BOULEVARD TEMPLE CARE CENTER, LLC Nursing Home


BOULEVARD TEMPLE CARE CENTER, LLC (CCN: 235498) is a For profit - Corporation facility located in DETROIT, MI (48208). The facility has an overall rating of 3/5, health inspection rating of 3/5, and a staffing rating of 4/5. It offers 124 certified beds and maintains an average of 95.3 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.61060 total hours per resident per day. It has been certified since May 3, 1990 and the last listed health inspection was on January 31, 2023, The facility is located in Wayne county and provides senior and nursing home care.

BOULEVARD TEMPLE CARE CENTER, LLC Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Boulevard Temple Care Center, Llc below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: BOULEVARD TEMPLE CARE CENTER, LLC

Address: 2567 WEST GRAND BOULEVARD, DETROIT, MI 48208

Phone: (313) 895-5340

County: Wayne (810)

Ownership Type: For profit - Corporation

Certified Beds: 124

Average Residents Per Day: 95.3 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: BOULEVARD TEMPLE CARE CENTER, LLC

First Approved Date: May 3, 1990

Affiliated Entity: CIENA HEALTHCARE/LAUREL HEALTH CARE (144)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: None

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 3 ()

QM Rating: 4 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 3 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.13717, LPN Staff Hours Per Day: 0.8442, RN Staff Hours Per Day: 0.6291, Licensed Staff Hours Per Day: 1.4734

Total Nurse Staff Hours Per Day, per resident: 3.61060

Weekend Nurse Staff Hours: 3.23736, Weekend RN Staff Hours: 0.4087

PT Staff Hours Per Day, per resident: 0.0391

Nurse Staff Turnover: 47.8, Nurse Turnover Note:

RN Turnover: 33.3, RN Turnover Note:

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 1.8829, Case Mix LPN Hours Per Day: 0.6623, Case Mix RN Hours Per Day: 0.2933

Adjusted Nurse Aide Hours Per Day, per resident: 2.31225, Adjusted LPN Hours Per Day: 0.9407, Adjusted RN Hours Per Day: 0.8081

Total Adjusted Nurse Hours Per Day, per resident: 4.00916

Adjusted Weekend Nurse Hours Per Day, per resident: 3.59472

Health Survey Dates and Scores: Cycle 1: 2023-01-31 (Score: 75), Cycle 2: 2021-10-25 (Score: 171), Cycle 3: 2020-09-24 (Score: 32)

Total Weighted Health Score: 99.833

Reported Incidents: 9, Substantiated Complaints: 10

Infection Control Citations:

Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 210972.75, Payment Denials Number: 1, Total Penalties Number: 3

Location and GPS: 2567 WEST GRAND BOULEVARD,DETROIT,MI,48208 (42.3634, -83.092)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-01-31

Type: Health, Deficiency: Provide basic life support, including CPR, prior to the arrival of emergency medical personnel , subject to physician orders and the resident’s advance directives.

Severity: J - Level 4: Immediate jeopardy to resident health or safety. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-31

Citation on 2022-08-31

Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-08-31

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: J - Level 4: Immediate jeopardy to resident health or safety. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-08-03

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Past Non-Compliance on 2022-07-05

Citation on 2021-10-25

Type: Health, Deficiency: Provide safe, appropriate dialysis care/services for a resident who requires such services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Honor the resident's right to be treated with respect and dignity and to retain and use personal possessions.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Reasonably accommodate the needs and preferences of each resident.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Protect each resident from the wrongful use of the resident's belongings or money.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Provide safe, appropriate pain management for a resident who requires such services.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Provide or obtain x-rays/tests when ordered and promptly tell the ordering practitioner of the results.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-10-25

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2021-04-12

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-05-03

Citation on 2020-09-24

Type: Health, Deficiency: Ensure that nurses and nurse aides have the appropriate competencies to care for every resident in a way that maximizes each resident's well being.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-24

Type: Health, Deficiency: Provide pharmaceutical services to meet the needs of each resident and employ or obtain the services of a licensed pharmacist.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-24

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-24

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-01-30

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2023-01-30

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2023-01-30

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2023-01-30

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2023-01-30

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2023-01-30

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2023-01-30

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2023-01-30

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2023-01-30

Type: Fire Safety, Tag: 0925, Version: New

Description: Ensure that sources of ignition are removed from patients receiving respiratory therapy.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-16

Citation on 2021-10-25

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0325, Version: New

Description: Have properly installed hallway dispensers for alcohol-based hand rub.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0346, Version: New

Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-08

Citation on 2021-10-25

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2021-12-27

Citation on 2021-10-25

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0912, Version: New

Description: Have power receptacles that are properly grounded.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-08

Citation on 2021-10-25

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0916, Version: New

Description: Have a battery powered remote alarm panel in a location accessible by operating personnel.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-25

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2021-12-27

Citation on 2021-10-25

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-23

Citation on 2021-10-14

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-22

Citation on 2020-09-24

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-05

Citation on 2020-09-24

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-11-05

Citation on 2020-09-24

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19

Citation on 2020-09-24

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-19