SNF-THE VILLA AT MARYMOUNT Nursing Home


SNF-THE VILLA AT MARYMOUNT (CCN: 366335) is a For profit - Limited Liability company facility located in GARFIELD HEIGHTS, OH (44125). The facility has an overall rating of 2/5, health inspection rating of 2/5, and a staffing rating of 4/5. It offers 130 certified beds and maintains an average of 100. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.80153 total hours per resident per day. It has been certified since January 31, 2007 and the last listed health inspection was on November 30, 2023, The facility is located in Cuyahoga county and provides senior and nursing home care.

SNF-THE VILLA AT MARYMOUNT Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Snf-the Villa At Marymount below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: SNF-THE VILLA AT MARYMOUNT

Address: 5200 MARYMOUNT VILLAGE DRIVE, GARFIELD HEIGHTS, OH 44125

Phone: (216) 332-1100

County: Cuyahoga (170)

Ownership Type: For profit - Limited Liability company

Certified Beds: 130

Average Residents Per Day: 100. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: Legal Business Name Not Available

First Approved Date: January 31, 2007

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: Y

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 2 ()

Health Inspection Rating: 2 ()

QM Rating: 4 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 1 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.20145, LPN Staff Hours Per Day: 1.8393, RN Staff Hours Per Day: 0.7607, Licensed Staff Hours Per Day: 2.6000

Total Nurse Staff Hours Per Day, per resident: 4.80153

Weekend Nurse Staff Hours: 4.31836, Weekend RN Staff Hours: 0.4640

PT Staff Hours Per Day, per resident: 0.1635

Nurse Staff Turnover: 61.2, Nurse Turnover Note:

RN Turnover: 50.0, RN Turnover Note:

Admin Left Number: 3, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1056, Case Mix LPN Hours Per Day: 0.7338, Case Mix RN Hours Per Day: 0.3503

Adjusted Nurse Aide Hours Per Day, per resident: 2.12994, Adjusted LPN Hours Per Day: 1.8497, Adjusted RN Hours Per Day: 0.8180

Total Adjusted Nurse Hours Per Day, per resident: 4.74458

Adjusted Weekend Nurse Hours Per Day, per resident: 4.26714

Health Survey Dates and Scores: Cycle 1: 2023-11-30 (Score: 139), Cycle 2: 2021-06-04 (Score: 32), Cycle 3: 2019-01-17 (Score: 20)

Total Weighted Health Score: 83.500

Reported Incidents: 1, Substantiated Complaints: 9

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 83080.00, Payment Denials Number: 1, Total Penalties Number: 2

Location and GPS: 5200 MARYMOUNT VILLAGE DRIVE,GARFIELD HEIGHTS,OH,44125 (41.4353, -81.658)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-11-30

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-08

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-30

Citation on 2023-11-08

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: J - Level 4: Immediate jeopardy to resident health or safety. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-11-30

Citation on 2023-11-08

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-30

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-30

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-30

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2022-07-11

Type: Health, Deficiency: Ensure medication error rates are not 5 percent or greater.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-22

Citation on 2022-07-11

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-22

Citation on 2021-06-04

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-04

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-04-15

Type: Health, Deficiency: Ensure that residents are free from significant medication errors.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-06-04


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-11-28

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0754, Version: New

Description: Provide properly sized and located linen or trash receptacles.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2023-11-28

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-12-05

Citation on 2021-06-09

Type: Fire Safety, Tag: 0132, Version: New

Description: Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0161, Version: New

Description: Use approved construction type or materials.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0163, Version: New

Description: Install noncombustible or limited-combustible interior walls.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2021-09-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2021-09-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0343, Version: New

Description: Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0373, Version: New

Description: Have enough space near smoke barriers to protect residents.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2021-06-09

Type: Fire Safety, Tag: 0926, Version: New

Description: Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-20

Citation on 2019-01-16

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2019-08-01

Citation on 2019-01-16

Type: Fire Safety, Tag: 0227, Version: New

Description: Have ramps, exits, fire escape ladders, steps, and areas of refuge that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2019-08-01

Citation on 2019-01-16

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-08

Citation on 2019-01-16

Type: Fire Safety, Tag: 0347, Version: New

Description: Properly provide smoke detection systems in areas open to corridors.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-08

Citation on 2019-01-16

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-08

Citation on 2019-01-16

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-08

Citation on 2019-01-16

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-08

Citation on 2019-01-16

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Waiver has been granted on 2019-08-01

Citation on 2019-01-16

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-08

Citation on 2019-01-16

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-08

Citation on 2019-01-16

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-03-08