PRESTIGE CARE CENTER OF PLATTSMOUTH Nursing Home


PRESTIGE CARE CENTER OF PLATTSMOUTH (CCN: 285104) is a For profit - Limited Liability company facility located in PLATTSMOUTH, NE (68048). The facility has an overall rating of 1/5, health inspection rating of 1/5, and a staffing rating of 1/5. It offers 111 certified beds and maintains an average of 77.7 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.18144 total hours per resident per day. It has been certified since April 18, 1991 and the last listed health inspection was on January 22, 2024, The facility is located in Cass county and provides senior and nursing home care.

PRESTIGE CARE CENTER OF PLATTSMOUTH Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Prestige Care Center Of Plattsmouth below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: PRESTIGE CARE CENTER OF PLATTSMOUTH

Address: 602 SOUTH 18TH STREET, PLATTSMOUTH, NE 68048

Phone: (402) 296-2800

County: Cass (120)

Ownership Type: For profit - Limited Liability company

Certified Beds: 111

Average Residents Per Day: 77.7 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: PLATTSMOUTH OPERATIONS LLC

First Approved Date: April 18, 1991

Affiliated Entity: PRESTIGE CARE CENTER (602)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 1 ()

Health Inspection Rating: 1 ()

QM Rating: 3 ()

Long Stay QM Rating: 2 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 1 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.25490, LPN Staff Hours Per Day: 0.5789, RN Staff Hours Per Day: 0.3475, Licensed Staff Hours Per Day: 0.9265

Total Nurse Staff Hours Per Day, per resident: 3.18144

Weekend Nurse Staff Hours: 3.08534, Weekend RN Staff Hours: 0.2365

PT Staff Hours Per Day, per resident: 0.0561

Nurse Staff Turnover: 80.7, Nurse Turnover Note:

RN Turnover: 71.4, RN Turnover Note:

Admin Left Number: 2, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 1.9862, Case Mix LPN Hours Per Day: 0.6961, Case Mix RN Hours Per Day: 0.3169

Adjusted Nurse Aide Hours Per Day, per resident: 2.31285, Adjusted LPN Hours Per Day: 0.6137, Adjusted RN Hours Per Day: 0.4132

Total Adjusted Nurse Hours Per Day, per resident: 3.34346

Adjusted Weekend Nurse Hours Per Day, per resident: 3.24247

Health Survey Dates and Scores: Cycle 1: 2024-01-22 (Score: 48), Cycle 2: 2023-01-24 (Score: 168), Cycle 3: 2021-09-14 (Score: 68)

Total Weighted Health Score: 91.333

Reported Incidents: 3, Substantiated Complaints: 4

Infection Control Citations:

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 650.00, Payment Denials Number: 1, Total Penalties Number: 2

Location and GPS: 602 SOUTH 18TH STREET,PLATTSMOUTH,NE,68048 (41.0048, -95.901)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2024-01-22

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-06

Citation on 2024-01-22

Type: Health, Deficiency: Coordinate assessments with the pre-admission screening and resident review program; and referring for services as needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-22

Type: Health, Deficiency: Provide medically-related social services to help each resident achieve the highest possible quality of life.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-22

Type: Health, Deficiency: Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-29

Citation on 2024-01-22

Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-01-29

Citation on 2022-09-19

Type: Health, Deficiency: Make sure that a working call system is available in each resident's bathroom and bathing area.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-28

Citation on 2023-01-24

Type: Health, Deficiency: Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decline/room, etc.) that affect the resident.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Ensure residents do not lose the ability to perform activities of daily living unless there is a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Provide activities to meet all resident's needs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Employ sufficient staff with the appropriate competencies and skills sets to carry out the functions of the food and nutrition service, including a qualified dietician.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Provide sufficient support personnel to safely and effectively carry out the functions of the food and nutrition service.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Have a plan that describes the process for conducting QAPI and QAA activities.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Have enough outside ventilation via a window or mechanical ventilation, or both.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2023-01-24

Type: Health, Deficiency: Provide enough nursing staff every day to meet the needs of every resident; and have a licensed nurse in charge on each shift.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-10

Citation on 2021-09-14

Type: Health, Deficiency: Not hire anyone with a finding of abuse, neglect, exploitation, or theft.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Ensure each resident’s drug regimen must be free from unnecessary drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Provide sufficient support personnel to safely and effectively carry out the functions of the food and nutrition service.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-09-14

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2024-01-25

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0111, Version: New

Description: Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0500, Version: New

Description: Meet other general requirements that are deficient.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0700, Version: New

Description: Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0919, Version: New

Description: Meet requirements for the use of electrical equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0921, Version: New

Description: Ensure that testing and maintenance of electrical equipment is performed.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-02-07

Citation on 2024-01-25

Type: Fire Safety, Tag: 0922, Version: New

Description: Meet requirements for the use and maintenance of medical gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2024-03-07

Citation on 2023-01-20

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0331, Version: New

Description: Construct fire resistant interior walls.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0500, Version: New

Description: Meet other general requirements that are deficient.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0919, Version: New

Description: Meet requirements for the use of electrical equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2023-01-20

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-28

Citation on 2021-09-08

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0300, Version: New

Description: Meet other general requirements that are deficient.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29

Citation on 2021-09-08

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-29