MEADOWBROOK AT CHETEK Nursing Home


MEADOWBROOK AT CHETEK (CCN: 525672) is a For profit - Limited Liability company facility located in CHETEK, WI (54728). The facility has an overall rating of 3/5, health inspection rating of 3/5, and a staffing rating of 4/5. It offers 97 certified beds and maintains an average of 64.1 residents per day. The nursing staff includes Nurse Aides, LPNs, and RNs working 3.64132 total hours per resident per day. It has been certified since May 10, 2004 and the last listed health inspection was on March 29, 2023, The facility is located in Barron county and provides senior and nursing home care.

MEADOWBROOK AT CHETEK Summary


Patient Ratings
Please rate how you felt your loved one or yourself have been treated at Meadowbrook At Chetek below to help others make a more informed decision. Thank you.
Current Rating: Loading...

Provider Name: MEADOWBROOK AT CHETEK

Address: 725 KNAPP ST, CHETEK, WI 54728

Phone: (715) 924-4891

County: Barron (020)

Ownership Type: For profit - Limited Liability company

Certified Beds: 97

Average Residents Per Day: 64.1 ()

Provider Type: Medicare and Medicaid, Resides in Hospital: No

Legal Business Name: CHETEK NURSING AND REHAB LLC

First Approved Date: May 10, 2004

Affiliated Entity: SYNERGY SENIOR CARE (502)

Retirement Community: N, Special Focus Status:

Ownership Change in Last 12 Months: N

Resident Family Council: Resident

Sprinkler System Status: Yes

Overall Rating: 3 ()

Health Inspection Rating: 3 ()

QM Rating: 4 ()

Long Stay QM Rating: 4 ()

Short Stay QM Rating: 3 ()

Staffing Rating: 4 ()

Staffing Report Note:

PT Staffing Note:

Nurse Aide Staff Hours Per Day, per resident: 2.12104, LPN Staff Hours Per Day: 0.3310, RN Staff Hours Per Day: 1.1892, Licensed Staff Hours Per Day: 1.5202

Total Nurse Staff Hours Per Day, per resident: 3.64132

Weekend Nurse Staff Hours: 2.98876, Weekend RN Staff Hours: 0.8281

PT Staff Hours Per Day, per resident: 0.0338

Nurse Staff Turnover: 21.6, Nurse Turnover Note:

RN Turnover: 18.8, RN Turnover Note:

Admin Left Number: 0, Admin Turnover Note:

Case Mix Nurse Aide Hours Per Day, per resident: 2.3360, Case Mix LPN Hours Per Day: 0.8015, Case Mix RN Hours Per Day: 0.4157

Adjusted Nurse Aide Hours Per Day, per resident: 1.84975, Adjusted LPN Hours Per Day: 0.3048, Adjusted RN Hours Per Day: 1.0778

Total Adjusted Nurse Hours Per Day, per resident: 3.23012

Adjusted Weekend Nurse Hours Per Day, per resident: 2.65126

Health Survey Dates and Scores: Cycle 1: 2023-03-29 (Score: 48), Cycle 2: 2022-02-02 (Score: 40), Cycle 3: 2020-02-20 (Score: 60)

Total Weighted Health Score: 47.333

Reported Incidents: 0, Substantiated Complaints: 2

Infection Control Citations: 0

Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 10650.00, Payment Denials Number: 0, Total Penalties Number: 2

Location and GPS: 725 KNAPP ST,CHETEK,WI,54728 (45.3145, -91.657)

Process Date: 2024-03-01


Health Inspection Citations Details

Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-03-29

Type: Health, Deficiency: Ensure that residents are fully informed and understand their health status, care and treatments.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-24

Citation on 2023-03-29

Type: Health, Deficiency: Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decline/room, etc.) that affect the resident.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-24

Citation on 2023-03-29

Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-24

Citation on 2023-03-29

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-24

Citation on 2023-03-29

Type: Health, Deficiency: Designate a qualified infection preventionist to be responsible for the infection prevent and control program in the nursing home.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-24

Citation on 2023-03-29

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-24

Citation on 2023-01-10

Type: Health, Deficiency: Observe each nurse aide's job performance and give regular training.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-10

Citation on 2023-01-10

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-02-10

Citation on 2022-02-02

Type: Health, Deficiency: Honor the resident's right to and the facility must promote and facilitate resident self-determination through support of resident choice.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-02

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-02

Type: Health, Deficiency: Provide and implement an infection prevention and control program.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2021-09-01

Type: Health, Deficiency: Keep all essential equipment working safely.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-15

Citation on 2021-09-01

Type: Health, Deficiency: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2021-10-15

Citation on 2020-02-20

Type: Health, Deficiency: Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decline/room, etc.) that affect the resident.

Severity: G - Level 3: Actual harm that is not immediate jeopardy. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-20

Citation on 2020-02-20

Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-20

Citation on 2020-02-20

Type: Health, Deficiency: Provide enough food/fluids to maintain a resident's health.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-20


Fire Safety Citations Details

Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:

Citation on 2023-03-27

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-14

Citation on 2023-03-27

Type: Fire Safety, Tag: 0741, Version: New

Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-14

Citation on 2023-03-27

Type: Fire Safety, Tag: 0919, Version: New

Description: Meet requirements for the use of electrical equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-14

Citation on 2023-03-27

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2023-04-14

Citation on 2022-02-03

Type: Fire Safety, Tag: 0222, Version: New

Description: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0271, Version: New

Description: Have exits that are accessible at all times.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0363, Version: New

Description: Install corridor and hallway doors that block smoke.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0372, Version: New

Description: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0374, Version: New

Description: Install smoke barrier doors that can resist smoke for at least 20 minutes.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0511, Version: New

Description: Have properly installed electrical wiring and gas equipment.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2022-02-03

Type: Fire Safety, Tag: 0918, Version: New

Description: Have generator or other power source capable of supplying service within 10 seconds.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2022-03-02

Citation on 2020-02-18

Type: Fire Safety, Tag: 0324, Version: New

Description: Provide properly protected cooking facilities.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13

Citation on 2020-02-18

Type: Fire Safety, Tag: 0345, Version: New

Description: Have approved installation, maintenance and testing program for fire alarm systems.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13

Citation on 2020-02-18

Type: Fire Safety, Tag: 0351, Version: New

Description: Install an approved automatic sprinkler system.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13

Citation on 2020-02-18

Type: Fire Safety, Tag: 0353, Version: New

Description: Inspect, test, and maintain automatic sprinkler systems.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13

Citation on 2020-02-18

Type: Fire Safety, Tag: 0521, Version: New

Description: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13

Citation on 2020-02-18

Type: Fire Safety, Tag: 0712, Version: New

Description: Have simulated fire drills held at unexpected times.

Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13

Citation on 2020-02-18

Type: Fire Safety, Tag: 0914, Version: New

Description: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13

Citation on 2020-02-18

Type: Fire Safety, Tag: 0920, Version: New

Description: Ensure proper usage of power strips and extension cords.

Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13

Citation on 2020-02-18

Type: Fire Safety, Tag: 0923, Version: New

Description: Have proper medical gas storage and administration areas.

Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.

Corrected: Deficient, Provider has date of correction on 2020-03-13