Provider Name: YAKIMA VALLEY SCHOOL
Address: 609 SPEYERS ROAD, SELAH, WA 98942
Phone: (509) 698-1300
County: Yakima (380)
Ownership Type: Government - State
Certified Beds: 112
Average Residents Per Day: 50.5 ()
Provider Type: Medicaid, Resides in Hospital: No
Legal Business Name: Legal Business Name Not Available
First Approved Date: April 21, 1994
Affiliated Entity: ()
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: Family
Sprinkler System Status: Yes
Overall Rating: 5 ()
Health Inspection Rating: 5 ()
QM Rating: 4 ()
Long Stay QM Rating: 4 ()
Short Stay QM Rating: (2)
Staffing Rating: 5 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 10.4710, LPN Staff Hours Per Day: 0.6257, RN Staff Hours Per Day: 2.0527, Licensed Staff Hours Per Day: 2.6784
Total Nurse Staff Hours Per Day, per resident: 13.1494
Weekend Nurse Staff Hours: 11.3519, Weekend RN Staff Hours: 1.2897
PT Staff Hours Per Day, per resident: 0.1052
Nurse Staff Turnover: 39.6, Nurse Turnover Note:
RN Turnover: 26.1, RN Turnover Note:
Admin Left Number: , Admin Turnover Note: 6
Case Mix Nurse Aide Hours Per Day, per resident: 2.0642, Case Mix LPN Hours Per Day: 0.6843, Case Mix RN Hours Per Day: 0.2543
Adjusted Nurse Aide Hours Per Day, per resident: 10.3339, Adjusted LPN Hours Per Day: 0.6747, Adjusted RN Hours Per Day: 3.0410
Total Adjusted Nurse Hours Per Day, per resident: 13.8022
Adjusted Weekend Nurse Hours Per Day, per resident: 11.9154
Health Survey Dates and Scores: Cycle 1: 2023-06-09 (Score: 8), Cycle 2: 2022-02-10 (Score: 20), Cycle 3: 2019-03-20 (Score: 60)
Total Weighted Health Score: 20.667
Reported Incidents: 1, Substantiated Complaints: 0
Infection Control Citations: 0
Fines and Penalties: Number of Fines: 0, Total Fines in Dollars: 0.00, Payment Denials Number: 0, Total Penalties Number: 0
Location and GPS: 609 SPEYERS ROAD,SELAH,WA,98942 (46.6592, -120.538)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-28
Type: Health, Deficiency: Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-03-04
Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-03-04
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-03-04
Type: Health, Deficiency: Implement a program that monitors antibiotic use.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-03-04
Type: Health, Deficiency: Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decline/room, etc.) that affect the resident.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-06-09
Type: Health, Deficiency: Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-19
Type: Health, Deficiency: Honor the resident's right to request, refuse, and/or discontinue treatment, to participate in or refuse to participate in experimental research, and to formulate an advance directive.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-19
Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-19
Type: Health, Deficiency: Provide appropriate treatment and care according to orders, resident’s preferences and goals.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-19
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-19
Type: Health, Deficiency: Provide enough nursing staff every day to meet the needs of every resident; and have a licensed nurse in charge on each shift.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-19
Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-19
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0100, Version: New
Description: Meet other general requirements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-09
Type: Fire Safety, Tag: 0221, Version: New
Description: Provide rooms that can be unlocked from inside without a key.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-06
Type: Fire Safety, Tag: 0223, Version: New
Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-05
Type: Fire Safety, Tag: 0293, Version: New
Description: Have properly located and lighted "Exit" signs.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-09
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-09
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-30
Type: Fire Safety, Tag: 0355, Version: New
Description: Properly select, install, inspect, or maintain portable fire extinguishes.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-09
Type: Fire Safety, Tag: 0521, Version: New
Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-23
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-29
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-12
Type: Fire Safety, Tag: 0923, Version: New
Description: Have proper medical gas storage and administration areas.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-12
Type: Fire Safety, Tag: 0926, Version: New
Description: Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-06-23
Type: Fire Safety, Tag: 0100, Version: New
Description: Meet other general requirements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-15
Type: Fire Safety, Tag: 0222, Version: New
Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-15
Type: Fire Safety, Tag: 0223, Version: New
Description: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-15
Type: Fire Safety, Tag: 0225, Version: New
Description: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-17
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-03-25
Type: Fire Safety, Tag: 0511, Version: New
Description: Have properly installed electrical wiring and gas equipment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-28
Type: Fire Safety, Tag: 0531, Version: New
Description: Have elevators that firefighters can control in the event of a fire.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-02-11
Type: Fire Safety, Tag: 0372, Version: New
Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-21
Type: Fire Safety, Tag: 0531, Version: New
Description: Have elevators that firefighters can control in the event of a fire.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-15
Type: Fire Safety, Tag: 0761, Version: New
Description: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-21
Type: Fire Safety, Tag: 0914, Version: New
Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-19
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-11
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-04-15
Type: Fire Safety, Tag: 0921, Version: New
Description: Ensure that testing and maintenance of electrical equipment is performed.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2019-03-27