HIGHLAND REHABILITATION & HEALTH CARE CENTER Nursing Home


HIGHLAND REHABILITATION & HEALTH CARE CENTER (CCN: 265167) is a For profit - Corporation facility located in KANSAS CITY, MO (64131). The facility has an overall rating of 4/5, health inspection rating of 3/5, and a staffing rating of 2/5. It offers 162 certified beds and maintains an average of 115. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 2.97519 total hours per resident per day. It has been certified since June 1, 1982 and the last listed health inspection was on July 7, 2023, The facility is located in Jackson county and provides senior and nursing home care.

HIGHLAND REHABILITATION & HEALTH CARE CENTER Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Highland Rehabilitation & Health Care Center below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: HIGHLAND REHABILITATION & HEALTH CARE CENTER

Address: 904 EAST 68TH STREET, KANSAS CITY, MO 64131

Phone: (816) 333-5485

County: Jackson (470)

Ownership Type: For profit - Corporation

Certified Beds: 162

Average Residents Per Day: 115. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: HIGHLAND NURSING AND REHABILITATION CENTER, LLC

First Approved Date: June 1, 1982

Affiliated Entity: TUTERA SENIOR LIVING & HEALTH CARE (531)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 3 ()

QM Rating: 5 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: (2)

Staffing Rating: 2 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.18052, LPN Staff Hours Per Day: 0.5266, RN Staff Hours Per Day: 0.2680, Licensed Staff Hours Per Day: 0.7946

Total Nurse Staff Hours Per Day, per resident: 2.97519

Weekend Nurse Staff Hours: 2.78437, Weekend RN Staff Hours: 0.2887

PT Staff Hours Per Day, per resident: 0.0082

Nurse Staff Turnover: 42.7, Nurse Turnover Note:

RN Turnover: 55.6, RN Turnover Note:

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 1.7214, Case Mix LPN Hours Per Day: 0.6590, Case Mix RN Hours Per Day: 0.3066

Adjusted Nurse Aide Hours Per Day, per resident: 2.58052, Adjusted LPN Hours Per Day: 0.5896, Adjusted RN Hours Per Day: 0.3293

Total Adjusted Nurse Hours Per Day, per resident: 3.48983

Adjusted Weekend Nurse Hours Per Day, per resident: 3.26600

Health Survey Dates and Scores: Cycle 1: 2023-07-07 (Score: 24), Cycle 2: 2021-11-23 (Score: 136), Cycle 3: 2019-05-17 (Score: 84)

Total Weighted Health Score: 71.333

Reported Incidents: 3, Substantiated Complaints: 2

Infection Control Citations: 2

Fines and Penalties: Number of Fines: 3, Total Fines in Dollars: 23405.14, Payment Denials Number: 1, Total Penalties Number: 4

Location and GPS: 904 EAST 68TH STREET,KANSAS CITY,MO,64131 (39.0042, -94.577)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-07

Type: Health, Deficiency: Give residents notice of Medicaid/Medicare coverage and potential liability for services not covered.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Health, Deficiency: PASARR screening for Mental disorders or Intellectual Disabilities

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Health, Deficiency: Notify the appropriate authorities when residents with MD or ID services has a significant change in condition.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Health, Deficiency: Ensure that feeding tubes are not used unless there is a medical reason and the resident agrees; and provide appropriate care for a resident with a feeding tube.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Health, Deficiency: Provide for the safe, appropriate administration of IV fluids for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-02-01

Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Past Non-Compliance on 2023-01-31

Citation on 2022-12-02

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2022-12-02

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2022-12-02

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-11

Citation on 2022-10-05

Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-23

Citation on 2022-08-04

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-08

Citation on 2022-07-15

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-15

Citation on 2021-11-23

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Notify the resident or the resident’s representative in writing how long the nursing home will hold the resident’s bed in cases of transfer to a hospital or therapeutic leave.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: PASARR screening for Mental disorders or Intellectual Disabilities

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Post nurse staffing information every day.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Ensure a licensed pharmacist perform a monthly drug regimen review, including the medical chart, following irregularity reporting guidelines in developed policies and procedures.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Have a policy regarding use and storage of foods brought to residents by family and other visitors.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Dispose of garbage and refuse properly.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2019-05-17

Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Notify the resident or the resident’s representative in writing how long the nursing home will hold the resident’s bed in cases of transfer to a hospital or therapeutic leave.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Create and put into place a plan for meeting the resident's most immediate needs within 48 hours of being admitted

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Ensure residents do not lose the ability to perform activities of daily living unless there is a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Provide activities to meet all resident's needs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Provide the appropriate treatment and services to a resident who displays or is diagnosed with mental disorder or psychosocial adjustment difficulty, or who has a history of trauma and/or post-traumatic stress disorder.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Ensure that residents are free from significant medication errors.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Have a policy regarding use and storage of foods brought to residents by family and other visitors.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-07

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2023-08-04

Citation on 2023-07-07

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Fire Safety, Tag: 0771, Version: New

Description: Ensure that smoke control systems are tested and documented in accordance with established engineering principles.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2023-07-07

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-04

Citation on 2021-11-23

Type: Fire Safety, Tag: 0036, Version: New

Description: Establish emergency prep training and testing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0100, Version: New

Description: Meet other general requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0331, Version: New

Description: Construct fire resistant interior walls.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0343, Version: New

Description: Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0347, Version: New

Description: Properly provide smoke detection systems in areas open to corridors.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0541, Version: New

Description: Install properly constructed and protected linen or trash chutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0771, Version: New

Description: Ensure that smoke control systems are tested and documented in accordance with established engineering principles.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0919, Version: New

Description: Meet requirements for the use of electrical equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2021-11-23

Type: Fire Safety, Tag: 0926, Version: New

Description: Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-07

Citation on 2019-05-17

Type: Fire Safety, Tag: 0001, Version: New

Description: Establish an Emergency Preparedness Program (EP).

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0300, Version: New

Description: Meet other general requirements that are deficient.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0354, Version: New

Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0900, Version: New

Description: Meet Health Care Facilities Code mechanical requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26

Citation on 2019-05-17

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-06-26