OTTAWA CO RIVERVIEW NURSING HO Nursing Home


OTTAWA CO RIVERVIEW NURSING HO (CCN: 365498) is a Government - County facility located in OAK HARBOR, OH (43449). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 3/5. It offers 115 certified beds and maintains an average of 50.2 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.82548 total hours per resident per day. It has been certified since June 27, 1980 and the last listed health inspection was on May 18, 2023, The facility is located in Ottawa county and provides senior and nursing home care.

OTTAWA CO RIVERVIEW NURSING HO Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Ottawa Co Riverview Nursing Ho below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: OTTAWA CO RIVERVIEW NURSING HO

Address: 8180 W STATE RT 163, OAK HARBOR, OH 43449

Phone: (419) 898-2851

County: Ottawa (630)

Ownership Type: Government - County

Certified Beds: 115

Average Residents Per Day: 50.2 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: COUNTY OF OTTAWA

First Approved Date: June 27, 1980

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 5 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 3 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.08457, LPN Staff Hours Per Day: 0.9546, RN Staff Hours Per Day: 0.7862, Licensed Staff Hours Per Day: 1.7409

Total Nurse Staff Hours Per Day, per resident: 3.82548

Weekend Nurse Staff Hours: 3.64781, Weekend RN Staff Hours: 0.6061

PT Staff Hours Per Day, per resident: 0.0935

Nurse Staff Turnover: 54.2, Nurse Turnover Note:

RN Turnover: 27.3, RN Turnover Note:

Admin Left Number: 1, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.0485, Case Mix LPN Hours Per Day: 0.8094, Case Mix RN Hours Per Day: 0.4595

Adjusted Nurse Aide Hours Per Day, per resident: 2.07303, Adjusted LPN Hours Per Day: 0.8704, Adjusted RN Hours Per Day: 0.6446

Total Adjusted Nurse Hours Per Day, per resident: 3.63460

Adjusted Weekend Nurse Hours Per Day, per resident: 3.46579

Health Survey Dates and Scores: Cycle 1: 2023-05-18 (Score: 4), Cycle 2: 2020-01-23 (Score: 4), Cycle 3: 2018-11-29 (Score: 0)

Total Weighted Health Score: 3.333

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 1625.00, Payment Denials Number: 0, Total Penalties Number: 2

Location and GPS: 8180 W STATE RT 163,OAK HARBOR,OH,43449 (41.5337, -83.138)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-05-18

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2020-01-23

Type: Health, Deficiency: Honor the resident's right to request, refuse, and/or discontinue treatment, to participate in or refuse to participate in experimental research, and to formulate an advance directive.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-12


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-05-16

Type: Fire Safety, Tag: 0161, Version: New

Description: Use approved construction type or materials.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2023-05-16

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2023-05-16

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2023-05-16

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2023-05-16

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2023-05-16

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2023-05-16

Type: Fire Safety, Tag: 0711, Version: New

Description: Provide a written emergency evacuation plan.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2020-01-23

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-12

Citation on 2020-01-23

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-12

Citation on 2020-01-23

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-12

Citation on 2020-01-23

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-12

Citation on 2018-11-28

Type: Fire Safety, Tag: 0226, Version: New

Description: Have horizontal exits used in accordance with safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-17

Citation on 2018-11-28

Type: Fire Safety, Tag: 0281, Version: New

Description: Install proper backup exit lighting.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-17

Citation on 2018-11-28

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-17

Citation on 2018-11-28

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-17

Citation on 2018-11-28

Type: Fire Safety, Tag: 0347, Version: New

Description: Properly provide smoke detection systems in areas open to corridors.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-17

Citation on 2018-11-28

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-17

Citation on 2018-11-28

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-17

Citation on 2018-11-28

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-01-17