GOLDEN GOOD SHEPHERD HOME Nursing Home


GOLDEN GOOD SHEPHERD HOME (CCN: 146111) is a Non profit - Corporation facility located in GOLDEN, IL (62339). The facility has an overall rating of 4/5, health inspection rating of 5/5, and a staffing rating of 1/5. It offers 46 certified beds and maintains an average of 31.2 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.56183 total hours per resident per day. It has been certified since July 1, 2007 and the last listed health inspection was on September 7, 2023, The facility is located in Adams county and provides senior and nursing home care.

GOLDEN GOOD SHEPHERD HOME Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Golden Good Shepherd Home below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: GOLDEN GOOD SHEPHERD HOME

Address: 101 PRAIRIE MILLS ROAD, GOLDEN, IL 62339

Phone: (217) 696-4421

County: Adams (000)

Ownership Type: Non profit - Corporation

Certified Beds: 46

Average Residents Per Day: 31.2 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: GOLDEN GOOD SHEPHERD HOME

First Approved Date: July 1, 2007

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 5 ()

QM Rating: 3 ()

Long Stay QM Rating: 3 ()

Short Stay QM Rating: (2)

Staffing Rating: 1 (12)

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.14300, LPN Staff Hours Per Day: 0.8460, RN Staff Hours Per Day: 0.5727, Licensed Staff Hours Per Day: 1.4188

Total Nurse Staff Hours Per Day, per resident: 3.56183

Weekend Nurse Staff Hours: 3.29293, Weekend RN Staff Hours: 0.3894

PT Staff Hours Per Day, per resident: 0.0139

Nurse Staff Turnover: 51.3, Nurse Turnover Note:

RN Turnover: 71.4, RN Turnover Note:

Admin Left Number: 2, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.0364, Case Mix LPN Hours Per Day: 0.6652, Case Mix RN Hours Per Day: 0.3015

Adjusted Nurse Aide Hours Per Day, per resident: 2.14386, Adjusted LPN Hours Per Day: 0.9385, Adjusted RN Hours Per Day: 0.7157

Total Adjusted Nurse Hours Per Day, per resident: 3.73832

Adjusted Weekend Nurse Hours Per Day, per resident: 3.45609

Health Survey Dates and Scores: Cycle 1: 2023-09-07 (Score: 28), Cycle 2: 2022-08-18 (Score: 16), Cycle 3: 2021-09-09 (Score: 0)

Total Weighted Health Score: 19.333

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 650.00, Payment Denials Number: 0, Total Penalties Number: 1

Location and GPS: 101 PRAIRIE MILLS ROAD,GOLDEN,IL,62339 (40.1066, -91.028)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-09-07

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-11

Citation on 2023-09-07

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-15

Citation on 2023-09-07

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-10

Citation on 2023-09-07

Type: Health, Deficiency: Implement a program that monitors antibiotic use.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-15

Citation on 2022-08-18

Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-07

Citation on 2022-08-18

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-07

Citation on 2022-08-18

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-07

Citation on 2022-08-18

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-07


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-09-11

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-06

Citation on 2023-09-11

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-18

Citation on 2023-09-11

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-12

Citation on 2023-09-11

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-04

Citation on 2023-09-11

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-13

Citation on 2023-09-11

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-11

Citation on 2022-08-31

Type: Fire Safety, Tag: 0133, Version: New

Description: Install a two-hour-resistant firewall separation.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-31

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-31

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-31

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-31

Citation on 2022-08-31

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-31

Citation on 2022-08-31

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-27

Citation on 2022-08-31

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-31

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-31

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-31

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-31

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-31

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2021-11-03

Type: Fire Safety, Tag: 0031, Version: New

Description: Provide emergency officials' contact information.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-08

Citation on 2021-11-03

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-18

Citation on 2021-11-03

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-15

Citation on 2021-11-03

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-18

Citation on 2021-11-03

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-19