resident is free from the use of physical restraints, unless needed for medical treatment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-19

Citation on 2022-10-26

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-19

Citation on 2022-10-26

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-19

Citation on 2022-10-26

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-19

Citation on 2022-10-26

Type: Health, Deficiency: Ensure each resident receives and the facility provides food prepared in a form designed to meet individual needs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-19

Citation on 2022-10-26

Type: Health, Deficiency: Ensure each resident receives and the facility provides food that accommodates resident allergies, intolerances, and preferences, as well as appealing options.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-19

Citation on 2022-10-26

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-19

Citation on 2021-04-21

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-05-13

Citation on 2021-04-21

Type: Health, Deficiency: Develop and implement policies and procedures for flu and pneumonia vaccinations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-05-13

Citation on 2021-11-03

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-24

Citation on 2021-11-03

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-24

Citation on 2021-11-03

Type: Health, Deficiency: Provide for the safe, appropriate administration of IV fluids for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-24

Citation on 2021-11-03

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-24

Citation on 2021-11-03

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-24


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-08-03

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-20

Citation on 2023-08-03

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-23

Citation on 2023-08-03

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-05

Citation on 2022-11-04

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-02

Citation on 2022-11-04

Type: Fire Safety, Tag: 0346, Version: New

Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-02

Citation on 2022-11-04

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-02

Citation on 2022-11-04

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-02

Citation on 2022-11-04

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-02

Citation on 2022-11-04

Type: Fire Safety, Tag: 0915, Version: New

Description: Have proper power supply for life support equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-06

Citation on 2022-11-04

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-02

Citation on 2021-11-17

Type: Fire Safety, Tag: 0007, Version: New

Description: Address patient/client population and determine types of services needed.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0013, Version: New

Description: Develop Emergency Preparedness policies and procedures.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0022, Version: New

Description: Establish policies and procedures for sheltering.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0032, Version: New

Description: Provide primary/alternate means for communication.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-30

Citation on 2021-11-17

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-30

Citation on 2021-11-17

Type: Fire Safety, Tag: 0346, Version: New

Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0354, Version: New

Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-30

Citation on 2021-11-17

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-30

Citation on 2021-11-17

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17

Citation on 2021-11-17

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-17