Provider Name: YONKERS GARDENS CENTER FOR NURSING AND REHAB
Address: 115 SOUTH BROADWAY, YONKERS, NY 10701
Phone: (914) 378-7358
County: Westchester (800)
Ownership Type: For profit - Corporation
Certified Beds: 200
Average Residents Per Day: 131. ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: YONKERS GARDENS LLC
First Approved Date: April 5, 1976
Affiliated Entity: INFINITE CARE (578)
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Resident
Sprinkler System Status: Yes
Overall Rating: 1 ()
Health Inspection Rating: 2 ()
QM Rating: 2 ()
Long Stay QM Rating: 2 ()
Short Stay QM Rating: 2 ()
Staffing Rating: 1 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 1.92558, LPN Staff Hours Per Day: 0.5328, RN Staff Hours Per Day: 0.7026, Licensed Staff Hours Per Day: 1.2354
Total Nurse Staff Hours Per Day, per resident: 3.16107
Weekend Nurse Staff Hours: 2.78006, Weekend RN Staff Hours: 0.4981
PT Staff Hours Per Day, per resident: 0.0658
Nurse Staff Turnover: 47.2, Nurse Turnover Note:
RN Turnover: 66.7, RN Turnover Note:
Admin Left Number: 2, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 2.1780, Case Mix LPN Hours Per Day: 0.9900, Case Mix RN Hours Per Day: 0.5713
Adjusted Nurse Aide Hours Per Day, per resident: 1.80112, Adjusted LPN Hours Per Day: 0.3971, Adjusted RN Hours Per Day: 0.4634
Total Adjusted Nurse Hours Per Day, per resident: 2.66453
Adjusted Weekend Nurse Hours Per Day, per resident: 2.34337
Health Survey Dates and Scores: Cycle 1: 2023-08-15 (Score: 40), Cycle 2: 2019-05-22 (Score: 20), Cycle 3: 2017-09-05 (Score: 32)
Total Weighted Health Score: 34.667
Reported Incidents: 5, Substantiated Complaints: 1
Infection Control Citations: 0
Fines and Penalties: Number of Fines: 6, Total Fines in Dollars: 69816.02, Payment Denials Number: 0, Total Penalties Number: 6
Location and GPS: 115 SOUTH BROADWAY,YONKERS,NY,10701 (40.9303, -73.898)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-10-31
Type: Health, Deficiency: Ensure each resident receives an accurate assessment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-01
Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-01
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-01
Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-10-31
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-10-31
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-10-31
Type: Health, Deficiency: Designate a qualified infection preventionist to be responsible for the infection prevent and control program in the nursing home.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-10-31
Type: Health, Deficiency: Educate residents and staff on COVID-19 vaccination, offer the COVID-19 vaccine to eligible residents and staff after education, and properly document each resident and staff member's vaccination status.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-10-31
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-10-31
Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Health, Deficiency: Provide timely notification to the resident, and if applicable to the resident representative and ombudsman, before transfer or discharge, including appeal rights.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Health, Deficiency: Assure that each resident’s assessment is updated at least once every 3 months.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-04
Type: Health, Deficiency: Provide housekeeping and maintenance services.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-10-25
Type: Health, Deficiency: Provide care by qualified persons according to each resident's written plan of care.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-10-25
Type: Health, Deficiency: Prepare food that is nutritional, appetizing, tasty, attractive, well-cooked, and at the right temperature.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-11-06
Type: Health, Deficiency: At least once a month, have a licensed pharmacist review each resident's medication(s) and report any irregularities to the attending doctor.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-10-25
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0015, Version: New
Description: Address subsistence needs for staff and patients.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-10
Type: Fire Safety, Tag: 0030, Version: New
Description: List the names and contact information of those in the facility.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-10
Type: Fire Safety, Tag: 0271, Version: New
Description: Have exits that are accessible at all times.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-09-13
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-09-13
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-10
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-02
Type: Fire Safety, Tag: 0921, Version: New
Description: Ensure that testing and maintenance of electrical equipment is performed.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0009, Version: New
Description: Include a process for Emergency Preparedness collaboration.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0015, Version: New
Description: Address subsistence needs for staff and patients.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0039, Version: New
Description: Conduct testing and exercise requirements.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0225, Version: New
Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0281, Version: New
Description: Install proper backup exit lighting.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0372, Version: New
Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0521, Version: New
Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0901, Version: New
Description: Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0921, Version: New
Description: Ensure that testing and maintenance of electrical equipment is performed.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-07-16
Type: Fire Safety, Tag: 0281, Version: New
Description: Install proper backup exit lighting.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-10-23
Type: Fire Safety, Tag: 0352, Version: New
Description: Properly install and monitor supervisory attachments on automatic sprinkler systems.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-10-23
Type: Fire Safety, Tag: 0541, Version: New
Description: Install properly constructed and protected linen or trash chutes.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-10-23
Type: Fire Safety, Tag: 0914, Version: New
Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-10-23
Type: Fire Safety, Tag: 0919, Version: New
Description: Meet requirements for the use of electrical equipment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2017-10-23