ASCENSION CASA SCALABRINI Nursing Home


ASCENSION CASA SCALABRINI (CCN: 145956) is a Non profit - Corporation facility located in NORTHLAKE, IL (60164). The facility has an overall rating of 4/5, health inspection rating of 4/5, and a staffing rating of 4/5. It offers 229 certified beds and maintains an average of 154. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.47242 total hours per resident per day. It has been certified since January 19, 1998 and the last listed health inspection was on January 5, 2024, The facility is located in Cook county and provides senior and nursing home care.

ASCENSION CASA SCALABRINI Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Ascension Casa Scalabrini below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: ASCENSION CASA SCALABRINI

Address: 480 NORTH WOLF ROAD, NORTHLAKE, IL 60164

Phone: (708) 562-0040

County: Cook (141)

Ownership Type: Non profit - Corporation

Certified Beds: 229

Average Residents Per Day: 154. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: PRESENCE SENIOR SERVICES CHICAGOLAND

First Approved Date: January 19, 1998

Affiliated Entity: ASCENSION LIVING (48)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 4 ()

QM Rating: 4 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: 4 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.07828, LPN Staff Hours Per Day: 0.1894, RN Staff Hours Per Day: 1.2046, Licensed Staff Hours Per Day: 1.3941

Total Nurse Staff Hours Per Day, per resident: 3.47242

Weekend Nurse Staff Hours: 3.20373, Weekend RN Staff Hours: 0.9808

PT Staff Hours Per Day, per resident: 0.0576

Nurse Staff Turnover: 59.0, Nurse Turnover Note:

RN Turnover: 34.9, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.2829, Case Mix LPN Hours Per Day: 0.7390, Case Mix RN Hours Per Day: 0.3474

Adjusted Nurse Aide Hours Per Day, per resident: 1.85464, Adjusted LPN Hours Per Day: 0.1891, Adjusted RN Hours Per Day: 1.3066

Total Adjusted Nurse Hours Per Day, per resident: 3.24842

Adjusted Weekend Nurse Hours Per Day, per resident: 2.99706

Health Survey Dates and Scores: Cycle 1: 2024-01-05 (Score: 24), Cycle 2: 2023-03-02 (Score: 36), Cycle 3: 2021-10-15 (Score: 28)

Total Weighted Health Score: 28.667

Reported Incidents: 0, Substantiated Complaints: 3

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 480 NORTH WOLF ROAD,NORTHLAKE,IL,60164 (41.9173, -87.904)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-10-04

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-02

Citation on 2024-01-05

Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-09

Citation on 2024-01-05

Type: Health, Deficiency: Reasonably accommodate the needs and preferences of each resident.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-09

Citation on 2024-01-05

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-09

Citation on 2024-01-05

Type: Health, Deficiency: Ensure that feeding tubes are not used unless there is a medical reason and the resident agrees; and provide appropriate care for a resident with a feeding tube.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-09

Citation on 2024-01-05

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-09

Citation on 2022-11-22

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-09

Citation on 2022-11-22

Type: Health, Deficiency: Provide sufficient support personnel to safely and effectively carry out the functions of the food and nutrition service.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-09

Citation on 2023-03-02

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-20

Citation on 2023-03-02

Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-20

Citation on 2023-03-02

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-20

Citation on 2023-03-02

Type: Health, Deficiency: Ensure menus must meet the nutritional needs of residents, be prepared in advance, be followed, be updated, be reviewed by dietician, and meet the needs of the resident.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-20

Citation on 2021-06-01

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Past Non-Compliance on 2021-06-14

Citation on 2021-10-15

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2024-01-16

Type: Fire Safety, Tag: 0133, Version: New

Description: Install a two-hour-resistant firewall separation.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0342, Version: New

Description: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0541, Version: New

Description: Install properly constructed and protected linen or trash chutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-16

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2023-03-07

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-07

Type: Fire Safety, Tag: 0022, Version: New

Description: Establish policies and procedures for sheltering.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-07

Type: Fire Safety, Tag: 0133, Version: New

Description: Install a two-hour-resistant firewall separation.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-07

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-07

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-23

Citation on 2023-03-07

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-07

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-07

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-16

Citation on 2023-03-07

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-05

Citation on 2023-03-07

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-07

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-16

Citation on 2023-03-07

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-16

Citation on 2021-10-20

Type: Fire Safety, Tag: 0133, Version: New

Description: Install a two-hour-resistant firewall separation.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2022-05-27

Citation on 2021-10-20

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0915, Version: New

Description: Have proper power supply for life support equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-05

Citation on 2021-10-20

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-08