HCC AT WHITE HORSE VILLAGE Nursing Home


HCC AT WHITE HORSE VILLAGE (CCN: 395833) is a Non profit - Corporation facility located in NEWTOWN SQUARE, PA (19073). The facility has an overall rating of 5/5, health inspection rating of 5/5, and a staffing rating of 5/5. It offers 55 certified beds and maintains an average of 48.1 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 4.25920 total hours per resident per day. It has been certified since July 30, 1990 and the last listed health inspection was on April 6, 2023, The facility is located in Delaware county and provides senior and nursing home care.

HCC AT WHITE HORSE VILLAGE Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Hcc At White Horse Village below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: HCC AT WHITE HORSE VILLAGE

Address: 535 GRADYVILLE ROAD, NEWTOWN SQUARE, PA 19073

Phone: (610) 558-5044

County: Delaware (290)

Ownership Type: Non profit - Corporation

Certified Beds: 55

Average Residents Per Day: 48.1 ()

Provider Type: Medicare, Resides in Hospital: No

Legal Business Name: WHITE HORSE VILLAGE INC.

First Approved Date: July 30, 1990

Affiliated Entity: ()

Retirement Community: Y, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 5 ()

Health Inspection Rating: 5 ()

QM Rating: 5 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: 5 ()

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.21794, LPN Staff Hours Per Day: 0.6312, RN Staff Hours Per Day: 1.4100, Licensed Staff Hours Per Day: 2.0412

Total Nurse Staff Hours Per Day, per resident: 4.25920

Weekend Nurse Staff Hours: 3.81491, Weekend RN Staff Hours: 1.0812

PT Staff Hours Per Day, per resident: 0.0236

Nurse Staff Turnover: 43.3, Nurse Turnover Note:

RN Turnover: 44.4, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.1361, Case Mix LPN Hours Per Day: 0.6148, Case Mix RN Hours Per Day: 0.2762

Adjusted Nurse Aide Hours Per Day, per resident: 2.11525, Adjusted LPN Hours Per Day: 0.7576, Adjusted RN Hours Per Day: 1.9233

Total Adjusted Nurse Hours Per Day, per resident: 4.43484

Adjusted Weekend Nurse Hours Per Day, per resident: 3.97222

Health Survey Dates and Scores: Cycle 1: 2023-04-06 (Score: 0), Cycle 2: 2022-04-14 (Score: 12), Cycle 3: 2021-03-26 (Score: 12)

Total Weighted Health Score: 6.000

Reported Incidents: 0, Substantiated Complaints: 0

Infection Control Citations:

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 650.00, Payment Denials Number: 0, Total Penalties Number: 1

Location and GPS: 535 GRADYVILLE ROAD,NEWTOWN SQUARE,PA,19073 (39.9480, -75.465)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2022-04-14

Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-11

Citation on 2022-04-14

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-11

Citation on 2022-04-14

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-11

Citation on 2021-03-26

Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-05-01

Citation on 2021-03-26

Type: Health, Deficiency: Provide enough food/fluids to maintain a resident's health.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-05-01


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-04-27

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2023-04-27

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-07-06

Citation on 2023-04-27

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-11

Citation on 2023-04-27

Type: Fire Safety, Tag: 0362, Version: New

Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-11

Citation on 2023-04-27

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-11

Citation on 2023-04-27

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-11

Citation on 2023-04-27

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-11

Citation on 2023-04-27

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-11

Citation on 2022-04-28

Type: Fire Safety, Tag: 0004, Version: New

Description: Develop and maintain an Emergency Preparedness Program (EP).

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-31

Citation on 2022-04-28

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-31

Citation on 2022-04-28

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-31

Citation on 2022-04-28

Type: Fire Safety, Tag: 0293, Version: New

Description: Have properly located and lighted "Exit" signs.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-31

Citation on 2022-04-28

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-31

Citation on 2022-04-28

Type: Fire Safety, Tag: 0781, Version: New

Description: Have restrictions on the use of portable space heaters.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-31

Citation on 2022-04-28

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-05-31

Citation on 2020-11-23

Type: Fire Safety, Tag: 0133, Version: New

Description: Install a two-hour-resistant firewall separation.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-02-21

Citation on 2020-11-23

Type: Fire Safety, Tag: 0211, Version: New

Description: Keep aisles, corridors, and exits free of obstruction in case of emergency.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0225, Version: New

Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0347, Version: New

Description: Properly provide smoke detection systems in areas open to corridors.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0355, Version: New

Description: Properly select, install, inspect, or maintain portable fire extinguishes.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0522, Version: New

Description: Have an externally vented heating system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22

Citation on 2020-11-23

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-01-22