ADDOLORATA VILLA Nursing Home


ADDOLORATA VILLA (CCN: 145724) is a Non profit - Church related facility located in WHEELING, IL (60090). The facility has an overall rating of 4/5, health inspection rating of 3/5, and a staffing rating of 5/5. It offers 90 certified beds and maintains an average of 71.5 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.75498 total hours per resident per day. It has been certified since June 1, 1992 and the last listed health inspection was on February 16, 2023, The facility is located in Cook county and provides senior and nursing home care.

ADDOLORATA VILLA Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Addolorata Villa below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: ADDOLORATA VILLA

Address: 555 MCHENRY ROAD, WHEELING, IL 60090

Phone: (847) 537-2900

County: Cook (141)

Ownership Type: Non profit - Church related

Certified Beds: 90

Average Residents Per Day: 71.5 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: FRANCISCAN COMMUNITIES, INC

First Approved Date: June 1, 1992

Affiliated Entity: FRANCISCAN COMMUNITIES (227)

Retirement Community: Y, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 3 ()

QM Rating: 4 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: 4 ()

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 3.04454, LPN Staff Hours Per Day: 0.3585, RN Staff Hours Per Day: 1.3518, Licensed Staff Hours Per Day: 1.7104

Total Nurse Staff Hours Per Day, per resident: 4.75498

Weekend Nurse Staff Hours: 4.36949, Weekend RN Staff Hours: 1.0530

PT Staff Hours Per Day, per resident: 0.0571

Nurse Staff Turnover: 39.1, Nurse Turnover Note:

RN Turnover: 30.4, RN Turnover Note:

Admin Left Number: 1, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.2523, Case Mix LPN Hours Per Day: 0.6951, Case Mix RN Hours Per Day: 0.3283

Adjusted Nurse Aide Hours Per Day, per resident: 2.75376, Adjusted LPN Hours Per Day: 0.3806, Adjusted RN Hours Per Day: 1.5512

Total Adjusted Nurse Hours Per Day, per resident: 4.57520

Adjusted Weekend Nurse Hours Per Day, per resident: 4.20427

Health Survey Dates and Scores: Cycle 1: 2023-02-16 (Score: 92), Cycle 2: 2022-04-15 (Score: 48), Cycle 3: 2020-10-01 (Score: 64)

Total Weighted Health Score: 72.667

Reported Incidents: 3, Substantiated Complaints: 7

Infection Control Citations:

Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 30785.00, Payment Denials Number: 0, Total Penalties Number: 2

Location and GPS: 555 MCHENRY ROAD,WHEELING,IL,60090 (42.1457, -87.941)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-08-25

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-18

Citation on 2023-07-13

Type: Health, Deficiency: Develop and implement policies and procedures to prevent abuse, neglect, and theft.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-03

Citation on 2023-05-25

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-21

Citation on 2023-02-16

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-08

Citation on 2023-02-16

Type: Health, Deficiency: Ensure services provided by the nursing facility meet professional standards of quality.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-08

Citation on 2023-02-16

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-08

Citation on 2023-02-16

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-08

Citation on 2023-02-16

Type: Health, Deficiency: Provide safe, appropriate pain management for a resident who requires such services.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-08

Citation on 2023-02-16

Type: Health, Deficiency: Arrange for the provision of hospice services or assist the resident in transferring to a facility that will arrange for the provision of hospice services.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-08

Citation on 2023-02-16

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-02

Citation on 2022-06-02

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-20

Citation on 2022-04-15

Type: Health, Deficiency: Reasonably accommodate the needs and preferences of each resident.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-05

Citation on 2022-04-15

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-05

Citation on 2022-04-15

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-05

Citation on 2022-04-15

Type: Health, Deficiency: Provide safe, appropriate pain management for a resident who requires such services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-05

Citation on 2022-04-15

Type: Health, Deficiency: Ensure each resident’s drug regimen must be free from unnecessary drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-05

Citation on 2022-04-15

Type: Health, Deficiency: Ensure meals and snacks are served at times in accordance with resident’s needs, preferences, and requests. Suitable and nourishing alternative meals and snacks must be provided for residents who want to eat at non-traditional times or outside of scheduled meal times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-05

Citation on 2022-02-28

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-11

Citation on 2022-02-28

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-11

Citation on 2021-08-16

Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-10

Citation on 2021-08-16

Type: Health, Deficiency: Provide enough nursing staff every day to meet the needs of every resident; and have a licensed nurse in charge on each shift.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-10

Citation on 2021-08-16

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-10

Citation on 2020-10-01

Type: Health, Deficiency: Ensure medication error rates are not 5 percent or greater.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-23


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-03-02

Type: Fire Safety, Tag: 0133, Version: New

Description: Install a two-hour-resistant firewall separation.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-16

Citation on 2023-03-02

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-17

Citation on 2023-03-02

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-17

Citation on 2023-03-02

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-20

Citation on 2023-03-02

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-20

Citation on 2023-03-02

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-17

Citation on 2023-03-02

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-02

Type: Fire Safety, Tag: 0926, Version: New

Description: Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-27

Citation on 2022-04-27

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-20

Citation on 2022-04-27

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-20

Citation on 2022-04-27

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-20

Citation on 2020-09-29

Type: Fire Safety, Tag: 0007, Version: New

Description: Address patient/client population and determine types of services needed.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-02

Citation on 2020-09-29

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-02

Citation on 2020-09-29

Type: Fire Safety, Tag: 0024, Version: New

Description: Establish policies and procedures for volunteers.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-02

Citation on 2020-09-29

Type: Fire Safety, Tag: 0031, Version: New

Description: Provide emergency officials' contact information.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-02

Citation on 2020-09-29

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-23

Citation on 2020-09-29

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-13

Citation on 2020-09-29

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-02

Citation on 2020-09-29

Type: Fire Safety, Tag: 0347, Version: New

Description: Properly provide smoke detection systems in areas open to corridors.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-02

Citation on 2020-09-29

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-13

Citation on 2020-09-29

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-30

Citation on 2020-09-29

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-23

Citation on 2020-09-29

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-13

Citation on 2020-09-29

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-13

Citation on 2020-09-29

Type: Fire Safety, Tag: 0916, Version: New

Description: Have a battery powered remote alarm panel in a location accessible by operating personnel.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-02