Provider Name: WESTPARK HEALTHCARE CAMPUS
Address: 4401 W 150TH STREET, CLEVELAND, OH 44135
Phone: (216) 252-7555
County: Cuyahoga (170)
Ownership Type: For profit - Individual
Certified Beds: 100
Average Residents Per Day: 81.0 ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: MYOCARENURSING HOME, INC.
First Approved Date: July 10, 1990
Affiliated Entity: ()
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Resident
Sprinkler System Status: Yes
Overall Rating: 3 ()
Health Inspection Rating: 3 ()
QM Rating: 5 ()
Long Stay QM Rating: 5 ()
Short Stay QM Rating: (2)
Staffing Rating: 1 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 1.73818, LPN Staff Hours Per Day: 1.1155, RN Staff Hours Per Day: 0.4249, Licensed Staff Hours Per Day: 1.5404
Total Nurse Staff Hours Per Day, per resident: 3.27867
Weekend Nurse Staff Hours: 2.75103, Weekend RN Staff Hours: 0.2193
PT Staff Hours Per Day, per resident: 0.0391
Nurse Staff Turnover: 53.9, Nurse Turnover Note:
RN Turnover: 54.5, RN Turnover Note:
Admin Left Number: 0, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 2.0264, Case Mix LPN Hours Per Day: 0.8715, Case Mix RN Hours Per Day: 0.4876
Adjusted Nurse Aide Hours Per Day, per resident: 1.74742, Adjusted LPN Hours Per Day: 0.9445, Adjusted RN Hours Per Day: 0.3283
Total Adjusted Nurse Hours Per Day, per resident: 3.05235
Adjusted Weekend Nurse Hours Per Day, per resident: 2.56114
Health Survey Dates and Scores: Cycle 1: 2023-03-27 (Score: 36), Cycle 2: 2019-11-07 (Score: 64), Cycle 3: 2018-10-03 (Score: 96)
Total Weighted Health Score: 55.333
Reported Incidents: 2, Substantiated Complaints: 6
Infection Control Citations: 0
Fines and Penalties: Number of Fines: 4, Total Fines in Dollars: 17945.68, Payment Denials Number: 1, Total Penalties Number: 5
Location and GPS: 4401 W 150TH STREET,CLEVELAND,OH,44135 (41.4349, -81.801)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Notify the appropriate authorities when residents with MD or ID services has a significant change in condition.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Health, Deficiency: Provide safe, appropriate dialysis care/services for a resident who requires such services.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Health, Deficiency: Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decline/room, etc.) that affect the resident.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.
Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-02-03
Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-02-03
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-02-03
Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-15
Type: Health, Deficiency: Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-05-13
Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-05-13
Type: Health, Deficiency: Reasonably accommodate the needs and preferences of each resident.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-08
Type: Health, Deficiency: Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-08
Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Honor the resident's right to request, refuse, and/or discontinue treatment, to participate in or refuse to participate in experimental research, and to formulate an advance directive.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Respond appropriately to all alleged violations.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Ensure each resident receives an accurate assessment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Provide bedrooms that don't allow residents to see each other when privacy is needed.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Health, Deficiency: Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0211, Version: New
Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Fire Safety, Tag: 0222, Version: New
Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Fire Safety, Tag: 0324, Version: New
Description: Provide properly protected cooking facilities.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Fire Safety, Tag: 0374, Version: New
Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Fire Safety, Tag: 0923, Version: New
Description: Have proper medical gas storage and administration areas.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-12
Type: Fire Safety, Tag: 0015, Version: New
Description: Address subsistence needs for staff and patients.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has plan of correction on 2019-12-13
Type: Fire Safety, Tag: 0025, Version: New
Description: Create arrangements with other facilities to receive patients.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has plan of correction on 2019-12-13
Type: Fire Safety, Tag: 0026, Version: New
Description: Establish roles under a Waiver declared by secretary.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has plan of correction on 2019-12-13
Type: Fire Safety, Tag: 0133, Version: New
Description: Install a two-hour-resistant firewall separation.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0372, Version: New
Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0753, Version: New
Description: Have restrictions on the use of highly flammable decorations.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0911, Version: New
Description: Meet requirements for the installation and maintenance of electrical systems.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0919, Version: New
Description: Meet requirements for the use of electrical equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0923, Version: New
Description: Have proper medical gas storage and administration areas.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-12-20
Type: Fire Safety, Tag: 0036, Version: New
Description: Establish emergency prep training and testing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Fire Safety, Tag: 0039, Version: New
Description: Conduct testing and exercise requirements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Fire Safety, Tag: 0225, Version: New
Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Fire Safety, Tag: 0700, Version: New
Description: Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Fire Safety, Tag: 0711, Version: New
Description: Provide a written emergency evacuation plan.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-03
Type: Fire Safety, Tag: 0741, Version: New
Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-03
Type: Fire Safety, Tag: 0912, Version: New
Description: Have power receptacles that are properly grounded.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-02
Type: Fire Safety, Tag: 0915, Version: New
Description: Have proper power supply for life support equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Waiver has been granted on 2019-06-09
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-01-03