Provider Name: LAWRENCE PRESBYTERIAN MANOR
Address: 1429 KASOLD DR, LAWRENCE, KS 66049
Phone: (785) 841-4262
County: Douglas (220)
Ownership Type: Non profit - Corporation
Certified Beds: 40
Average Residents Per Day: 37.4 ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: PRESBYTERIAN MANORS INC
First Approved Date: July 1, 1994
Affiliated Entity: PRESBYTERIAN MANORS OF MID-AMERICA (413)
Retirement Community: Y, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Resident
Sprinkler System Status: Yes
Overall Rating: 5 ()
Health Inspection Rating: 5 ()
QM Rating: 2 ()
Long Stay QM Rating: 1 ()
Short Stay QM Rating: 3 ()
Staffing Rating: 5 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 3.51141, LPN Staff Hours Per Day: 0.4714, RN Staff Hours Per Day: 1.1458, Licensed Staff Hours Per Day: 1.6173
Total Nurse Staff Hours Per Day, per resident: 5.12876
Weekend Nurse Staff Hours: 4.69112, Weekend RN Staff Hours: 0.5631
PT Staff Hours Per Day, per resident: 0.0209
Nurse Staff Turnover: 65.0, Nurse Turnover Note:
RN Turnover: 40.0, RN Turnover Note:
Admin Left Number: 0, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 2.0695, Case Mix LPN Hours Per Day: 0.6732, Case Mix RN Hours Per Day: 0.2704
Adjusted Nurse Aide Hours Per Day, per resident: 3.45665, Adjusted LPN Hours Per Day: 0.5168, Adjusted RN Hours Per Day: 1.5967
Total Adjusted Nurse Hours Per Day, per resident: 5.36506
Adjusted Weekend Nurse Hours Per Day, per resident: 4.90725
Health Survey Dates and Scores: Cycle 1: 2022-11-02 (Score: 8), Cycle 2: 2021-06-17 (Score: 0), Cycle 3: 2019-10-29 (Score: 20)
Total Weighted Health Score: 7.333
Reported Incidents: 0, Substantiated Complaints: 0
Infection Control Citations:
Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 650.00, Payment Denials Number: 0, Total Penalties Number: 1
Location and GPS: 1429 KASOLD DR,LAWRENCE,KS,66049 (38.9587, -95.279)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Respond appropriately to all alleged violations.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-12-01
Type: Health, Deficiency: Ensure that nurses and nurse aides have the appropriate competencies to care for every resident in a way that maximizes each resident's well being.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-12-01
Type: Health, Deficiency: Ensure necessary information is communicated to the resident, and receiving health care provider at the time of a planned discharge.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-11-28
Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-11-28
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-11-28
Type: Health, Deficiency: Ensure a licensed pharmacist perform a monthly drug regimen review, including the medical chart, following irregularity reporting guidelines in developed policies and procedures.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-11-28
Type: Health, Deficiency: Ensure each resident’s drug regimen must be free from unnecessary drugs.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-11-28
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0293, Version: New
Description: Have properly located and lighted "Exit" signs.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-20
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-20
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-20
Type: Fire Safety, Tag: 0355, Version: New
Description: Properly select, install, inspect, or maintain portable fire extinguishes.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-20
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-01-20
Type: Fire Safety, Tag: 0222, Version: New
Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0223, Version: New
Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0311, Version: New
Description: Have an enclosure around a vertical opening shaft.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0521, Version: New
Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0531, Version: New
Description: Have elevators that firefighters can control in the event of a fire.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-08-18
Type: Fire Safety, Tag: 0022, Version: New
Description: Establish policies and procedures for sheltering.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-09-18
Type: Fire Safety, Tag: 0293, Version: New
Description: Have properly located and lighted "Exit" signs.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-09-18
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-09-18
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-09-18
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-09-18
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-09-18
Type: Fire Safety, Tag: 0923, Version: New
Description: Have proper medical gas storage and administration areas.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-09-18