BINGER NURSING AND REHABILITATION Nursing Home


BINGER NURSING AND REHABILITATION (CCN: 375398) is a For profit - Limited Liability company facility located in BINGER, OK (73009). The facility has an overall rating of 3/5, health inspection rating of 4/5, and a staffing rating of 1/5. It offers 65 certified beds and maintains an average of 35.8 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.07245 total hours per resident per day. It has been certified since November 1, 2001 and the last listed health inspection was on August 21, 2023, The facility is located in Caddo county and provides senior and nursing home care.

BINGER NURSING AND REHABILITATION Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Binger Nursing And Rehabilitation below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: BINGER NURSING AND REHABILITATION

Address: 516 NORTH BROADWAY, BINGER, OK 73009

Phone: (405) 656-2302

County: Caddo (070)

Ownership Type: For profit - Limited Liability company

Certified Beds: 65

Average Residents Per Day: 35.8 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: BINGER NURSING AND REHABILITATION, LLC

First Approved Date: November 1, 2001

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 4 ()

QM Rating: 2 ()

Long Stay QM Rating: 2 ()

Short Stay QM Rating: (2)

Staffing Rating: 1 (12)

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.82730, LPN Staff Hours Per Day: 1.1009, RN Staff Hours Per Day: 0.1442, Licensed Staff Hours Per Day: 1.2451

Total Nurse Staff Hours Per Day, per resident: 4.07245

Weekend Nurse Staff Hours: 3.78135, Weekend RN Staff Hours: 0.2730

PT Staff Hours Per Day, per resident: 0.0034

Nurse Staff Turnover: , Nurse Turnover Note: 6

RN Turnover: , RN Turnover Note: 6

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 1.8189, Case Mix LPN Hours Per Day: 0.6465, Case Mix RN Hours Per Day: 0.3033

Adjusted Nurse Aide Hours Per Day, per resident: 3.16670, Adjusted LPN Hours Per Day: 1.2565, Adjusted RN Hours Per Day: 0.1791

Total Adjusted Nurse Hours Per Day, per resident: 4.63601

Adjusted Weekend Nurse Hours Per Day, per resident: 4.30463

Health Survey Dates and Scores: Cycle 1: 2023-08-21 (Score: 12), Cycle 2: 2022-09-01 (Score: 32), Cycle 3: 2021-07-13 (Score: 48)

Total Weighted Health Score: 24.667

Reported Incidents: 0, Substantiated Complaints: 1

Infection Control Citations:

Fines and Penalties: Number of Fines: 16, Total Fines in Dollars: 68132.14, Payment Denials Number: 0, Total Penalties Number: 16

Location and GPS: 516 NORTH BROADWAY,BINGER,OK,73009 (35.3134, -98.342)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-08-21

Type: Health, Deficiency: Encode each resident’s assessment data and transmit these data to the State within 7 days of assessment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-10

Citation on 2023-08-21

Type: Health, Deficiency: Make sure that a working call system is available in each resident's bathroom and bathing area.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-10-05

Citation on 2022-04-06

Type: Health, Deficiency: Ensure staff are vaccinated for COVID-19

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-17

Citation on 2022-09-01

Type: Health, Deficiency: Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decline/room, etc.) that affect the resident.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-09-01

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-09-01

Type: Health, Deficiency: Report COVID19 data to residents and families.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2021-07-13

Type: Health, Deficiency: Give residents notice of Medicaid/Medicare coverage and potential liability for services not covered.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-09

Citation on 2021-07-13

Type: Health, Deficiency: Provide appropriate care for a resident to maintain and/or improve range of motion (ROM), limited ROM and/or mobility, unless a decline is for a medical reason.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-09

Citation on 2021-07-13

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-09

Citation on 2021-07-13

Type: Health, Deficiency: Provide or obtain laboratory tests/services when ordered and promptly tell the ordering practitioner of the results.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-09

Citation on 2021-07-13

Type: Health, Deficiency: Properly hold, secure, and manage each resident's personal money which is deposited with the nursing home.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-09

Citation on 2021-07-13

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-09


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-08-29

Type: Fire Safety, Tag: 0004, Version: New

Description: Develop and maintain an Emergency Preparedness Program (EP).

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0039, Version: New

Description: Conduct testing and exercise requirements.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0300, Version: New

Description: Meet other general requirements that are deficient.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2022-08-29

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-10-15

Citation on 2021-07-09

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2021-09-16

Citation on 2021-07-09

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2021-10-14

Citation on 2021-07-09

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-16

Citation on 2021-07-09

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2021-11-15

Citation on 2021-07-09

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has plan of correction on 2021-10-11

Citation on 2021-07-09

Type: Fire Safety, Tag: 0522, Version: New

Description: Have an externally vented heating system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-16

Citation on 2021-07-09

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-16

Citation on 2019-04-02

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-28

Citation on 2019-04-02

Type: Fire Safety, Tag: 0343, Version: New

Description: Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-28

Citation on 2019-04-02

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-28

Citation on 2019-04-02

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2019-05-28