TAYLORVILLE SKLD NUR & REHAB Nursing Home


TAYLORVILLE SKLD NUR & REHAB (CCN: 146048) is a For profit - Limited Liability company facility located in TAYLORVILLE, IL (62568). The facility has an overall rating of 4/5, health inspection rating of 4/5, and a staffing rating of 2/5. It offers 96 certified beds and maintains an average of 78.4 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 2.98695 total hours per resident per day. It has been certified since June 1, 2003 and the last listed health inspection was on February 1, 2024, The facility is located in Christian county and provides senior and nursing home care.

TAYLORVILLE SKLD NUR & REHAB Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Taylorville Skld Nur & Rehab below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: TAYLORVILLE SKLD NUR & REHAB

Address: 800 MCADAM DR, TAYLORVILLE, IL 62568

Phone: (217) 824-2277

County: Christian (100)

Ownership Type: For profit - Limited Liability company

Certified Beds: 96

Average Residents Per Day: 78.4 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: TAYLORVILLE SKILLED NURSING & REHAB LLC

First Approved Date: June 1, 2003

Affiliated Entity: CREST HEALTHCARE CONSULTING (170)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 4 ()

QM Rating: 4 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 3 ()

Staffing Rating: 2 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 1.82580, LPN Staff Hours Per Day: 0.5732, RN Staff Hours Per Day: 0.5878, Licensed Staff Hours Per Day: 1.1611

Total Nurse Staff Hours Per Day, per resident: 2.98695

Weekend Nurse Staff Hours: 2.48885, Weekend RN Staff Hours: 0.3273

PT Staff Hours Per Day, per resident: 0.0205

Nurse Staff Turnover: 48.7, Nurse Turnover Note:

RN Turnover: 46.2, RN Turnover Note:

Admin Left Number: 1, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1062, Case Mix LPN Hours Per Day: 0.7560, Case Mix RN Hours Per Day: 0.3558

Adjusted Nurse Aide Hours Per Day, per resident: 1.76602, Adjusted LPN Hours Per Day: 0.5595, Adjusted RN Hours Per Day: 0.6225

Total Adjusted Nurse Hours Per Day, per resident: 2.92566

Adjusted Weekend Nurse Hours Per Day, per resident: 2.43778

Health Survey Dates and Scores: Cycle 1: 2024-02-01 (Score: 8), Cycle 2: 2023-03-07 (Score: 116), Cycle 3: 2022-02-17 (Score: 76)

Total Weighted Health Score: 55.333

Reported Incidents: 0, Substantiated Complaints: 1

Infection Control Citations: 1

Fines and Penalties: Number of Fines: 4, Total Fines in Dollars: 92573.00, Payment Denials Number: 0, Total Penalties Number: 4

Location and GPS: 800 MCADAM DR,TAYLORVILLE,IL,62568 (39.5562, -89.278)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2024-02-01

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-23

Citation on 2023-03-07

Type: Health, Deficiency: Create and put into place a plan for meeting the resident's most immediate needs within 48 hours of being admitted

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Ensure that nurses and nurse aides have the appropriate competencies to care for every resident in a way that maximizes each resident's well being.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Ensure menus must meet the nutritional needs of residents, be prepared in advance, be followed, be updated, be reviewed by dietician, and meet the needs of the resident.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Ensure each resident receives and the facility provides food that accommodates resident allergies, intolerances, and preferences, as well as appealing options.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Have a plan that describes the process for conducting QAPI and QAA activities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2023-03-07

Type: Health, Deficiency: Implement a program that monitors antibiotic use.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-28

Citation on 2021-12-20

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-31

Citation on 2021-03-16

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-04-01

Citation on 2022-02-17

Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2022-03-08

Citation on 2022-02-17

Type: Health, Deficiency: Notify the resident or the resident’s representative in writing how long the nursing home will hold the resident’s bed in cases of transfer to a hospital or therapeutic leave.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2022-03-08

Citation on 2022-02-17

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-08

Citation on 2022-02-17

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-08

Citation on 2022-02-17

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-08


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2024-01-31

Type: Fire Safety, Tag: 0004, Version: New

Description: Develop and maintain an Emergency Preparedness Program (EP).

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0013, Version: New

Description: Develop Emergency Preparedness policies and procedures.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0029, Version: New

Description: Develop a communication plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0036, Version: New

Description: Establish emergency prep training and testing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2024-01-31

Type: Fire Safety, Tag: 0930, Version: New

Description: Ensure proper storage of liquid oxygen.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-23

Citation on 2023-03-01

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0030, Version: New

Description: List the names and contact information of those in the facility.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0354, Version: New

Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2023-03-01

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-30

Citation on 2022-03-10

Type: Fire Safety, Tag: 0025, Version: New

Description: Create arrangements with other facilities to receive patients.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-25

Citation on 2022-03-10

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-25

Citation on 2022-03-10

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-25

Citation on 2022-03-10

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-25