MIDDLETOWN NURSING AND REHABILITATION CENTER Nursing Home


MIDDLETOWN NURSING AND REHABILITATION CENTER (CCN: 155486) is a For profit - Corporation facility located in MIDDLETOWN, IN (47356). The facility has an overall rating of 5/5, health inspection rating of 4/5, and a staffing rating of 5/5. It offers 45 certified beds and maintains an average of 13.3 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 5.32533 total hours per resident per day. It has been certified since May 1, 1993 and the last listed health inspection was on September 22, 2023, The facility is located in Henry county and provides senior and nursing home care.

MIDDLETOWN NURSING AND REHABILITATION CENTER Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Middletown Nursing And Rehabilitation Center below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: MIDDLETOWN NURSING AND REHABILITATION CENTER

Address: 131 S 10TH ST, MIDDLETOWN, IN 47356

Phone: (765) 354-2223

County: Henry (320)

Ownership Type: For profit - Corporation

Certified Beds: 45

Average Residents Per Day: 13.3 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: MOORE HEALTHCARE ENTERPRISES INC

First Approved Date: May 1, 1993

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 4 ()

QM Rating: 4 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: (2)

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.84467, LPN Staff Hours Per Day: 1.7811, RN Staff Hours Per Day: 0.6995, Licensed Staff Hours Per Day: 2.4806

Total Nurse Staff Hours Per Day, per resident: 5.32533

Weekend Nurse Staff Hours: 4.73621, Weekend RN Staff Hours: 0.6392

PT Staff Hours Per Day, per resident: 0.0000

Nurse Staff Turnover: , Nurse Turnover Note: 6

RN Turnover: , RN Turnover Note: 6

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 2.3734, Case Mix LPN Hours Per Day: 0.6467, Case Mix RN Hours Per Day: 0.3232

Adjusted Nurse Aide Hours Per Day, per resident: 2.44174, Adjusted LPN Hours Per Day: 2.0323, Adjusted RN Hours Per Day: 0.8155

Total Adjusted Nurse Hours Per Day, per resident: 5.02055

Adjusted Weekend Nurse Hours Per Day, per resident: 4.46515

Health Survey Dates and Scores: Cycle 1: 2023-09-22 (Score: 20), Cycle 2: 2022-08-05 (Score: 24), Cycle 3: 2019-11-04 (Score: 12)

Total Weighted Health Score: 20.000

Reported Incidents: 0, Substantiated Complaints: 3

Infection Control Citations: 1

Fines and Penalties: Number of Fines: 7, Total Fines in Dollars: 18423.06, Payment Denials Number: 0, Total Penalties Number: 7

Location and GPS: 131 S 10TH ST,MIDDLETOWN,IN,47356 (40.0533, -85.542)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-09-22

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-12

Citation on 2023-09-22

Type: Health, Deficiency: Electronically submit to CMS complete and accurate direct care staffing information, based on payroll and other verifiable and auditable data.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-12

Citation on 2022-03-14

Type: Health, Deficiency: Ensure staff are vaccinated for COVID-19

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2022-03-30

Citation on 2022-08-05

Type: Health, Deficiency: Honor the resident's right to receive visitors of his or her choosing, at the time of his or her choosing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-26

Citation on 2022-08-05

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-26

Citation on 2022-08-05

Type: Health, Deficiency: Have a registered nurse on duty 8 hours a day; and select a registered nurse to be the director of nurses on a full time basis.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-26

Citation on 2022-08-05

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-26

Citation on 2022-08-05

Type: Health, Deficiency: Perform COVID19 testing on residents and staff.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-26

Citation on 2021-11-05

Type: Health, Deficiency: Develop and implement policies and procedures to prevent abuse, neglect, and theft.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-19

Citation on 2021-11-05

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-19

Citation on 2021-11-05

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-19


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-11-06

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-22

Citation on 2023-11-06

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-22

Citation on 2023-11-06

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-22

Citation on 2023-11-06

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-22

Citation on 2023-11-06

Type: Fire Safety, Tag: 0361, Version: New

Description: Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-22

Citation on 2023-11-06

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-28

Citation on 2023-11-06

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-22

Citation on 2023-11-06

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-22

Citation on 2023-11-06

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-22

Citation on 2022-09-14

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0361, Version: New

Description: Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2022-09-14

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-15

Citation on 2019-12-26

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-09

Citation on 2019-12-26

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-09

Citation on 2019-12-26

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-09

Citation on 2019-12-26

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-09

Citation on 2019-12-26

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-09

Citation on 2019-12-26

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-09

Citation on 2019-12-26

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2020-03-25

Citation on 2019-12-26

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-09