HICKORY RIDGE NURSING & REHABILITATION CENTER Nursing Home


HICKORY RIDGE NURSING & REHABILITATION CENTER (CCN: 365134) is a For profit - Corporation facility located in AKRON, OH (44303). The facility has an overall rating of 3/5, health inspection rating of 4/5, and a staffing rating of 1/5. It offers 165 certified beds and maintains an average of 145. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.17517 total hours per resident per day. It has been certified since January 1, 1967 and the last listed health inspection was on January 12, 2023, The facility is located in Summit county and provides senior and nursing home care.

HICKORY RIDGE NURSING & REHABILITATION CENTER Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Hickory Ridge Nursing & Rehabilitation Center below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: HICKORY RIDGE NURSING & REHABILITATION CENTER

Address: 721 HICKORY ST, AKRON, OH 44303

Phone: (330) 762-6486

County: Summit (780)

Ownership Type: For profit - Corporation

Certified Beds: 165

Average Residents Per Day: 145. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: FHS HICKORY RIDGE INC

First Approved Date: January 1, 1967

Affiliated Entity: FOUNDATIONS HEALTH SOLUTIONS (225)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: None

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 4 ()

QM Rating: 4 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: (2)

Staffing Rating: 1 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 1.77649, LPN Staff Hours Per Day: 1.1015, RN Staff Hours Per Day: 0.2971, Licensed Staff Hours Per Day: 1.3986

Total Nurse Staff Hours Per Day, per resident: 3.17517

Weekend Nurse Staff Hours: 2.85456, Weekend RN Staff Hours: 0.1508

PT Staff Hours Per Day, per resident: 0.0050

Nurse Staff Turnover: 34.9, Nurse Turnover Note:

RN Turnover: 50.0, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.3107, Case Mix LPN Hours Per Day: 0.9204, Case Mix RN Hours Per Day: 0.5808

Adjusted Nurse Aide Hours Per Day, per resident: 1.56621, Adjusted LPN Hours Per Day: 0.8832, Adjusted RN Hours Per Day: 0.1927

Total Adjusted Nurse Hours Per Day, per resident: 2.62543

Adjusted Weekend Nurse Hours Per Day, per resident: 2.36033

Health Survey Dates and Scores: Cycle 1: 2023-01-12 (Score: 20), Cycle 2: 2020-01-15 (Score: 32), Cycle 3: 2018-11-29 (Score: 68)

Total Weighted Health Score: 32.000

Reported Incidents: 0, Substantiated Complaints: 1

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 657.80, Payment Denials Number: 0, Total Penalties Number: 1

Location and GPS: 721 HICKORY ST,AKRON,OH,44303 (41.1026, -81.530)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-25

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-17

Citation on 2023-01-12

Type: Health, Deficiency: Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2020-01-15

Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2020-01-15

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2020-01-15

Type: Health, Deficiency: Ensure that feeding tubes are not used unless there is a medical reason and the resident agrees; and provide appropriate care for a resident with a feeding tube.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2020-01-15

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2021-08-21

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-07

Citation on 2018-11-29

Type: Health, Deficiency: Develop and implement policies and procedures to prevent abuse, neglect, and theft.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-29

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-29

Type: Health, Deficiency: Encode each resident’s assessment data and transmit these data to the State within 7 days of assessment.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-29

Type: Health, Deficiency: Ensure each resident receives an accurate assessment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-29

Type: Health, Deficiency: Provide enough nursing staff every day to meet the needs of every resident; and have a licensed nurse in charge on each shift.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-29

Type: Health, Deficiency: Ensure menus must meet the nutritional needs of residents, be prepared in advance, be followed, be updated, be reviewed by dietician, and meet the needs of the resident.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-29

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-29

Type: Health, Deficiency: Administer the facility in a manner that enables it to use its resources effectively and efficiently.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-29

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-01-12

Type: Fire Safety, Tag: 0132, Version: New

Description: Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0361, Version: New

Description: Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2023-01-12

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-11

Citation on 2020-01-14

Type: Fire Safety, Tag: 0161, Version: New

Description: Use approved construction type or materials.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2020-01-14

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2020-01-14

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2020-01-14

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2020-01-14

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2020-01-14

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-31

Citation on 2018-11-27

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0331, Version: New

Description: Construct fire resistant interior walls.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24

Citation on 2018-11-27

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-12-24