Provider Name: ARMA OPERATOR, LLC
Address: 605 E MELVIN STREET, ARMA, KS 66712
Phone: (620) 347-4103
County: Crawford (180)
Ownership Type: For profit - Corporation
Certified Beds: 45
Average Residents Per Day: 39.7 ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: ARMA OPERATOR LLC
First Approved Date: September 28, 1995
Affiliated Entity: MISSION HEALTH COMMUNITIES (354)
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Resident
Sprinkler System Status: Yes
Overall Rating: 3 ()
Health Inspection Rating: 3 ()
QM Rating: 4 ()
Long Stay QM Rating: 5 ()
Short Stay QM Rating: 4 ()
Staffing Rating: 4 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 2.53193, LPN Staff Hours Per Day: 0.2789, RN Staff Hours Per Day: 1.0684, Licensed Staff Hours Per Day: 1.3474
Total Nurse Staff Hours Per Day, per resident: 3.87937
Weekend Nurse Staff Hours: 3.55324, Weekend RN Staff Hours: 0.8278
PT Staff Hours Per Day, per resident: 0.0281
Nurse Staff Turnover: 49.0, Nurse Turnover Note:
RN Turnover: 22.2, RN Turnover Note:
Admin Left Number: 0, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 2.2419, Case Mix LPN Hours Per Day: 0.8098, Case Mix RN Hours Per Day: 0.4356
Adjusted Nurse Aide Hours Per Day, per resident: 2.30077, Adjusted LPN Hours Per Day: 0.2542, Adjusted RN Hours Per Day: 0.9241
Total Adjusted Nurse Hours Per Day, per resident: 3.50627
Adjusted Weekend Nurse Hours Per Day, per resident: 3.21150
Health Survey Dates and Scores: Cycle 1: 2023-03-21 (Score: 60), Cycle 2: 2021-08-26 (Score: 20), Cycle 3: 2020-01-02 (Score: 0)
Total Weighted Health Score: 36.667
Reported Incidents: 0, Substantiated Complaints: 0
Infection Control Citations:
Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0
Location and GPS: 605 E MELVIN STREET,ARMA,KS,66712 (37.5421, -94.698)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Reasonably accommodate the needs and preferences of each resident.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Honor the resident's right to voice grievances without discrimination or reprisal and the facility must establish a grievance policy and make prompt efforts to resolve grievances.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Respond appropriately to all alleged violations.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Dispose of garbage and refuse properly.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-04
Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-09-24
Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-09-24
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-09-24
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-09-24
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0222, Version: New
Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0324, Version: New
Description: Provide properly protected cooking facilities.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0355, Version: New
Description: Properly select, install, inspect, or maintain portable fire extinguishes.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0511, Version: New
Description: Have properly installed electrical wiring and gas equipment.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0741, Version: New
Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0753, Version: New
Description: Have restrictions on the use of highly flammable decorations.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-08
Type: Fire Safety, Tag: 0211, Version: New
Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-10-20
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-10-20
Type: Fire Safety, Tag: 0324, Version: New
Description: Provide properly protected cooking facilities.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-10-20
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-10-20
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-10-20
Type: Fire Safety, Tag: 0914, Version: New
Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-10-20
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-10-20
Type: Fire Safety, Tag: 0032, Version: New
Description: Provide primary/alternate means for communication.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-01-19
Type: Fire Safety, Tag: 0039, Version: New
Description: Conduct testing and exercise requirements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-01-19
Type: Fire Safety, Tag: 0211, Version: New
Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-01-19
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-01-19
Type: Fire Safety, Tag: 0914, Version: New
Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-01-19
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-01-19