Provider Name: BOWERSTON HILLS NURSING & REHABILITATION
Address: 9076 CUMBERLAND ROAD, BOWERSTON, OH 44695
Phone: (740) 269-4000
County: Carroll (090)
Ownership Type: For profit - Corporation
Certified Beds: 25
Average Residents Per Day: 19.3 ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: BOWERSTON HILLS HEALTHCARE LLC
First Approved Date: February 1, 1996
Affiliated Entity: HILLSTONE HEALTHCARE (271)
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Resident
Sprinkler System Status: Yes
Overall Rating: 4 ()
Health Inspection Rating: 3 ()
QM Rating: 5 ()
Long Stay QM Rating: 5 ()
Short Stay QM Rating: (2)
Staffing Rating: 2 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 2.06674, LPN Staff Hours Per Day: 0.7959, RN Staff Hours Per Day: 0.6951, Licensed Staff Hours Per Day: 1.4911
Total Nurse Staff Hours Per Day, per resident: 3.55785
Weekend Nurse Staff Hours: 3.35700, Weekend RN Staff Hours: 0.6636
PT Staff Hours Per Day, per resident: 0.0103
Nurse Staff Turnover: 31.3, Nurse Turnover Note:
RN Turnover: , RN Turnover Note: 6
Admin Left Number: 1, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 2.0737, Case Mix LPN Hours Per Day: 0.7987, Case Mix RN Hours Per Day: 0.5931
Adjusted Nurse Aide Hours Per Day, per resident: 2.03033, Adjusted LPN Hours Per Day: 0.7353, Adjusted RN Hours Per Day: 0.4416
Total Adjusted Nurse Hours Per Day, per resident: 3.23587
Adjusted Weekend Nurse Hours Per Day, per resident: 3.05319
Health Survey Dates and Scores: Cycle 1: 2023-02-23 (Score: 64), Cycle 2: 2021-04-26 (Score: 16), Cycle 3: 2019-02-22 (Score: 0)
Total Weighted Health Score: 37.333
Reported Incidents: 0, Substantiated Complaints: 0
Infection Control Citations:
Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0
Location and GPS: 9076 CUMBERLAND ROAD,BOWERSTON,OH,44695 (40.4447, -81.204)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Give residents a notice of rights, rules, services and charges.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Honor the resident's right to voice grievances without discrimination or reprisal and the facility must establish a grievance policy and make prompt efforts to resolve grievances.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Assess the resident when there is a significant change in condition
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Ensure each resident receives an accurate assessment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Coordinate assessments with the pre-admission screening and resident review program; and referring for services as needed.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Assist a resident in gaining access to vision and hearing services.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Provide or obtain dental services for each resident.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Health, Deficiency: Ensure each resident receives an accurate assessment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0341, Version: New
Description: Install a fire alarm system that can be heard throughout the facility.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Fire Safety, Tag: 0521, Version: New
Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-03-31
Type: Fire Safety, Tag: 0222, Version: New
Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Type: Fire Safety, Tag: 0511, Version: New
Description: Have properly installed electrical wiring and gas equipment.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Type: Fire Safety, Tag: 0915, Version: New
Description: Have proper power supply for life support equipment.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Type: Fire Safety, Tag: 0223, Version: New
Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-18
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-18
Type: Fire Safety, Tag: 0362, Version: New
Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-18
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-18
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-18
Type: Fire Safety, Tag: 0914, Version: New
Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-18
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-18
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-18