PINE RUN HEALTH CENTER Nursing Home


PINE RUN HEALTH CENTER (CCN: 395366) is a Non profit - Corporation facility located in DOYLESTOWN, PA (18901). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 4/5. It offers 90 certified beds and maintains an average of 77.3 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.09486 total hours per resident per day. It has been certified since April 8, 1977 and the last listed health inspection was on April 6, 2023, The facility is located in Bucks county and provides senior and nursing home care.

PINE RUN HEALTH CENTER Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Pine Run Health Center below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: PINE RUN HEALTH CENTER

Address: 777 FERRY ROAD, DOYLESTOWN, PA 18901

Phone: (215) 340-5200

County: Bucks (140)

Ownership Type: Non profit - Corporation

Certified Beds: 90

Average Residents Per Day: 77.3 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: PINE RUN VILLAGE, INC

First Approved Date: April 8, 1977

Affiliated Entity: PRESBYTERIAN SENIOR LIVING (415)

Retirement Community: Y, Special Focus Status:

Ownership Change in Last 12 Months: Y

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 3 ()

Long Stay QM Rating: 3 ()

Short Stay QM Rating: 3 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.06577, LPN Staff Hours Per Day: 0.9644, RN Staff Hours Per Day: 1.0646, Licensed Staff Hours Per Day: 2.0290

Total Nurse Staff Hours Per Day, per resident: 4.09486

Weekend Nurse Staff Hours: 3.75757, Weekend RN Staff Hours: 0.7436

PT Staff Hours Per Day, per resident: 0.1029

Nurse Staff Turnover: 38.8, Nurse Turnover Note:

RN Turnover: 50.0, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1177, Case Mix LPN Hours Per Day: 0.8090, Case Mix RN Hours Per Day: 0.4370

Adjusted Nurse Aide Hours Per Day, per resident: 1.98728, Adjusted LPN Hours Per Day: 0.8797, Adjusted RN Hours Per Day: 0.9178

Total Adjusted Nurse Hours Per Day, per resident: 3.83707

Adjusted Weekend Nurse Hours Per Day, per resident: 3.52101

Health Survey Dates and Scores: Cycle 1: 2023-04-06 (Score: 0), Cycle 2: 2022-05-19 (Score: 0), Cycle 3: 2021-06-17 (Score: 0)

Total Weighted Health Score: 0.000

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 650.00, Payment Denials Number: 0, Total Penalties Number: 1

Location and GPS: 777 FERRY ROAD,DOYLESTOWN,PA,18901 (40.3211, -75.172)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-04-19

Type: Fire Safety, Tag: 0161, Version: New

Description: Use approved construction type or materials.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-05

Citation on 2023-04-19

Type: Fire Safety, Tag: 0200, Version: New

Description: Meet other general requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-05

Citation on 2023-04-19

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-05

Citation on 2023-04-19

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-05

Citation on 2023-04-19

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-05

Citation on 2023-04-19

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-05

Citation on 2023-04-19

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-05

Citation on 2022-05-23

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-27

Citation on 2022-05-23

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-27

Citation on 2022-05-23

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-27

Citation on 2022-05-23

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-27

Citation on 2022-05-23

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-27

Citation on 2022-05-23

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-27

Citation on 2021-06-22

Type: Fire Safety, Tag: 0100, Version: New

Description: Meet other general requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0131, Version: New

Description: Meet requirements for sections of health care facilities separated by fire resistive construction.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-06-22

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-06-22

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-06-22

Type: Fire Safety, Tag: 0347, Version: New

Description: Properly provide smoke detection systems in areas open to corridors.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-06-22

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0915, Version: New

Description: Have proper power supply for life support equipment.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13

Citation on 2021-06-22

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-13