PENNSYLVANIA SOLDIERS AND SAILORS HOME Nursing Home


PENNSYLVANIA SOLDIERS AND SAILORS HOME (CCN: 39A434) is a Government - State facility located in ERIE, PA (16512). The facility has an overall rating of 3/5, health inspection rating of 2/5, and a staffing rating of 5/5. It offers 107 certified beds and maintains an average of 94.8 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 5.26834 total hours per resident per day. It has been certified since January 1, 2009 and the last listed health inspection was on April 21, 2023, The facility is located in Erie county and provides senior and nursing home care.

PENNSYLVANIA SOLDIERS AND SAILORS HOME Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Pennsylvania Soldiers And Sailors Home below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: PENNSYLVANIA SOLDIERS AND SAILORS HOME

Address: 560 EAST THIRD ST, ERIE, PA 16512

Phone: (814) 871-4531

County: Erie (320)

Ownership Type: Government - State

Certified Beds: 107

Average Residents Per Day: 94.8 ()

Provider Type: Medicaid, Resides in Hospital: No

Legal Business Name: Legal Business Name Not Available

First Approved Date: January 1, 2009

Affiliated Entity: ()

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 2 ()

QM Rating: 3 ()

Long Stay QM Rating: 3 ()

Short Stay QM Rating: (2)

Staffing Rating: 5 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 3.00260, LPN Staff Hours Per Day: 0.9658, RN Staff Hours Per Day: 1.2999, Licensed Staff Hours Per Day: 2.2657

Total Nurse Staff Hours Per Day, per resident: 5.26834

Weekend Nurse Staff Hours: 4.55907, Weekend RN Staff Hours: 0.9170

PT Staff Hours Per Day, per resident: 0.0578

Nurse Staff Turnover: 39.7, Nurse Turnover Note:

RN Turnover: 30.3, RN Turnover Note:

Admin Left Number: , Admin Turnover Note: 6

Case Mix Nurse Aide Hours Per Day, per resident: 1.8693, Case Mix LPN Hours Per Day: 0.6203, Case Mix RN Hours Per Day: 0.2569

Adjusted Nurse Aide Hours Per Day, per resident: 3.27233, Adjusted LPN Hours Per Day: 1.1489, Adjusted RN Hours Per Day: 1.9065

Total Adjusted Nurse Hours Per Day, per resident: 6.04597

Adjusted Weekend Nurse Hours Per Day, per resident: 5.23201

Health Survey Dates and Scores: Cycle 1: 2023-04-21 (Score: 133), Cycle 2: 2022-05-20 (Score: 4), Cycle 3: 2021-07-29 (Score: 0)

Total Weighted Health Score: 67.833

Reported Incidents: 1, Substantiated Complaints: 0

Infection Control Citations: 1

Fines and Penalties: Number of Fines: 1, Total Fines in Dollars: 176348.25, Payment Denials Number: 0, Total Penalties Number: 1

Location and GPS: 560 EAST THIRD ST,ERIE,PA,16512 (42.1370, -80.074)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-05-16

Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

Severity: K - Level 4: Immediate jeopardy to resident health or safety. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-13

Citation on 2023-05-16

Type: Health, Deficiency: Administer the facility in a manner that enables it to use its resources effectively and efficiently.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-13

Citation on 2022-05-20

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-06


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-04-25

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-01

Citation on 2023-04-25

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-06-01

Citation on 2022-05-24

Type: Fire Safety, Tag: 0100, Version: New

Description: Meet other general requirements.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-30

Citation on 2022-05-24

Type: Fire Safety, Tag: 0223, Version: New

Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-30

Citation on 2022-05-24

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-30

Citation on 2022-05-24

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-30

Citation on 2022-05-24

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-30

Citation on 2022-05-24

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-30

Citation on 2022-05-24

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-30

Citation on 2022-05-24

Type: Fire Safety, Tag: 0912, Version: New

Description: Have power receptacles that are properly grounded.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-06-30

Citation on 2021-07-28

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25

Citation on 2021-07-28

Type: Fire Safety, Tag: 0311, Version: New

Description: Have an enclosure around a vertical opening shaft.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25

Citation on 2021-07-28

Type: Fire Safety, Tag: 0321, Version: New

Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25

Citation on 2021-07-28

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25

Citation on 2021-07-28

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25

Citation on 2021-07-28

Type: Fire Safety, Tag: 0761, Version: New

Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25

Citation on 2021-07-28

Type: Fire Safety, Tag: 0911, Version: New

Description: Meet requirements for the installation and maintenance of electrical systems.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25

Citation on 2021-07-28

Type: Fire Safety, Tag: 0912, Version: New

Description: Have power receptacles that are properly grounded.

Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25

Citation on 2021-07-28

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-08-25