SUMNER PLACE Nursing Home


SUMNER PLACE (CCN: 285002) is a Non profit - Corporation facility located in LINCOLN, NE (68502). The facility has an overall rating of 5/5, health inspection rating of 4/5, and a staffing rating of 4/5. It offers 104 certified beds and maintains an average of 96.1 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.03817 total hours per resident per day. It has been certified since January 1, 1967 and the last listed health inspection was on July 25, 2023, The facility is located in Lancaster county and provides senior and nursing home care.

SUMNER PLACE Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Sumner Place below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: SUMNER PLACE

Address: 1750 SOUTH 20TH STREET, LINCOLN, NE 68502

Phone: (402) 475-6791

County: Lancaster (540)

Ownership Type: Non profit - Corporation

Certified Beds: 104

Average Residents Per Day: 96.1 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: VSL LINCOLN SUMNER LLC

First Approved Date: January 1, 1967

Affiliated Entity: VETTER SENIOR LIVING (547)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 4 ()

QM Rating: 5 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: (2)

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.82445, LPN Staff Hours Per Day: 0.5547, RN Staff Hours Per Day: 0.6590, Licensed Staff Hours Per Day: 1.2137

Total Nurse Staff Hours Per Day, per resident: 4.03817

Weekend Nurse Staff Hours: 3.61289, Weekend RN Staff Hours: 0.4912

PT Staff Hours Per Day, per resident: 0.0163

Nurse Staff Turnover: 49.2, Nurse Turnover Note:

RN Turnover: 23.5, RN Turnover Note:

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 2.0846, Case Mix LPN Hours Per Day: 0.6527, Case Mix RN Hours Per Day: 0.2816

Adjusted Nurse Aide Hours Per Day, per resident: 2.76029, Adjusted LPN Hours Per Day: 0.6271, Adjusted RN Hours Per Day: 0.8817

Total Adjusted Nurse Hours Per Day, per resident: 4.21619

Adjusted Weekend Nurse Hours Per Day, per resident: 3.77217

Health Survey Dates and Scores: Cycle 1: 2023-07-25 (Score: 12), Cycle 2: 2022-04-19 (Score: 24), Cycle 3: 2020-09-08 (Score: 20)

Total Weighted Health Score: 17.333

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 1750 SOUTH 20TH STREET,LINCOLN,NE,68502 (40.7947, -96.692)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-25

Type: Health, Deficiency: Ensure that feeding tubes are not used unless there is a medical reason and the resident agrees; and provide appropriate care for a resident with a feeding tube.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-08

Citation on 2023-07-25

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-08

Citation on 2023-07-25

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-08

Citation on 2022-04-19

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-27

Citation on 2022-04-19

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-27

Citation on 2022-04-19

Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-27

Citation on 2022-04-19

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-27

Citation on 2020-09-08

Type: Health, Deficiency: Give residents notice of Medicaid/Medicare coverage and potential liability for services not covered.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-08

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-08

Type: Health, Deficiency: Ensure each resident must receive and the facility must provide necessary behavioral health care and services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-08

Type: Health, Deficiency: Provide each resident with a nourishing, palatable, well-balanced diet that meets his or her daily nutritional and special dietary needs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-20

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0500, Version: New

Description: Meet other general requirements that are deficient.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0754, Version: New

Description: Provide properly sized and located linen or trash receptacles.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0919, Version: New

Description: Meet requirements for the use of electrical equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-20

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2022-04-14

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-15

Citation on 2022-04-14

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-15

Citation on 2022-04-14

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2022-06-15

Citation on 2022-04-14

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-15

Citation on 2020-09-03

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-03

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-03

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16

Citation on 2020-09-03

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-16