NEW BRIGHTON CARE CENTER Nursing Home


NEW BRIGHTON CARE CENTER (CCN: 245421) is a For profit - Corporation facility located in NEW BRIGHTON, MN (55112). The facility has an overall rating of 2/5, health inspection rating of 2/5, and a staffing rating of 4/5. It offers 57 certified beds and maintains an average of 41.8 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.57121 total hours per resident per day. It has been certified since February 1, 1987 and the last listed health inspection was on November 22, 2023, The facility is located in Ramsey county and provides senior and nursing home care.

NEW BRIGHTON CARE CENTER Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at New Brighton Care Center below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: NEW BRIGHTON CARE CENTER

Address: 805 SIXTH AVENUE NORTHWEST, NEW BRIGHTON, MN 55112

Phone: (651) 403-5241

County: Ramsey (610)

Ownership Type: For profit - Corporation

Certified Beds: 57

Average Residents Per Day: 41.8 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: NORTH CITIES HEALTH CARE, INC

First Approved Date: February 1, 1987

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 2 ()

Health Inspection Rating: 2 ()

QM Rating: 2 ()

Long Stay QM Rating: 2 ()

Short Stay QM Rating: 1 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.57704, LPN Staff Hours Per Day: 0.4515, RN Staff Hours Per Day: 1.5426, Licensed Staff Hours Per Day: 1.9941

Total Nurse Staff Hours Per Day, per resident: 4.57121

Weekend Nurse Staff Hours: 3.79713, Weekend RN Staff Hours: 0.9361

PT Staff Hours Per Day, per resident: 0.0537

Nurse Staff Turnover: 74.5, Nurse Turnover Note:

RN Turnover: 86.7, RN Turnover Note:

Admin Left Number: 2, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.0055, Case Mix LPN Hours Per Day: 0.6881, Case Mix RN Hours Per Day: 0.3101

Adjusted Nurse Aide Hours Per Day, per resident: 2.61776, Adjusted LPN Hours Per Day: 0.4842, Adjusted RN Hours Per Day: 1.8744

Total Adjusted Nurse Hours Per Day, per resident: 4.79681

Adjusted Weekend Nurse Hours Per Day, per resident: 3.98453

Health Survey Dates and Scores: Cycle 1: 2023-11-22 (Score: 84), Cycle 2: 2022-11-03 (Score: 44), Cycle 3: 2021-08-11 (Score: 16)

Total Weighted Health Score: 59.333

Reported Incidents: 9, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 3, Total Fines in Dollars: 37500.00, Payment Denials Number: 1, Total Penalties Number: 4

Location and GPS: 805 SIXTH AVENUE NORTHWEST,NEW BRIGHTON,MN,55112 (45.0628, -93.194)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-08-23

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-16

Citation on 2023-08-23

Type: Health, Deficiency: Develop, implement, and/or maintain an effective training program for all new and existing staff members.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-16

Citation on 2023-07-26

Type: Health, Deficiency: Ensure that nurses and nurse aides have the appropriate competencies to care for every resident in a way that maximizes each resident's well being.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-11

Citation on 2023-11-22

Type: Health, Deficiency: Allow residents to self-administer drugs if determined clinically appropriate.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-22

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-22

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-22

Type: Health, Deficiency: Provide safe, appropriate dialysis care/services for a resident who requires such services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-22

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-22

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-12

Citation on 2023-11-22

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-22

Type: Health, Deficiency: Develop and implement policies and procedures for flu and pneumonia vaccinations.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-22

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-12

Citation on 2023-02-07

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-31

Citation on 2022-04-18

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-05

Citation on 2022-11-03

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-03

Type: Health, Deficiency: Ensure necessary information is communicated to the resident, and receiving health care provider at the time of a planned discharge.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-04

Citation on 2022-11-03

Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-03

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-03

Type: Health, Deficiency: Post nurse staffing information every day.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-04

Citation on 2022-11-03

Type: Health, Deficiency: Set up an ongoing quality assessment and assurance group to review quality deficiencies and develop corrective plans of action.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-16

Citation on 2022-11-03

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-16

Citation on 2021-08-11

Type: Health, Deficiency: Honor the resident's right to request, refuse, and/or discontinue treatment, to participate in or refuse to participate in experimental research, and to formulate an advance directive.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-11

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-11

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-11-22

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-03

Citation on 2023-11-21

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-10

Citation on 2023-11-21

Type: Fire Safety, Tag: 0901, Version: New

Description: Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-10

Citation on 2023-11-21

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-10

Citation on 2023-11-21

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-02-10

Citation on 2023-11-21

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2023-11-21

Type: Fire Safety, Tag: 0926, Version: New

Description: Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-29

Citation on 2022-11-07

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-10

Citation on 2022-11-07

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-07

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-07

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-07

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-20

Citation on 2022-11-07

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-15

Citation on 2022-11-07

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-28

Citation on 2022-11-07

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-07

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-03

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-23

Citation on 2022-11-03

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-21

Citation on 2021-08-11

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-11

Type: Fire Safety, Tag: 0346, Version: New

Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-11

Type: Fire Safety, Tag: 0354, Version: New

Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-01

Citation on 2021-08-11

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-17

Citation on 2021-08-11

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-17