GOOD SAMARITAN SOCIETY - AUBURN Nursing Home


GOOD SAMARITAN SOCIETY - AUBURN (CCN: 285112) is a Non profit - Corporation facility located in AUBURN, NE (68305). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 4/5. It offers 102 certified beds and maintains an average of 58.4 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.39020 total hours per resident per day. It has been certified since December 1, 1991 and the last listed health inspection was on August 2, 2023, The facility is located in Nemaha county and provides senior and nursing home care.

GOOD SAMARITAN SOCIETY - AUBURN Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Good Samaritan Society - Auburn below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: GOOD SAMARITAN SOCIETY - AUBURN

Address: 1322 U STREET, AUBURN, NE 68305

Phone: (402) 274-4954

County: Nemaha (630)

Ownership Type: Non profit - Corporation

Certified Beds: 102

Average Residents Per Day: 58.4 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: THE EVANGELICAL LUTHERAN GOOD SAMARITAN SOCIETY

First Approved Date: December 1, 1991

Affiliated Entity: EVANGELICAL LUTHERAN GOOD SAMARITAN SOCIETY (214)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Both

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 5 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.08379, LPN Staff Hours Per Day: 0.8760, RN Staff Hours Per Day: 0.4303, Licensed Staff Hours Per Day: 1.3064

Total Nurse Staff Hours Per Day, per resident: 3.39020

Weekend Nurse Staff Hours: 2.98109, Weekend RN Staff Hours: 0.2051

PT Staff Hours Per Day, per resident: 0.0506

Nurse Staff Turnover: 41.7, Nurse Turnover Note:

RN Turnover: 25.0, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 1.8739, Case Mix LPN Hours Per Day: 0.6495, Case Mix RN Hours Per Day: 0.2703

Adjusted Nurse Aide Hours Per Day, per resident: 2.26543, Adjusted LPN Hours Per Day: 0.9952, Adjusted RN Hours Per Day: 0.5999

Total Adjusted Nurse Hours Per Day, per resident: 3.82496

Adjusted Weekend Nurse Hours Per Day, per resident: 3.36338

Health Survey Dates and Scores: Cycle 1: 2023-08-02 (Score: 0), Cycle 2: 2022-03-08 (Score: 24), Cycle 3: 2020-02-11 (Score: 40)

Total Weighted Health Score: 14.667

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 1322 U STREET,AUBURN,NE,68305 (40.3888, -95.853)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-03-08

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2022-03-08

Type: Health, Deficiency: Coordinate assessments with the pre-admission screening and resident review program; and referring for services as needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2022-03-08

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2022-03-08

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2020-02-11

Type: Health, Deficiency: Allow residents to self-administer drugs if determined clinically appropriate.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-11

Type: Health, Deficiency: Honor the resident's right to request, refuse, and/or discontinue treatment, to participate in or refuse to participate in experimental research, and to formulate an advance directive.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-11

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-11

Type: Health, Deficiency: Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-11

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-11

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-08-07

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0200, Version: New

Description: Meet other general requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0500, Version: New

Description: Meet other general requirements that are deficient.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-08-07

Type: Fire Safety, Tag: 0919, Version: New

Description: Meet requirements for the use of electrical equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2022-03-08

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2022-03-08

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2022-03-08

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2022-03-08

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2022-03-08

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2022-03-08

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0041, Version: New

Description: Implement emergency and standby power systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2020-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0161, Version: New

Description: Use approved construction type or materials.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0919, Version: New

Description: Meet requirements for the use of electrical equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27

Citation on 2020-02-05

Type: Fire Safety, Tag: 0922, Version: New

Description: Meet requirements for the use and maintenance of medical gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-27