ELCOR NURSING AND REHABILITATION CENTER Nursing Home


ELCOR NURSING AND REHABILITATION CENTER (CCN: 335053) is a For profit - Limited Liability company facility located in HORSEHEADS, NY (14845). The facility has an overall rating of 3/5, health inspection rating of 3/5, and a staffing rating of 2/5. It offers 305 certified beds and maintains an average of 255. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.30004 total hours per resident per day. It has been certified since January 1, 1967 and the last listed health inspection was on December 1, 2023, The facility is located in Chemung county and provides senior and nursing home care.

ELCOR NURSING AND REHABILITATION CENTER Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Elcor Nursing And Rehabilitation Center below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: ELCOR NURSING AND REHABILITATION CENTER

Address: 48 COLONIAL DRIVE, HORSEHEADS, NY 14845

Phone: (607) 739-0304

County: Chemung (070)

Ownership Type: For profit - Limited Liability company

Certified Beds: 305

Average Residents Per Day: 255. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: ELCOR OPERATING COMPANY LLC

First Approved Date: January 1, 1967

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 3 ()

QM Rating: 2 ()

Long Stay QM Rating: 2 ()

Short Stay QM Rating: 2 ()

Staffing Rating: 2 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.17824, LPN Staff Hours Per Day: 0.7221, RN Staff Hours Per Day: 0.3996, Licensed Staff Hours Per Day: 1.1218

Total Nurse Staff Hours Per Day, per resident: 3.30004

Weekend Nurse Staff Hours: 2.83337, Weekend RN Staff Hours: 0.2198

PT Staff Hours Per Day, per resident: 0.0702

Nurse Staff Turnover: 45.0, Nurse Turnover Note:

RN Turnover: 33.3, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.0209, Case Mix LPN Hours Per Day: 0.8042, Case Mix RN Hours Per Day: 0.4397

Adjusted Nurse Aide Hours Per Day, per resident: 2.19586, Adjusted LPN Hours Per Day: 0.6626, Adjusted RN Hours Per Day: 0.3425

Total Adjusted Nurse Hours Per Day, per resident: 3.18600

Adjusted Weekend Nurse Hours Per Day, per resident: 2.73546

Health Survey Dates and Scores: Cycle 1: 2023-12-01 (Score: 44), Cycle 2: 2021-08-26 (Score: 0), Cycle 3: 2018-12-03 (Score: 28)

Total Weighted Health Score: 26.667

Reported Incidents: 0, Substantiated Complaints: 1

Infection Control Citations:

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 48 COLONIAL DRIVE,HORSEHEADS,NY,14845 (42.1622, -76.853)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-12-01

Type: Health, Deficiency: Honor the resident's right to manage his or her financial affairs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Health, Deficiency: Notify the resident or the resident’s representative in writing how long the nursing home will hold the resident’s bed in cases of transfer to a hospital or therapeutic leave.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Health, Deficiency: Ensure the facility is licensed under applicable State and local law and operates and provides services in compliance with all applicable Federal, State, and local laws, regulations, and codes, and with accepted professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Health, Deficiency: Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2018-12-03

Type: Health, Deficiency: Create and put into place a plan for meeting the resident's most immediate needs within 48 hours of being admitted

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Health, Deficiency: Provide enough food/fluids to maintain a resident's health.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-12-01

Type: Fire Safety, Tag: 0232, Version: New

Description: Have corridors or aisles that are unobstructed and are at least 8 feet in width.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0361, Version: New

Description: Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2023-12-01

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2024-01-26

Citation on 2021-08-26

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-08-26

Type: Fire Safety, Tag: 0232, Version: New

Description: Have corridors or aisles that are unobstructed and are at least 8 feet in width.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-08-26

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-08-26

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-08-26

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-08-26

Type: Fire Safety, Tag: 0531, Version: New

Description: Have elevators that firefighters can control in the event of a fire.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-08-26

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2021-08-26

Type: Fire Safety, Tag: 0921, Version: New

Description: Ensure that testing and maintenance of electrical equipment is performed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-28

Citation on 2018-12-03

Type: Fire Safety, Tag: 0036, Version: New

Description: Establish emergency prep training and testing.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Fire Safety, Tag: 0037, Version: New

Description: Establish staff and initial training requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31

Citation on 2018-12-03

Type: Fire Safety, Tag: 0916, Version: New

Description: Have a battery powered remote alarm panel in a location accessible by operating personnel.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-31