MENORAH PARK CENTER FOR SENIOR Nursing Home


MENORAH PARK CENTER FOR SENIOR (CCN: 365094) is a Non profit - Corporation facility located in BEACHWOOD, OH (44122). The facility has an overall rating of 4/5, health inspection rating of 3/5, and a staffing rating of 2/5. It offers 355 certified beds and maintains an average of 317. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.44791 total hours per resident per day. It has been certified since January 1, 1967 and the last listed health inspection was on April 19, 2023, The facility is located in Cuyahoga county and provides senior and nursing home care.

MENORAH PARK CENTER FOR SENIOR Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Menorah Park Center For Senior below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: MENORAH PARK CENTER FOR SENIOR

Address: 27100 CEDAR RD, BEACHWOOD, OH 44122

Phone: (216) 831-6500

County: Cuyahoga (170)

Ownership Type: Non profit - Corporation

Certified Beds: 355

Average Residents Per Day: 317. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: MENORAH PARK CENTER FOR SENIOR LIVING

First Approved Date: January 1, 1967

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 3 ()

QM Rating: 5 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 2 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 1.85834, LPN Staff Hours Per Day: 0.8491, RN Staff Hours Per Day: 0.7404, Licensed Staff Hours Per Day: 1.5895

Total Nurse Staff Hours Per Day, per resident: 3.44791

Weekend Nurse Staff Hours: 3.16759, Weekend RN Staff Hours: 0.5742

PT Staff Hours Per Day, per resident: 0.0679

Nurse Staff Turnover: 58.5, Nurse Turnover Note:

RN Turnover: 47.1, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1990, Case Mix LPN Hours Per Day: 0.7738, Case Mix RN Hours Per Day: 0.3858

Adjusted Nurse Aide Hours Per Day, per resident: 1.72164, Adjusted LPN Hours Per Day: 0.8097, Adjusted RN Hours Per Day: 0.7231

Total Adjusted Nurse Hours Per Day, per resident: 3.23577

Adjusted Weekend Nurse Hours Per Day, per resident: 2.97270

Health Survey Dates and Scores: Cycle 1: 2023-04-19 (Score: 60), Cycle 2: 2020-02-06 (Score: 56), Cycle 3: 2019-01-10 (Score: 68)

Total Weighted Health Score: 60.000

Reported Incidents: 0, Substantiated Complaints: 20

Infection Control Citations: 2

Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 20400.00, Payment Denials Number: 1, Total Penalties Number: 3

Location and GPS: 27100 CEDAR RD,BEACHWOOD,OH,44122 (41.5012, -81.489)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-10

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-21

Citation on 2023-07-10

Type: Health, Deficiency: Provide appropriate colostomy, urostomy, or ileostomy care/services for a resident who requires such services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-21

Citation on 2023-04-19

Type: Health, Deficiency: Coordinate assessments with the pre-admission screening and resident review program; and referring for services as needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-19

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-19

Type: Health, Deficiency: Provide enough food/fluids to maintain a resident's health.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-19

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-19

Type: Health, Deficiency: Provide safe, appropriate dialysis care/services for a resident who requires such services.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-19

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-19

Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-19

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2022-08-10

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-18

Citation on 2022-08-10

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-18

Citation on 2022-08-10

Type: Health, Deficiency: Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-18

Citation on 2022-06-29

Type: Health, Deficiency: Plan the resident's discharge to meet the resident's goals and needs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-08

Citation on 2020-02-06

Type: Health, Deficiency: Honor the resident's right to and the facility must promote and facilitate resident self-determination through support of resident choice.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-06

Type: Health, Deficiency: Ensure each resident receives an accurate assessment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-06

Type: Health, Deficiency: PASARR screening for Mental disorders or Intellectual Disabilities

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-06

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-06

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-06

Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2021-11-22

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-06

Citation on 2021-10-28

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-06

Citation on 2021-10-28

Type: Health, Deficiency: Ensure medication error rates are not 5 percent or greater.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-12-06

Citation on 2021-09-14

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-27

Citation on 2021-09-14

Type: Health, Deficiency: Ensure that residents are free from significant medication errors.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-27

Citation on 2021-05-04

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-05-28

Citation on 2021-05-04

Type: Health, Deficiency: Perform COVID19 testing on residents and staff.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-05-28


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-04-13

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-13

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-13

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-13

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-13

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-13

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-13

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2023-04-13

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-05-08

Citation on 2020-02-04

Type: Fire Safety, Tag: 0132, Version: New

Description: Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0227, Version: New

Description: Have ramps, exits, fire escape ladders, steps, and areas of refuge that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0255, Version: New

Description: Ensure that suites are correctly sub-divided by noncombustible or limited-combustible construction.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2020-02-04

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-26

Citation on 2019-01-09

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0255, Version: New

Description: Ensure that suites are correctly sub-divided by noncombustible or limited-combustible construction.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2019-05-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0342, Version: New

Description: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0361, Version: New

Description: Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2019-05-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2019-05-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0751, Version: New

Description: Have restrictions on the use of flammable curtains.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-24

Citation on 2019-01-09

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-02-24