NEWPORT HOUSE Nursing Home


NEWPORT HOUSE (CCN: 285085) is a Non profit - Corporation facility located in OMAHA, NE (68152). The facility has an overall rating of 5/5, health inspection rating of 4/5, and a staffing rating of 5/5. It offers 96 certified beds and maintains an average of 91.3 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.68810 total hours per resident per day. It has been certified since December 30, 1988 and the last listed health inspection was on July 25, 2023, The facility is located in Douglas county and provides senior and nursing home care.

NEWPORT HOUSE Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Newport House below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: NEWPORT HOUSE

Address: 6798 N 67TH PLAZA, OMAHA, NE 68152

Phone: (402) 572-2595

County: Douglas (270)

Ownership Type: Non profit - Corporation

Certified Beds: 96

Average Residents Per Day: 91.3 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: IMMANUEL LONG TERM CARE

First Approved Date: December 30, 1988

Affiliated Entity: IMMANUEL (281)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 4 ()

QM Rating: 5 ()

Long Stay QM Rating: 3 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.89618, LPN Staff Hours Per Day: 0.4646, RN Staff Hours Per Day: 1.3272, Licensed Staff Hours Per Day: 1.7919

Total Nurse Staff Hours Per Day, per resident: 4.68810

Weekend Nurse Staff Hours: 4.08666, Weekend RN Staff Hours: 1.0969

PT Staff Hours Per Day, per resident: 0.1175

Nurse Staff Turnover: 50.4, Nurse Turnover Note:

RN Turnover: 22.6, RN Turnover Note:

Admin Left Number: 1, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.0727, Case Mix LPN Hours Per Day: 0.6913, Case Mix RN Hours Per Day: 0.3298

Adjusted Nurse Aide Hours Per Day, per resident: 2.84663, Adjusted LPN Hours Per Day: 0.4960, Adjusted RN Hours Per Day: 1.5160

Total Adjusted Nurse Hours Per Day, per resident: 4.77611

Adjusted Weekend Nurse Hours Per Day, per resident: 4.16339

Health Survey Dates and Scores: Cycle 1: 2023-07-25 (Score: 16), Cycle 2: 2022-05-02 (Score: 28), Cycle 3: 2020-08-26 (Score: 0)

Total Weighted Health Score: 17.333

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 6798 N 67TH PLAZA,OMAHA,NE,68152 (41.2096, -96.156)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-25

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-07

Citation on 2022-05-02

Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Health, Deficiency: Create and put into place a plan for meeting the resident's most immediate needs within 48 hours of being admitted

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Health, Deficiency: Provide enough food/fluids to maintain a resident's health.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Health, Deficiency: Ensure menus must meet the nutritional needs of residents, be prepared in advance, be followed, be updated, be reviewed by dietician, and meet the needs of the resident.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-19

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-19

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-19

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-19

Type: Fire Safety, Tag: 0354, Version: New

Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-19

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-19

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-19

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-19

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-19

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2022-05-02

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0346, Version: New

Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0347, Version: New

Description: Properly provide smoke detection systems in areas open to corridors.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0354, Version: New

Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0921, Version: New

Description: Ensure that testing and maintenance of electrical equipment is performed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2022-05-02

Type: Fire Safety, Tag: 0922, Version: New

Description: Meet requirements for the use and maintenance of medical gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-10

Citation on 2020-08-21

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-01

Citation on 2020-08-21

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-01

Citation on 2020-08-21

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-01

Citation on 2020-08-21

Type: Fire Safety, Tag: 0919, Version: New

Description: Meet requirements for the use of electrical equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-01

Citation on 2020-08-21

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-01

Citation on 2020-08-21

Type: Fire Safety, Tag: 0922, Version: New

Description: Meet requirements for the use and maintenance of medical gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-10-01