Provider Name: SUMMIT HEALTH AND LIVING
Address: 701 S MAIN ST, SUMMITVILLE, IN 46070
Phone: (765) 203-2671
County: Madison (470)
Ownership Type: Government - County
Certified Beds: 34
Average Residents Per Day: 29.4 ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: PUTNAM COUNTY HOSPITAL
First Approved Date: September 30, 2015
Affiliated Entity: ()
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Resident
Sprinkler System Status: Yes
Overall Rating: 5 ()
Health Inspection Rating: 5 ()
QM Rating: 4 ()
Long Stay QM Rating: 2 ()
Short Stay QM Rating: 5 ()
Staffing Rating: 3 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 2.83947, LPN Staff Hours Per Day: 1.0327, RN Staff Hours Per Day: 0.4528, Licensed Staff Hours Per Day: 1.4856
Total Nurse Staff Hours Per Day, per resident: 4.32509
Weekend Nurse Staff Hours: 3.97817, Weekend RN Staff Hours: 0.3020
PT Staff Hours Per Day, per resident: 0.0159
Nurse Staff Turnover: 37.1, Nurse Turnover Note:
RN Turnover: , RN Turnover Note: 6
Admin Left Number: 2, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 2.4398, Case Mix LPN Hours Per Day: 0.7641, Case Mix RN Hours Per Day: 0.3196
Adjusted Nurse Aide Hours Per Day, per resident: 2.37098, Adjusted LPN Hours Per Day: 0.9973, Adjusted RN Hours Per Day: 0.5338
Total Adjusted Nurse Hours Per Day, per resident: 3.86901
Adjusted Weekend Nurse Hours Per Day, per resident: 3.55867
Health Survey Dates and Scores: Cycle 1: 2023-10-13 (Score: 8), Cycle 2: 2022-11-03 (Score: 8), Cycle 3: 2021-11-12 (Score: 8)
Total Weighted Health Score: 8.000
Reported Incidents: 1, Substantiated Complaints: 0
Infection Control Citations: 1
Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 975.00, Payment Denials Number: 0, Total Penalties Number: 1
Location and GPS: 701 S MAIN ST,SUMMITVILLE,IN,46070 (40.3320, -85.646)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Protect each resident from the wrongful use of the resident's belongings or money.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-23
Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-28
Type: Health, Deficiency: Ensure each resident receives an accurate assessment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-28
Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-10
Type: Health, Deficiency: Provide the appropriate treatment and services to a resident who displays or is diagnosed with dementia.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-10
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0015, Version: New
Description: Address subsistence needs for staff and patients.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-12-05
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-12-05
Type: Fire Safety, Tag: 0211, Version: New
Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-12-05
Type: Fire Safety, Tag: 0341, Version: New
Description: Install a fire alarm system that can be heard throughout the facility.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-12-05
Type: Fire Safety, Tag: 0500, Version: New
Description: Meet other general requirements that are deficient.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-12-05
Type: Fire Safety, Tag: 0511, Version: New
Description: Have properly installed electrical wiring and gas equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-12-05
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-12-05
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-12-05
Type: Fire Safety, Tag: 0034, Version: New
Description: Provide a means of sharing information on occupancy/needs.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0039, Version: New
Description: Conduct testing and exercise requirements.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0211, Version: New
Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0522, Version: New
Description: Have an externally vented heating system.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0753, Version: New
Description: Have restrictions on the use of highly flammable decorations.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0754, Version: New
Description: Provide properly sized and located linen or trash receptacles.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-26
Type: Fire Safety, Tag: 0036, Version: New
Description: Establish emergency prep training and testing.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0039, Version: New
Description: Conduct testing and exercise requirements.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0211, Version: New
Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0232, Version: New
Description: Have corridors or aisles that are unobstructed and are at least 8 feet in width.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0374, Version: New
Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0511, Version: New
Description: Have properly installed electrical wiring and gas equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-12-31