LIFEQUEST NURSING CENTER Nursing Home


LIFEQUEST NURSING CENTER (CCN: 395735) is a Non profit - Corporation facility located in QUAKERTOWN, PA (18951). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 2/5. It offers 140 certified beds and maintains an average of 76.8 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.59755 total hours per resident per day. It has been certified since June 26, 1987 and the last listed health inspection was on July 14, 2023, The facility is located in Bucks county and provides senior and nursing home care.

LIFEQUEST NURSING CENTER Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Lifequest Nursing Center below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: LIFEQUEST NURSING CENTER

Address: 2450 JOHN FRIES HIGHWAY, QUAKERTOWN, PA 18951

Phone: (215) 536-0770

County: Bucks (140)

Ownership Type: Non profit - Corporation

Certified Beds: 140

Average Residents Per Day: 76.8 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: LIFEQUEST NURSING CENTER

First Approved Date: June 26, 1987

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 4 ()

Long Stay QM Rating: 2 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 2 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 1.93913, LPN Staff Hours Per Day: 1.1880, RN Staff Hours Per Day: 0.4704, Licensed Staff Hours Per Day: 1.6584

Total Nurse Staff Hours Per Day, per resident: 3.59755

Weekend Nurse Staff Hours: 3.21177, Weekend RN Staff Hours: 0.3257

PT Staff Hours Per Day, per resident: 0.1220

Nurse Staff Turnover: 37.5, Nurse Turnover Note:

RN Turnover: 58.3, RN Turnover Note:

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 2.1645, Case Mix LPN Hours Per Day: 0.8242, Case Mix RN Hours Per Day: 0.4357

Adjusted Nurse Aide Hours Per Day, per resident: 1.82509, Adjusted LPN Hours Per Day: 1.0636, Adjusted RN Hours Per Day: 0.4068

Total Adjusted Nurse Hours Per Day, per resident: 3.31130

Adjusted Weekend Nurse Hours Per Day, per resident: 2.95621

Health Survey Dates and Scores: Cycle 1: 2023-07-14 (Score: 8), Cycle 2: 2022-07-21 (Score: 0), Cycle 3: 2021-07-29 (Score: 4)

Total Weighted Health Score: 4.667

Reported Incidents: 0, Substantiated Complaints: 1

Infection Control Citations:

Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0

Location and GPS: 2450 JOHN FRIES HIGHWAY,QUAKERTOWN,PA,18951 (40.4413, -75.388)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-14

Type: Health, Deficiency: Provide care and assistance to perform activities of daily living for any resident who is unable.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2023-07-14

Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-08-31

Citation on 2021-04-23

Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-05-12


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-07-27

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-07

Citation on 2023-07-27

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-07

Citation on 2023-07-27

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-07

Citation on 2023-07-27

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-07

Citation on 2023-07-27

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-09-07

Citation on 2022-07-21

Type: Fire Safety, Tag: 0100, Version: New

Description: Meet other general requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2022-07-21

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2022-07-21

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2022-07-21

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2022-07-21

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2022-07-21

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2022-07-21

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2022-07-21

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2022-07-21

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-08-29

Citation on 2021-08-02

Type: Fire Safety, Tag: 0132, Version: New

Description: Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-02

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-02

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-02

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-02

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14

Citation on 2021-08-02

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-09-14