DJ JACOBETTI HOME FOR VETERANS Nursing Home


DJ JACOBETTI HOME FOR VETERANS (CCN: 235724) is a Government - State facility located in MARQUETTE, MI (49855). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 5/5. It offers 81 certified beds and maintains an average of 62.2 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.54960 total hours per resident per day. It has been certified since September 30, 2018 and the last listed health inspection was on November 29, 2023, The facility is located in Marquette county and provides senior and nursing home care.

DJ JACOBETTI HOME FOR VETERANS Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Dj Jacobetti Home For Veterans below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: DJ JACOBETTI HOME FOR VETERANS

Address: 425 FISHER ST, MARQUETTE, MI 49855

Phone: (906) 226-3576

County: Marquette (510)

Ownership Type: Government - State

Certified Beds: 81

Average Residents Per Day: 62.2 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: STATE OF MICHIGAN OFFICE OF FINANCIAL MANAGEMENT

First Approved Date: September 30, 2018

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 5 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: (2)

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.37915, LPN Staff Hours Per Day: 1.1255, RN Staff Hours Per Day: 1.0449, Licensed Staff Hours Per Day: 2.1704

Total Nurse Staff Hours Per Day, per resident: 4.54960

Weekend Nurse Staff Hours: 3.63836, Weekend RN Staff Hours: 0.5605

PT Staff Hours Per Day, per resident: 0.0147

Nurse Staff Turnover: 31.2, Nurse Turnover Note:

RN Turnover: 18.5, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 1.8616, Case Mix LPN Hours Per Day: 0.6369, Case Mix RN Hours Per Day: 0.2954

Adjusted Nurse Aide Hours Per Day, per resident: 2.60350, Adjusted LPN Hours Per Day: 1.3040, Adjusted RN Hours Per Day: 1.3324

Total Adjusted Nurse Hours Per Day, per resident: 5.13234

Adjusted Weekend Nurse Hours Per Day, per resident: 4.10438

Health Survey Dates and Scores: Cycle 1: 2023-11-29 (Score: 4), Cycle 2: 2022-10-19 (Score: 4), Cycle 3: 2021-07-01 (Score: 119)

Total Weighted Health Score: 23.167

Reported Incidents: 1, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 7614.75, Payment Denials Number: 0, Total Penalties Number: 1

Location and GPS: 425 FISHER ST,MARQUETTE,MI,49855 (46.5401, -87.402)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-11-29

Type: Health, Deficiency: Arrange for the provision of hospice services or assist the resident in transferring to a facility that will arrange for the provision of hospice services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-22

Citation on 2022-10-19

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-29

Citation on 2021-07-01

Type: Health, Deficiency: Honor the resident's right to receive visitors of his or her choosing, at the time of his or her choosing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Health, Deficiency: Honor the resident's right to organize and participate in resident/family groups in the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Health, Deficiency: Ensure services provided by the nursing facility meet professional standards of quality.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Health, Deficiency: Try different approaches before using a bed rail. If a bed rail is needed, the facility must (1) assess a resident for safety risk; (2) review these risks and benefits with the resident/representative; (3) get informed consent; and (4) Correctly install and maintain the bed rail.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Health, Deficiency: Ensure medication error rates are not 5 percent or greater.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: J - Level 4: Immediate jeopardy to resident health or safety. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-11-29

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-22

Citation on 2023-11-29

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-22

Citation on 2023-11-29

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-22

Citation on 2023-11-29

Type: Fire Safety, Tag: 0753, Version: New

Description: Have restrictions on the use of highly flammable decorations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-22

Citation on 2023-11-29

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2023-12-22

Citation on 2022-10-18

Type: Fire Safety, Tag: 0004, Version: New

Description: Develop and maintain an Emergency Preparedness Program (EP).

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-10-18

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-02

Citation on 2022-10-18

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-10-18

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-10-18

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-10-18

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-10-18

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-10-18

Type: Fire Safety, Tag: 0700, Version: New

Description: Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-10-18

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2022-10-18

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-21

Citation on 2021-06-30

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-06-30

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-06-30

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-06-30

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-06-30

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-06-30

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30