SHOLOM HOME WEST Nursing Home


SHOLOM HOME WEST (CCN: 245574) is a Non profit - Corporation facility located in SAINT LOUIS PARK, MN (55426). The facility has an overall rating of 5/5, health inspection rating of 4/5, and a staffing rating of 5/5. It offers 129 certified beds and maintains an average of 104. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 5.64230 total hours per resident per day. It has been certified since July 24, 1991 and the last listed health inspection was on September 21, 2023, The facility is located in Hennepin county and provides senior and nursing home care.

SHOLOM HOME WEST Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Sholom Home West below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: SHOLOM HOME WEST

Address: 3620 PHILLIPS PARKWAY SOUTH, SAINT LOUIS PARK, MN 55426

Phone: (952) 935-6311

County: Hennepin (260)

Ownership Type: Non profit - Corporation

Certified Beds: 129

Average Residents Per Day: 104. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: SHOLOM HOME WEST INC

First Approved Date: July 24, 1991

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 4 ()

QM Rating: 4 ()

Long Stay QM Rating: 2 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 3.24841, LPN Staff Hours Per Day: 1.5061, RN Staff Hours Per Day: 0.8876, Licensed Staff Hours Per Day: 2.3938

Total Nurse Staff Hours Per Day, per resident: 5.64230

Weekend Nurse Staff Hours: 5.07772, Weekend RN Staff Hours: 0.6309

PT Staff Hours Per Day, per resident: 0.0977

Nurse Staff Turnover: 27.8, Nurse Turnover Note:

RN Turnover: 36.4, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1090, Case Mix LPN Hours Per Day: 0.6612, Case Mix RN Hours Per Day: 0.3071

Adjusted Nurse Aide Hours Per Day, per resident: 3.13788, Adjusted LPN Hours Per Day: 1.6809, Adjusted RN Hours Per Day: 1.0890

Total Adjusted Nurse Hours Per Day, per resident: 5.77917

Adjusted Weekend Nurse Hours Per Day, per resident: 5.20090

Health Survey Dates and Scores: Cycle 1: 2023-09-21 (Score: 8), Cycle 2: 2021-07-15 (Score: 28), Cycle 3: 2019-05-09 (Score: 28)

Total Weighted Health Score: 20.333

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 9750.00, Payment Denials Number: 1, Total Penalties Number: 2

Location and GPS: 3620 PHILLIPS PARKWAY SOUTH,SAINT LOUIS PARK,MN,55426 (44.9388, -93.393)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-09-21

Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-08

Citation on 2023-09-21

Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-08

Citation on 2022-10-14

Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-25

Citation on 2021-07-15

Type: Health, Deficiency: Keep residents' personal and medical records private and confidential.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-07-15

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-05

Citation on 2021-07-15

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-07-15

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2019-05-09

Type: Health, Deficiency: Allow residents to self-administer drugs if determined clinically appropriate.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-07-17

Citation on 2019-05-09

Type: Health, Deficiency: Honor the resident's right to request, refuse, and/or discontinue treatment, to participate in or refuse to participate in experimental research, and to formulate an advance directive.

Severity: J - Level 4: Immediate jeopardy to resident health or safety. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-17

Citation on 2019-05-09

Type: Health, Deficiency: Ensure that each resident is free from the use of physical restraints, unless needed for medical treatment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-07-17

Citation on 2019-05-09

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-07-17

Citation on 2019-05-09

Type: Health, Deficiency: Provide safe, appropriate dialysis care/services for a resident who requires such services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-17

Citation on 2019-05-09

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-17


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-09-18

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-19

Citation on 2023-09-18

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-10

Citation on 2023-09-18

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-15

Citation on 2023-09-18

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-23

Citation on 2023-09-18

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-29

Citation on 2023-09-18

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-25

Citation on 2023-09-18

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-31

Citation on 2023-09-18

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-10

Citation on 2023-09-18

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-22

Citation on 2023-09-18

Type: Fire Safety, Tag: 0901, Version: New

Description: Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-22

Citation on 2023-09-18

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-18

Citation on 2021-07-13

Type: Fire Safety, Tag: 0221, Version: New

Description: Provide rooms that can be unlocked from inside without a key.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-05

Citation on 2021-07-13

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-05

Citation on 2021-07-13

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-05

Citation on 2021-07-13

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-05

Citation on 2021-07-13

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-05

Citation on 2021-07-13

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-30

Citation on 2021-07-13

Type: Fire Safety, Tag: 0926, Version: New

Description: Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-10

Citation on 2019-05-16

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-21

Citation on 2019-05-16

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-21

Citation on 2019-05-16

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-21

Citation on 2019-05-16

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-21

Citation on 2019-05-16

Type: Fire Safety, Tag: 0901, Version: New

Description: Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-21

Citation on 2019-05-16

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-21