ABBEYVILLE SKILLED NURSING AND REHABILITATION CENT Nursing Home


ABBEYVILLE SKILLED NURSING AND REHABILITATION CENT (CCN: 395199) is a For profit - Limited Liability company facility located in LANCASTER, PA (17603). The facility has an overall rating of 3/5, health inspection rating of 4/5, and a staffing rating of 1/5. It offers 172 certified beds and maintains an average of 156. residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 2.91555 total hours per resident per day. It has been certified since April 11, 1967 and the last listed health inspection was on May 4, 2023, The facility is located in Lancaster county and provides senior and nursing home care.

ABBEYVILLE SKILLED NURSING AND REHABILITATION CENT Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Abbeyville Skilled Nursing And Rehabilitation Cent below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: ABBEYVILLE SKILLED NURSING AND REHABILITATION CENT

Address: 100 ABBEYVILLE ROAD, LANCASTER, PA 17603

Phone: (717) 397-4261

County: Lancaster (440)

Ownership Type: For profit - Limited Liability company

Certified Beds: 172

Average Residents Per Day: 156. ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: 100 ABBEYVILLE ROAD OPERATIONS LLC

First Approved Date: April 11, 1967

Affiliated Entity: GENESIS HEALTHCARE (237)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 4 ()

QM Rating: 3 ()

Long Stay QM Rating: 2 ()

Short Stay QM Rating: 4 ()

Staffing Rating: 1 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 1.65468, LPN Staff Hours Per Day: 0.8778, RN Staff Hours Per Day: 0.3830, Licensed Staff Hours Per Day: 1.2608

Total Nurse Staff Hours Per Day, per resident: 2.91555

Weekend Nurse Staff Hours: 2.53607, Weekend RN Staff Hours: 0.2500

PT Staff Hours Per Day, per resident: 0.0482

Nurse Staff Turnover: 50.8, Nurse Turnover Note:

RN Turnover: 61.9, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 1.9554, Case Mix LPN Hours Per Day: 0.7614, Case Mix RN Hours Per Day: 0.3995

Adjusted Nurse Aide Hours Per Day, per resident: 1.72392, Adjusted LPN Hours Per Day: 0.8507, Adjusted RN Hours Per Day: 0.3612

Total Adjusted Nurse Hours Per Day, per resident: 2.94885

Adjusted Weekend Nurse Hours Per Day, per resident: 2.56504

Health Survey Dates and Scores: Cycle 1: 2023-05-04 (Score: 16), Cycle 2: 2022-05-12 (Score: 0), Cycle 3: 2021-04-23 (Score: 12)

Total Weighted Health Score: 10.000

Reported Incidents: 0, Substantiated Complaints: 9

Infection Control Citations:

Fines and Penalties: Number of Fines: 4, Total Fines in Dollars: 4550.00, Payment Denials Number: 0, Total Penalties Number: 4

Location and GPS: 100 ABBEYVILLE ROAD,LANCASTER,PA,17603 (40.0362, -76.336)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-08-16

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-13

Citation on 2023-06-28

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-31

Citation on 2023-05-04

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-20

Citation on 2021-04-23

Type: Health, Deficiency: Respond appropriately to all alleged violations.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-06-11

Citation on 2021-04-23

Type: Health, Deficiency: Observe each nurse aide's job performance and give regular training.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-06-11


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-05-15

Type: Fire Safety, Tag: 0241, Version: New

Description: Have correct number of accessible exits for each story.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2023-05-15

Type: Fire Safety, Tag: 0929, Version: New

Description: Ensure precautions for handling oxygen cylinders and equipment are correctly followed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0100, Version: New

Description: Meet other general requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0241, Version: New

Description: Have correct number of accessible exits for each story.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-05-31

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2021-07-01

Type: Fire Safety, Tag: 0241, Version: New

Description: Have correct number of accessible exits for each story.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Fire Safety Evaluation Survey on 2021-07-30

Citation on 2021-07-01

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Fire Safety, Tag: 0325, Version: New

Description: Have properly installed hallway dispensers for alcohol-based hand rub.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30

Citation on 2021-07-01

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-07-30