BROOKDALE WESTLAKE VILLAGE Nursing Home


BROOKDALE WESTLAKE VILLAGE (CCN: 366373) is a For profit - Corporation facility located in WESTLAKE, OH (44145). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 4/5. It offers 60 certified beds and maintains an average of 45.3 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.78502 total hours per resident per day. It has been certified since February 3, 2009 and the last listed health inspection was on October 20, 2022, The facility is located in Cuyahoga county and provides senior and nursing home care.

BROOKDALE WESTLAKE VILLAGE Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Brookdale Westlake Village below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: BROOKDALE WESTLAKE VILLAGE

Address: 28450 WESTLAKE VILLAGE DRIVE, WESTLAKE, OH 44145

Phone: (440) 892-6200

County: Cuyahoga (170)

Ownership Type: For profit - Corporation

Certified Beds: 60

Average Residents Per Day: 45.3 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: ARC WESTLAKE VILLAGE SNF LLC

First Approved Date: February 3, 2009

Affiliated Entity: BROOKDALE SENIOR LIVING (93)

Retirement Community: Y, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: None

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 4 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: 4 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.33845, LPN Staff Hours Per Day: 0.9860, RN Staff Hours Per Day: 1.4605, Licensed Staff Hours Per Day: 2.4465

Total Nurse Staff Hours Per Day, per resident: 4.78502

Weekend Nurse Staff Hours: 4.09684, Weekend RN Staff Hours: 1.0830

PT Staff Hours Per Day, per resident: 0.1550

Nurse Staff Turnover: 52.0, Nurse Turnover Note:

RN Turnover: 40.0, RN Turnover Note:

Admin Left Number: 1, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.0916, Case Mix LPN Hours Per Day: 0.8018, Case Mix RN Hours Per Day: 0.4591

Adjusted Nurse Aide Hours Per Day, per resident: 2.27764, Adjusted LPN Hours Per Day: 0.9074, Adjusted RN Hours Per Day: 1.1986

Total Adjusted Nurse Hours Per Day, per resident: 4.49871

Adjusted Weekend Nurse Hours Per Day, per resident: 3.85171

Health Survey Dates and Scores: Cycle 1: 2022-10-20 (Score: 12), Cycle 2: 2019-11-15 (Score: 20), Cycle 3: 2018-10-11 (Score: 20)

Total Weighted Health Score: 16.000

Reported Incidents: 1, Substantiated Complaints: 1

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 10650.00, Payment Denials Number: 0, Total Penalties Number: 2

Location and GPS: 28450 WESTLAKE VILLAGE DRIVE,WESTLAKE,OH,44145 (41.4400, -81.941)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-10-06

Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-07

Citation on 2023-10-06

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Past Non-Compliance on 2023-10-06

Citation on 2022-10-20

Type: Health, Deficiency: Provide activities to meet all resident's needs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2022-03-09

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-31

Citation on 2019-11-15

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-12-18

Citation on 2018-10-11

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-11

Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-10-17

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2022-10-17

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2022-10-17

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2022-10-17

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2022-10-17

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2022-10-17

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2022-10-17

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-11-30

Citation on 2019-11-14

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-12-18

Citation on 2019-11-14

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-12-18

Citation on 2019-11-14

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-12-18

Citation on 2018-10-09

Type: Fire Safety, Tag: 0006, Version: New

Description: Conduct risk assessment and an All-Hazards approach.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0007, Version: New

Description: Address patient/client population and determine types of services needed.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0015, Version: New

Description: Address subsistence needs for staff and patients.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0022, Version: New

Description: Establish policies and procedures for sheltering.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0024, Version: New

Description: Establish policies and procedures for volunteers.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0034, Version: New

Description: Provide a means of sharing information on occupancy/needs.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0035, Version: New

Description: Provide family notifications of emergency plan.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30

Citation on 2018-10-09

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-11-30