VIA CHRISTI VILLAGE RIDGE Nursing Home


VIA CHRISTI VILLAGE RIDGE (CCN: 175539) is a Non profit - Corporation facility located in WICHITA, KS (67205). The facility has an overall rating of 3/5, health inspection rating of 3/5, and a staffing rating of 4/5. It offers 80 certified beds and maintains an average of 72.2 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.97274 total hours per resident per day. It has been certified since September 5, 2013 and the last listed health inspection was on April 11, 2022, The facility is located in Sedgwick county and provides senior and nursing home care.

VIA CHRISTI VILLAGE RIDGE Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Via Christi Village Ridge below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: VIA CHRISTI VILLAGE RIDGE

Address: 3636 NORTH RIDGE RD BLDG 400, WICHITA, KS 67205

Phone: (316) 462-7502

County: Sedgwick (860)

Ownership Type: Non profit - Corporation

Certified Beds: 80

Average Residents Per Day: 72.2 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: CORNERSTONE ASSISTED LIVING INC

First Approved Date: September 5, 2013

Affiliated Entity: ASCENSION LIVING (48)

Retirement Community: Y, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 3 ()

QM Rating: 4 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 3 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.09822, LPN Staff Hours Per Day: 0.9599, RN Staff Hours Per Day: 0.9145, Licensed Staff Hours Per Day: 1.8745

Total Nurse Staff Hours Per Day, per resident: 3.97274

Weekend Nurse Staff Hours: 3.51252, Weekend RN Staff Hours: 0.5334

PT Staff Hours Per Day, per resident: 0.0698

Nurse Staff Turnover: 60.9, Nurse Turnover Note:

RN Turnover: 62.5, RN Turnover Note:

Admin Left Number: 1, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.2208, Case Mix LPN Hours Per Day: 0.6865, Case Mix RN Hours Per Day: 0.2920

Adjusted Nurse Aide Hours Per Day, per resident: 1.92473, Adjusted LPN Hours Per Day: 1.0318, Adjusted RN Hours Per Day: 1.1802

Total Adjusted Nurse Hours Per Day, per resident: 3.91387

Adjusted Weekend Nurse Hours Per Day, per resident: 3.46047

Health Survey Dates and Scores: Cycle 1: 2022-04-11 (Score: 24), Cycle 2: 2020-10-08 (Score: 79), Cycle 3: 2019-05-20 (Score: 20)

Total Weighted Health Score: 41.667

Reported Incidents: 2, Substantiated Complaints: 1

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 39936.00, Payment Denials Number: 0, Total Penalties Number: 1

Location and GPS: 3636 NORTH RIDGE RD BLDG 400,WICHITA,KS,67205 (37.7493, -97.426)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-04-11

Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-18

Citation on 2022-04-11

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-18

Citation on 2022-04-11

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-18

Citation on 2022-04-11

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-18

Citation on 2022-04-11

Type: Health, Deficiency: Ensure each resident’s drug regimen must be free from unnecessary drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-18

Citation on 2022-04-11

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-18

Citation on 2022-12-14

Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.

Severity: J - Level 4: Immediate jeopardy to resident health or safety. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-14

Citation on 2020-10-08

Type: Health, Deficiency: Provide safe, appropriate dialysis care/services for a resident who requires such services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-08

Citation on 2021-05-18

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-06-16

Citation on 2019-05-20

Type: Health, Deficiency: Give residents notice of Medicaid/Medicare coverage and potential liability for services not covered.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-19

Citation on 2019-05-20

Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-19

Citation on 2019-05-20

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-19

Citation on 2019-05-20

Type: Health, Deficiency: Ensure services provided by the nursing facility meet professional standards of quality.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-19


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-03-08

Type: Fire Safety, Tag: 0006, Version: New

Description: Conduct risk assessment and an All-Hazards approach.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0020, Version: New

Description: Establish policies and procedures including evacuation.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0022, Version: New

Description: Establish policies and procedures for sheltering.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0024, Version: New

Description: Establish policies and procedures for volunteers.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0030, Version: New

Description: List the names and contact information of those in the facility.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0346, Version: New

Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0354, Version: New

Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0753, Version: New

Description: Have restrictions on the use of highly flammable decorations.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2022-03-08

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-04-07

Citation on 2020-12-03

Type: Fire Safety, Tag: 0161, Version: New

Description: Use approved construction type or materials.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-12-30

Citation on 2020-12-03

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-12-30

Citation on 2020-12-03

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-12-30

Citation on 2020-12-03

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-12-30

Citation on 2020-12-03

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-12-30

Citation on 2020-12-03

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-12-30

Citation on 2020-12-03

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-12-30

Citation on 2019-04-09

Type: Fire Safety, Tag: 0004, Version: New

Description: Develop and maintain an Emergency Preparedness Program (EP).

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0009, Version: New

Description: Include a process for Emergency Preparedness collaboration.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0020, Version: New

Description: Establish policies and procedures including evacuation.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0036, Version: New

Description: Establish emergency prep training and testing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03

Citation on 2019-04-09

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-03