WINDSOR MEDICAL CENTER INC Nursing Home


WINDSOR MEDICAL CENTER INC (CCN: 366456) is a For profit - Corporation facility located in NORTH CANTON, OH (44720). The facility has an overall rating of 3/5, health inspection rating of 2/5, and a staffing rating of 5/5. It offers 20 certified beds and maintains an average of 15.8 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 5.39141 total hours per resident per day. It has been certified since July 14, 2017 and the last listed health inspection was on June 23, 2022, The facility is located in Stark county and provides senior and nursing home care.

WINDSOR MEDICAL CENTER INC Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Windsor Medical Center Inc below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: WINDSOR MEDICAL CENTER INC

Address: 1454 EAST MAPLE STREET, NORTH CANTON, OH 44720

Phone: (330) 499-8300

County: Stark (770)

Ownership Type: For profit - Corporation

Certified Beds: 20

Average Residents Per Day: 15.8 ()

Provider Type: Medicare, Resides in Hospital: No

Legal Business Name: WINDSOR MEDICAL CENTER INC

First Approved Date: July 14, 2017

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 2 ()

QM Rating: 3 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 1 ()

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.92020, LPN Staff Hours Per Day: 0.7922, RN Staff Hours Per Day: 1.6789, Licensed Staff Hours Per Day: 2.4712

Total Nurse Staff Hours Per Day, per resident: 5.39141

Weekend Nurse Staff Hours: 4.38656, Weekend RN Staff Hours: 1.1702

PT Staff Hours Per Day, per resident: 0.0567

Nurse Staff Turnover: 57.5, Nurse Turnover Note:

RN Turnover: 41.7, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 1.9790, Case Mix LPN Hours Per Day: 0.7614, Case Mix RN Hours Per Day: 0.4187

Adjusted Nurse Aide Hours Per Day, per resident: 3.00605, Adjusted LPN Hours Per Day: 0.7678, Adjusted RN Hours Per Day: 1.5107

Total Adjusted Nurse Hours Per Day, per resident: 5.37909

Adjusted Weekend Nurse Hours Per Day, per resident: 4.37654

Health Survey Dates and Scores: Cycle 1: 2022-06-23 (Score: 203), Cycle 2: 2019-06-20 (Score: 0), Cycle 3: 2018-07-26 (Score: 0)

Total Weighted Health Score: 101.50

Reported Incidents: 2, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 91670.00, Payment Denials Number: 0, Total Penalties Number: 2

Location and GPS: 1454 EAST MAPLE STREET,NORTH CANTON,OH,44720 (40.8752, -81.378)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-03-14

Type: Health, Deficiency: Develop and implement policies and procedures to prevent abuse, neglect, and theft.

Severity: L - Level 4: Immediate jeopardy to resident health or safety. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-03-15

Citation on 2022-06-23

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-06-23

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-06-23

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-06-23

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-06-22

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-06-22

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-06-22

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-06-22

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-06-22

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2022-06-22

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-09-22

Citation on 2019-06-17

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-07-31

Citation on 2019-06-17

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-07-31

Citation on 2018-07-26

Type: Fire Safety, Tag: 0024, Version: New

Description: Establish policies and procedures for volunteers.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2018-09-14

Citation on 2018-07-26

Type: Fire Safety, Tag: 0026, Version: New

Description: Establish roles under a Waiver declared by secretary.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2018-09-14

Citation on 2018-07-26

Type: Fire Safety, Tag: 0131, Version: New

Description: Meet requirements for sections of health care facilities separated by fire resistive construction.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0341, Version: New

Description: Install a fire alarm system that can be heard throughout the facility.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0354, Version: New

Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0524, Version: New

Description: Ensure that gas fire places are out of the reach of patients and can be shut off if unit is working improperly.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18

Citation on 2018-07-26

Type: Fire Safety, Tag: 0916, Version: New

Description: Have a battery powered remote alarm panel in a location accessible by operating personnel.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-24

Citation on 2018-07-26

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-10-24

Citation on 2018-07-26

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2018-09-18