Provider Name: NEWPORT HOUSE
Address: 6798 N 67TH PLAZA, OMAHA, NE 68152
Phone: (402) 572-2595
County: Douglas (270)
Ownership Type: Non profit - Corporation
Certified Beds: 96
Average Residents Per Day: 91.3 ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: IMMANUEL LONG TERM CARE
First Approved Date: December 30, 1988
Affiliated Entity: IMMANUEL (281)
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Resident
Sprinkler System Status: Yes
Overall Rating: 5 ()
Health Inspection Rating: 4 ()
QM Rating: 5 ()
Long Stay QM Rating: 3 ()
Short Stay QM Rating: 5 ()
Staffing Rating: 5 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 2.89618, LPN Staff Hours Per Day: 0.4646, RN Staff Hours Per Day: 1.3272, Licensed Staff Hours Per Day: 1.7919
Total Nurse Staff Hours Per Day, per resident: 4.68810
Weekend Nurse Staff Hours: 4.08666, Weekend RN Staff Hours: 1.0969
PT Staff Hours Per Day, per resident: 0.1175
Nurse Staff Turnover: 50.4, Nurse Turnover Note:
RN Turnover: 22.6, RN Turnover Note:
Admin Left Number: 1, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 2.0727, Case Mix LPN Hours Per Day: 0.6913, Case Mix RN Hours Per Day: 0.3298
Adjusted Nurse Aide Hours Per Day, per resident: 2.84663, Adjusted LPN Hours Per Day: 0.4960, Adjusted RN Hours Per Day: 1.5160
Total Adjusted Nurse Hours Per Day, per resident: 4.77611
Adjusted Weekend Nurse Hours Per Day, per resident: 4.16339
Health Survey Dates and Scores: Cycle 1: 2023-07-25 (Score: 16), Cycle 2: 2022-05-02 (Score: 28), Cycle 3: 2020-08-26 (Score: 0)
Total Weighted Health Score: 17.333
Reported Incidents: 0, Substantiated Complaints: 0
Infection Control Citations:
Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0
Location and GPS: 6798 N 67TH PLAZA,OMAHA,NE,68152 (41.2096, -96.156)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-07
Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Health, Deficiency: Create and put into place a plan for meeting the resident's most immediate needs within 48 hours of being admitted
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Health, Deficiency: Provide enough food/fluids to maintain a resident's health.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Health, Deficiency: Ensure menus must meet the nutritional needs of residents, be prepared in advance, be followed, be updated, be reviewed by dietician, and meet the needs of the resident.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0341, Version: New
Description: Install a fire alarm system that can be heard throughout the facility.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0354, Version: New
Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0914, Version: New
Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-08-31
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0222, Version: New
Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0223, Version: New
Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0293, Version: New
Description: Have properly located and lighted "Exit" signs.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0324, Version: New
Description: Provide properly protected cooking facilities.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0346, Version: New
Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0347, Version: New
Description: Properly provide smoke detection systems in areas open to corridors.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0354, Version: New
Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0355, Version: New
Description: Properly select, install, inspect, or maintain portable fire extinguishes.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0374, Version: New
Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0911, Version: New
Description: Meet requirements for the installation and maintenance of electrical systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0921, Version: New
Description: Ensure that testing and maintenance of electrical equipment is performed.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0922, Version: New
Description: Meet requirements for the use and maintenance of medical gas equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-10
Type: Fire Safety, Tag: 0225, Version: New
Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-10-01
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-10-01
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-10-01
Type: Fire Safety, Tag: 0919, Version: New
Description: Meet requirements for the use of electrical equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-10-01
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-10-01
Type: Fire Safety, Tag: 0922, Version: New
Description: Meet requirements for the use and maintenance of medical gas equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-10-01