UNIVERSITY CENTER FOR REHABILITATION AND NURSING Nursing Home


UNIVERSITY CENTER FOR REHABILITATION AND NURSING (CCN: 335061) is a For profit - Limited Liability company facility located in BRONX, NY (10468). The facility has an overall rating of 5/5, health inspection rating of 4/5, and a staffing rating of 2/5. It offers 46 certified beds and maintains an average of 44.3 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.58570 total hours per resident per day. It has been certified since April 23, 1969 and the last listed health inspection was on November 22, 2022, The facility is located in Bronx county and provides senior and nursing home care.

UNIVERSITY CENTER FOR REHABILITATION AND NURSING Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at University Center For Rehabilitation And Nursing below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: UNIVERSITY CENTER FOR REHABILITATION AND NURSING

Address: 2505 GRAND AVE, BRONX, NY 10468

Phone: (718) 295-1400

County: Bronx (020)

Ownership Type: For profit - Limited Liability company

Certified Beds: 46

Average Residents Per Day: 44.3 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: UNIVERSITY NURSING HOME LLC

First Approved Date: April 23, 1969

Affiliated Entity: CENTER MANAGEMENT GROUP (619)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 4 ()

QM Rating: 5 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 3 ()

Staffing Rating: 2 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.13579, LPN Staff Hours Per Day: 0.8310, RN Staff Hours Per Day: 0.6188, Licensed Staff Hours Per Day: 1.4499

Total Nurse Staff Hours Per Day, per resident: 3.58570

Weekend Nurse Staff Hours: 3.14632, Weekend RN Staff Hours: 0.5307

PT Staff Hours Per Day, per resident: 0.1186

Nurse Staff Turnover: 34.5, Nurse Turnover Note:

RN Turnover: 50.0, RN Turnover Note:

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 2.1078, Case Mix LPN Hours Per Day: 0.9256, Case Mix RN Hours Per Day: 0.4824

Adjusted Nurse Aide Hours Per Day, per resident: 2.06422, Adjusted LPN Hours Per Day: 0.6625, Adjusted RN Hours Per Day: 0.4833

Total Adjusted Nurse Hours Per Day, per resident: 3.21450

Adjusted Weekend Nurse Hours Per Day, per resident: 2.82061

Health Survey Dates and Scores: Cycle 1: 2022-11-22 (Score: 20), Cycle 2: 2020-01-22 (Score: 4), Cycle 3: 2018-07-23 (Score: 20)

Total Weighted Health Score: 14.667

Reported Incidents: 0, Substantiated Complaints: 2

Infection Control Citations:

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 2505 GRAND AVE,BRONX,NY,10468 (40.8646, -73.902)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-11-22

Type: Health, Deficiency: Ensure necessary information is communicated to the resident, and receiving health care provider at the time of a planned discharge.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-17

Citation on 2022-11-22

Type: Health, Deficiency: Ensure a licensed pharmacist perform a monthly drug regimen review, including the medical chart, following irregularity reporting guidelines in developed policies and procedures.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-17

Citation on 2022-11-22

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-17

Citation on 2022-11-22

Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-17

Citation on 2022-11-22

Type: Health, Deficiency: Plan the resident's discharge to meet the resident's goals and needs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-17

Citation on 2020-01-22

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-08

Citation on 2018-07-23

Type: Health, Deficiency: Assess the resident completely in a timely manner when first admitted, and then periodically, at least every 12 months.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-07

Citation on 2018-07-23

Type: Health, Deficiency: Provide pharmaceutical services to meet the needs of each resident and employ or obtain the services of a licensed pharmacist.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-07


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-11-22

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-29

Citation on 2022-11-22

Type: Fire Safety, Tag: 0161, Version: New

Description: Use approved construction type or materials.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-20

Citation on 2022-11-22

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-29

Citation on 2022-11-22

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-12

Citation on 2022-11-22

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-28

Citation on 2022-11-22

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-31

Citation on 2022-11-22

Type: Fire Safety, Tag: 0915, Version: New

Description: Have proper power supply for life support equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-01-12

Citation on 2022-11-22

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-12-29

Citation on 2020-01-22

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-17

Citation on 2020-01-22

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-02-17

Citation on 2018-07-25

Type: Fire Safety, Tag: 0161, Version: New

Description: Use approved construction type or materials.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20

Citation on 2018-07-25

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20

Citation on 2018-07-25

Type: Fire Safety, Tag: 0232, Version: New

Description: Have corridors or aisles that are unobstructed and are at least 8 feet in width.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20

Citation on 2018-07-25

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20

Citation on 2018-07-25

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20

Citation on 2018-07-25

Type: Fire Safety, Tag: 0342, Version: New

Description: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20

Citation on 2018-07-25

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20

Citation on 2018-07-25

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20

Citation on 2018-07-25

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-20