ACCURA HEALTHCARE OF CASCADE LLC Nursing Home


ACCURA HEALTHCARE OF CASCADE LLC (CCN: 165568) is a For profit - Limited Liability company facility located in CASCADE, IA (52033). The facility has an overall rating of 4/5, health inspection rating of 4/5, and a staffing rating of 4/5. It offers 46 certified beds and maintains an average of 38.7 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.28660 total hours per resident per day. It has been certified since January 1, 2006 and the last listed health inspection was on June 1, 2023, The facility is located in Dubuque county and provides senior and nursing home care.

ACCURA HEALTHCARE OF CASCADE LLC Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Accura Healthcare Of Cascade Llc below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: ACCURA HEALTHCARE OF CASCADE LLC

Address: 701 NORTH JOHNSON STREET NW, CASCADE, IA 52033

Phone: (563) 852-3277

County: Dubuque (300)

Ownership Type: For profit - Limited Liability company

Certified Beds: 46

Average Residents Per Day: 38.7 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: ACCURA HEALTHCARE OF CASCADE LLC

First Approved Date: January 1, 2006

Affiliated Entity: ACCURA HEALTHCARE (8)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 4 ()

QM Rating: 3 ()

Long Stay QM Rating: 1 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.96099, LPN Staff Hours Per Day: 0.4920, RN Staff Hours Per Day: 0.8335, Licensed Staff Hours Per Day: 1.3256

Total Nurse Staff Hours Per Day, per resident: 4.28660

Weekend Nurse Staff Hours: 3.93639, Weekend RN Staff Hours: 0.4178

PT Staff Hours Per Day, per resident: 0.0298

Nurse Staff Turnover: , Nurse Turnover Note: 6

RN Turnover: , RN Turnover Note: 6

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 2.1315, Case Mix LPN Hours Per Day: 0.7282, Case Mix RN Hours Per Day: 0.3514

Adjusted Nurse Aide Hours Per Day, per resident: 2.83006, Adjusted LPN Hours Per Day: 0.4985, Adjusted RN Hours Per Day: 0.8936

Total Adjusted Nurse Hours Per Day, per resident: 4.20757

Adjusted Weekend Nurse Hours Per Day, per resident: 3.86382

Health Survey Dates and Scores: Cycle 1: 2023-06-01 (Score: 8), Cycle 2: 2022-02-24 (Score: 0), Cycle 3: 2020-01-30 (Score: 12)

Total Weighted Health Score: 6.000

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 701 NORTH JOHNSON STREET NW,CASCADE,IA,52033 (42.3022, -91.019)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-06-01

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-02

Citation on 2020-01-30

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-14

Citation on 2020-01-30

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-14


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-06-06

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-03

Citation on 2023-06-06

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-03

Citation on 2023-06-06

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-03

Citation on 2023-06-06

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-03

Citation on 2023-06-06

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-03

Citation on 2023-06-06

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-03

Citation on 2023-06-06

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-03

Citation on 2022-03-02

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-05

Citation on 2022-03-02

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-10

Citation on 2022-03-02

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-07

Citation on 2022-03-02

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-11

Citation on 2022-03-02

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-16

Citation on 2022-03-02

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-09

Citation on 2022-03-02

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-03-02

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-31

Citation on 2022-03-02

Type: Fire Safety, Tag: 0922, Version: New

Description: Meet requirements for the use and maintenance of medical gas equipment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-05

Citation on 2020-02-04

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-17

Citation on 2020-02-04

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-10

Citation on 2020-02-04

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-18

Citation on 2020-02-04

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2020-03-06

Citation on 2020-02-04

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-10

Citation on 2020-02-04

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-04