PINECREST MANOR Nursing Home


PINECREST MANOR (CCN: 395279) is a Non profit - Corporation facility located in ST MARYS, PA (15857). The facility has an overall rating of 4/5, health inspection rating of 4/5, and a staffing rating of 4/5. It offers 138 certified beds and maintains an average of 90.9 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.99822 total hours per resident per day. It has been certified since June 1, 1978 and the last listed health inspection was on April 28, 2023, The facility is located in Elk county and provides senior and nursing home care.

PINECREST MANOR Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Pinecrest Manor below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: PINECREST MANOR

Address: 763 JOHNSONBURG RD, ST MARYS, PA 15857

Phone: (814) 788-8488

County: Elk (310)

Ownership Type: Non profit - Corporation

Certified Beds: 138

Average Residents Per Day: 90.9 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: ELK REGIONAL HEALTH CENTER

First Approved Date: June 1, 1978

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 4 ()

Health Inspection Rating: 4 ()

QM Rating: 4 ()

Long Stay QM Rating: 5 ()

Short Stay QM Rating: 4 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.30288, LPN Staff Hours Per Day: 0.8386, RN Staff Hours Per Day: 0.8567, Licensed Staff Hours Per Day: 1.6953

Total Nurse Staff Hours Per Day, per resident: 3.99822

Weekend Nurse Staff Hours: 3.17431, Weekend RN Staff Hours: 0.4328

PT Staff Hours Per Day, per resident: 0.0434

Nurse Staff Turnover: 41.7, Nurse Turnover Note:

RN Turnover: 42.9, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1354, Case Mix LPN Hours Per Day: 0.8147, Case Mix RN Hours Per Day: 0.4557

Adjusted Nurse Aide Hours Per Day, per resident: 2.19700, Adjusted LPN Hours Per Day: 0.7596, Adjusted RN Hours Per Day: 0.7083

Total Adjusted Nurse Hours Per Day, per resident: 3.70023

Adjusted Weekend Nurse Hours Per Day, per resident: 2.93772

Health Survey Dates and Scores: Cycle 1: 2023-04-28 (Score: 8), Cycle 2: 2022-05-27 (Score: 0), Cycle 3: 2021-06-25 (Score: 20)

Total Weighted Health Score: 7.333

Reported Incidents: 0, Substantiated Complaints: 1

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 763 JOHNSONBURG RD,ST MARYS,PA,15857 (41.4258, -78.576)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-04-28

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-26

Citation on 2023-04-28

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-26

Citation on 2021-08-19

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-20

Citation on 2021-08-19

Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-20

Citation on 2021-06-25

Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-16

Citation on 2021-06-25

Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-16

Citation on 2021-06-25

Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-16


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-05-09

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-05

Citation on 2023-05-09

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-05

Citation on 2023-05-09

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-05

Citation on 2023-05-09

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-05

Citation on 2022-06-06

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-06-06

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-06-06

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-06-06

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2022-06-06

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-07-30

Citation on 2021-07-07

Type: Fire Safety, Tag: 0100, Version: New

Description: Meet other general requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0291, Version: New

Description: Install emergency lighting that can last at least 1 1/2 hours.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0912, Version: New

Description: Have power receptacles that are properly grounded.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05

Citation on 2021-07-07

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-05