NEURORESTORATIVE 4 KIDS Nursing Home


NEURORESTORATIVE 4 KIDS (CCN: 295084) is a For profit - Corporation facility located in LAS VEGAS, NV (89128). The facility has an overall rating of 4/5, health inspection rating of 4/5, and a staffing rating of 4/5. It offers 35 certified beds and maintains an average of 33.4 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 7.11478 total hours per resident per day. It has been certified since April 19, 2005 and the last listed health inspection was on March 10, 2023, The facility is located in Clark county and provides senior and nursing home care.

NEURORESTORATIVE 4 KIDS Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Neurorestorative 4 Kids below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: NEURORESTORATIVE 4 KIDS

Address: 7690 CARMEN BLVD, LAS VEGAS, NV 89128

Phone: (702) 255-7399

County: Clark (010)

Ownership Type: For profit - Corporation

Certified Beds: 35

Average Residents Per Day: 33.4 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: CAREMERIDIAN LLC

First Approved Date: April 19, 2005

Affiliated Entity: NEURORESTORATIVE (367)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: None

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 4 ()

QM Rating: 4 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: (2)

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 4.04925, LPN Staff Hours Per Day: 0.9464, RN Staff Hours Per Day: 2.1190, Licensed Staff Hours Per Day: 3.0655

Total Nurse Staff Hours Per Day, per resident: 7.11478

Weekend Nurse Staff Hours: 7.09720, Weekend RN Staff Hours: 2.1671

PT Staff Hours Per Day, per resident: 0.0000

Nurse Staff Turnover: , Nurse Turnover Note: 6

RN Turnover: , RN Turnover Note: 6

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 2.3996, Case Mix LPN Hours Per Day: 0.9939, Case Mix RN Hours Per Day: 1.2469

Adjusted Nurse Aide Hours Per Day, per resident: 3.43767, Adjusted LPN Hours Per Day: 0.7027, Adjusted RN Hours Per Day: 0.6403

Total Adjusted Nurse Hours Per Day, per resident: 4.83264

Adjusted Weekend Nurse Hours Per Day, per resident: 4.82070

Health Survey Dates and Scores: Cycle 1: 2023-03-10 (Score: 52), Cycle 2: 2021-09-02 (Score: 16), Cycle 3: 2019-07-03 (Score: 64)

Total Weighted Health Score: 42.000

Reported Incidents: 3, Substantiated Complaints: 0

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 5980.00, Payment Denials Number: 0, Total Penalties Number: 2

Location and GPS: 7690 CARMEN BLVD,LAS VEGAS,NV,89128 (36.1850, -115.269)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-03-10

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Ensure services provided by the nursing facility meet professional standards of quality.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Ensure that feeding tubes are not used unless there is a medical reason and the resident agrees; and provide appropriate care for a resident with a feeding tube.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Provide pharmaceutical services to meet the needs of each resident and employ or obtain the services of a licensed pharmacist.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Ensure each resident’s drug regimen must be free from unnecessary drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Ensure medication error rates are not 5 percent or greater.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Ensure menus must meet the nutritional needs of residents, be prepared in advance, be followed, be updated, be reviewed by dietician, and meet the needs of the resident.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-03-10

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-17

Citation on 2023-01-05

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-10

Citation on 2022-09-01

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-30

Citation on 2021-09-02

Type: Health, Deficiency: Ensure that feeding tubes are not used unless there is a medical reason and the resident agrees; and provide appropriate care for a resident with a feeding tube.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-08

Citation on 2021-09-02

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-08

Citation on 2021-12-22

Type: Health, Deficiency: Develop and implement policies and procedures to prevent abuse, neglect, and theft.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-14

Citation on 2021-12-22

Type: Health, Deficiency: Develop and implement policies and procedures to ensure (1) employees report any suspicion of a crime against any resident, according to timelines; (2) post the notice of employee rights; and (3) prohibit and prevent retaliation for reporting.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-01-14

Citation on 2019-07-03

Type: Health, Deficiency: Notify the resident or the resident’s representative in writing how long the nursing home will hold the resident’s bed in cases of transfer to a hospital or therapeutic leave.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Assess the resident completely in a timely manner when first admitted, and then periodically, at least every 12 months.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Ensure that feeding tubes are not used unless there is a medical reason and the resident agrees; and provide appropriate care for a resident with a feeding tube.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Provide safe, appropriate pain management for a resident who requires such services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Ensure each resident’s drug regimen must be free from unnecessary drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Ensure medication error rates are not 5 percent or greater.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15

Citation on 2019-07-03

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-08-15


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-03-09

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2023-03-09

Type: Fire Safety, Tag: 0023, Version: New

Description: Establish policies and procedures for medical documentation.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2023-03-09

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2023-03-09

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2023-03-09

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2023-03-09

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2023-03-09

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2023-03-09

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2023-03-09

Type: Fire Safety, Tag: 0900, Version: New

Description: Meet Health Care Facilities Code mechanical requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-21

Citation on 2021-09-01

Type: Fire Safety, Tag: 0006, Version: New

Description: Conduct risk assessment and an All-Hazards approach.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0020, Version: New

Description: Establish policies and procedures including evacuation.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0029, Version: New

Description: Develop a communication plan.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0030, Version: New

Description: List the names and contact information of those in the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0031, Version: New

Description: Provide emergency officials' contact information.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0232, Version: New

Description: Have corridors or aisles that are unobstructed and are at least 8 feet in width.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0331, Version: New

Description: Construct fire resistant interior walls.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0344, Version: New

Description: Have an alternate power supply for its alarm system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0751, Version: New

Description: Have restrictions on the use of flammable curtains.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0917, Version: New

Description: Ensure electrical receptacles or cover plates have distinctive color or marking.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2021-09-01

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-11-04

Citation on 2019-07-02

Type: Fire Safety, Tag: 0006, Version: New

Description: Conduct risk assessment and an All-Hazards approach.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0009, Version: New

Description: Include a process for Emergency Preparedness collaboration.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0013, Version: New

Description: Develop Emergency Preparedness policies and procedures.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0024, Version: New

Description: Establish policies and procedures for volunteers.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0036, Version: New

Description: Establish emergency prep training and testing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13

Citation on 2019-07-02

Type: Fire Safety, Tag: 0921, Version: New

Description: Ensure that testing and maintenance of electrical equipment is performed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-09-13