Provider Name: ASCENSION SAINT BENEDICT
Address: 6930 WEST TOUHY AVENUE, NILES, IL 60714
Phone: (847) 647-0003
County: Cook (141)
Ownership Type: Non profit - Church related
Certified Beds: 99
Average Residents Per Day: 83.1 ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: PRESENCE SENIOR SERVICES CHICAGOLAND
First Approved Date: August 1, 1992
Affiliated Entity: ASCENSION LIVING (48)
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Resident
Sprinkler System Status: Yes
Overall Rating: 5 ()
Health Inspection Rating: 4 ()
QM Rating: 5 ()
Long Stay QM Rating: 4 ()
Short Stay QM Rating: 5 ()
Staffing Rating: 4 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 2.04885, LPN Staff Hours Per Day: 0.3756, RN Staff Hours Per Day: 1.1295, Licensed Staff Hours Per Day: 1.5051
Total Nurse Staff Hours Per Day, per resident: 3.55403
Weekend Nurse Staff Hours: 3.11357, Weekend RN Staff Hours: 0.8261
PT Staff Hours Per Day, per resident: 0.0700
Nurse Staff Turnover: 41.8, Nurse Turnover Note:
RN Turnover: 26.1, RN Turnover Note:
Admin Left Number: 0, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 2.1849, Case Mix LPN Hours Per Day: 0.7335, Case Mix RN Hours Per Day: 0.3447
Adjusted Nurse Aide Hours Per Day, per resident: 1.91037, Adjusted LPN Hours Per Day: 0.3779, Adjusted RN Hours Per Day: 1.2345
Total Adjusted Nurse Hours Per Day, per resident: 3.43291
Adjusted Weekend Nurse Hours Per Day, per resident: 3.00746
Health Survey Dates and Scores: Cycle 1: 2023-04-06 (Score: 8), Cycle 2: 2021-03-05 (Score: 72), Cycle 3: 2019-05-23 (Score: 8)
Total Weighted Health Score: 29.333
Reported Incidents: 0, Substantiated Complaints: 2
Infection Control Citations:
Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 1, Total Penalties Number: 1
Location and GPS: 6930 WEST TOUHY AVENUE,NILES,IL,60714 (42.0123, -87.800)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-17
Type: Health, Deficiency: Notify the resident or the resident’s representative in writing how long the nursing home will hold the resident’s bed in cases of transfer to a hospital or therapeutic leave.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-29
Type: Health, Deficiency: Allow residents to self-administer drugs if determined clinically appropriate.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Ensure services provided by the nursing facility meet professional standards of quality.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.
Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Develop and implement policies and procedures for flu and pneumonia vaccinations.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Health, Deficiency: Honor the resident's right to request, refuse, and/or discontinue treatment, to participate in or refuse to participate in experimental research, and to formulate an advance directive.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-25
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-25
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0133, Version: New
Description: Install a two-hour-resistant firewall separation.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0225, Version: New
Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0293, Version: New
Description: Have properly located and lighted "Exit" signs.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-04-11
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0324, Version: New
Description: Provide properly protected cooking facilities.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-04-11
Type: Fire Safety, Tag: 0341, Version: New
Description: Install a fire alarm system that can be heard throughout the facility.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0351, Version: New
Description: Install an approved automatic sprinkler system.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0511, Version: New
Description: Have properly installed electrical wiring and gas equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-02
Type: Fire Safety, Tag: 0521, Version: New
Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-04-11
Type: Fire Safety, Tag: 0531, Version: New
Description: Have elevators that firefighters can control in the event of a fire.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-04-11
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-05
Type: Fire Safety, Tag: 0915, Version: New
Description: Have proper power supply for life support equipment.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0923, Version: New
Description: Have proper medical gas storage and administration areas.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0006, Version: New
Description: Conduct risk assessment and an All-Hazards approach.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0007, Version: New
Description: Address patient/client population and determine types of services needed.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0015, Version: New
Description: Address subsistence needs for staff and patients.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0020, Version: New
Description: Establish policies and procedures including evacuation.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0022, Version: New
Description: Establish policies and procedures for sheltering.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0034, Version: New
Description: Provide a means of sharing information on occupancy/needs.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0036, Version: New
Description: Establish emergency prep training and testing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0037, Version: New
Description: Establish staff and initial training requirements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0039, Version: New
Description: Conduct testing and exercise requirements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-09
Type: Fire Safety, Tag: 0211, Version: New
Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-03-31
Type: Fire Safety, Tag: 0225, Version: New
Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-03-31
Type: Fire Safety, Tag: 0346, Version: New
Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-03-31
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-03-31
Type: Fire Safety, Tag: 0354, Version: New
Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-03-31
Type: Fire Safety, Tag: 0521, Version: New
Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-04-07
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-03-31
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-03-31
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-25
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-25
Type: Fire Safety, Tag: 0351, Version: New
Description: Install an approved automatic sprinkler system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-07
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-10
Type: Fire Safety, Tag: 0354, Version: New
Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-25
Type: Fire Safety, Tag: 0531, Version: New
Description: Have elevators that firefighters can control in the event of a fire.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-10
Type: Fire Safety, Tag: 0711, Version: New
Description: Provide a written emergency evacuation plan.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-12
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-10
Type: Fire Safety, Tag: 0914, Version: New
Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-06-25