Provider Name: THE HILLS HEALTHCARE CENTER
Address: 10158 SUNLAND BLVD, SUNLAND, CA 91040
Phone: (818) 353-7800
County: Los Angeles (200)
Ownership Type: For profit - Limited Liability company
Certified Beds: 67
Average Residents Per Day: 63.6 ()
Provider Type: Medicare and Medicaid, Resides in Hospital: No
Legal Business Name: SUNLAND SNF LLC
First Approved Date: November 8, 1976
Affiliated Entity: ()
Retirement Community: N, Special Focus Status:
Ownership Change in Last 12 Months: N
Resident Family Council: None
Sprinkler System Status: Yes
Overall Rating: 4 ()
Health Inspection Rating: 3 ()
QM Rating: 3 ()
Long Stay QM Rating: 3 ()
Short Stay QM Rating: 2 ()
Staffing Rating: 5 ()
Staffing Report Note:
PT Staffing Note:
Nurse Aide Staff Hours Per Day, per resident: 2.75256, LPN Staff Hours Per Day: 0.8765, RN Staff Hours Per Day: 0.5767, Licensed Staff Hours Per Day: 1.4532
Total Nurse Staff Hours Per Day, per resident: 4.20585
Weekend Nurse Staff Hours: 3.81018, Weekend RN Staff Hours: 0.5321
PT Staff Hours Per Day, per resident: 0.0192
Nurse Staff Turnover: 26.3, Nurse Turnover Note:
RN Turnover: 33.3, RN Turnover Note:
Admin Left Number: 0, Admin Turnover Note:
Case Mix Nurse Aide Hours Per Day, per resident: 1.8271, Case Mix LPN Hours Per Day: 0.6608, Case Mix RN Hours Per Day: 0.3102
Adjusted Nurse Aide Hours Per Day, per resident: 3.06905, Adjusted LPN Hours Per Day: 0.9788, Adjusted RN Hours Per Day: 0.7004
Total Adjusted Nurse Hours Per Day, per resident: 4.73753
Adjusted Weekend Nurse Hours Per Day, per resident: 4.29185
Health Survey Dates and Scores: Cycle 1: 2023-11-02 (Score: 76), Cycle 2: 2022-10-14 (Score: 84), Cycle 3: 2020-02-07 (Score: 168)
Total Weighted Health Score: 94.000
Reported Incidents: 3, Substantiated Complaints: 7
Infection Control Citations: 0
Fines and Penalties: Number of Fines: 2, Total Fines in Dollars: 1625.00, Payment Denials Number: 0, Total Penalties Number: 2
Location and GPS: 10158 SUNLAND BLVD,SUNLAND,CA,91040 (34.2603, -118.339)
Process Date: 2024-03-01
Each record details specific health deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Health, Deficiency: Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-14
Type: Health, Deficiency: Provide safe, appropriate pain management for a resident who requires such services.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-05-16
Type: Health, Deficiency: Ensure that each resident is free from the use of physical restraints, unless needed for medical treatment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Provide pharmaceutical services to meet the needs of each resident and employ or obtain the services of a licensed pharmacist.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Ensure that residents are free from significant medication errors.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-06
Type: Health, Deficiency: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Waiver has been granted on 2023-11-06
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-06-24
Type: Health, Deficiency: Honor the resident's right to request, refuse, and/or discontinue treatment, to participate in or refuse to participate in experimental research, and to formulate an advance directive.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Give residents notice of Medicaid/Medicare coverage and potential liability for services not covered.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Ensure that each resident is free from the use of physical restraints, unless needed for medical treatment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Encode each resident’s assessment data and transmit these data to the State within 7 days of assessment.
Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: PASARR screening for Mental disorders or Intellectual Disabilities
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Create and put into place a plan for meeting the resident's most immediate needs within 48 hours of being admitted
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Provide appropriate pressure ulcer care and prevent new ulcers from developing.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Provide enough food/fluids to maintain a resident's health.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Post nurse staffing information every day.
Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Provide pharmaceutical services to meet the needs of each resident and employ or obtain the services of a licensed pharmacist.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Conduct and document a facility-wide assessment to determine what resources are necessary to care for residents competently during both day-to-day operations and emergencies.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-13
Type: Health, Deficiency: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has no plan of correction on
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-10-14
Type: Health, Deficiency: Honor the resident's right to and the facility must promote and facilitate resident self-determination through support of resident choice.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-05-16
Type: Health, Deficiency: Provide safe, appropriate dialysis care/services for a resident who requires such services.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-05-16
Type: Health, Deficiency: Keep residents' personal and medical records private and confidential.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2021-05-12
Type: Health, Deficiency: Reasonably accommodate the needs and preferences of each resident.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Honor the resident's right to share a room with spouse or roommate of choice and receive written notice before a change is made.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Give residents notice of Medicaid/Medicare coverage and potential liability for services not covered.
Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Honor the resident's right to voice grievances without discrimination or reprisal and the facility must establish a grievance policy and make prompt efforts to resolve grievances.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Ensure that each resident is free from the use of physical restraints, unless needed for medical treatment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Encode each resident’s assessment data and transmit these data to the State within 7 days of assessment.
Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Create and put into place a plan for meeting the resident's most immediate needs within 48 hours of being admitted
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Provide activities to meet all resident's needs.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Provide appropriate care for residents who are continent or incontinent of bowel/bladder, appropriate catheter care, and appropriate care to prevent urinary tract infections.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Provide safe and appropriate respiratory care for a resident when needed.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Try different approaches before using a bed rail. If a bed rail is needed, the facility must (1) assess a resident for safety risk; (2) review these risks and benefits with the resident/representative; (3) get informed consent; and (4) Correctly install and maintain the bed rail.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Ensure that nurses and nurse aides have the appropriate competencies to care for every resident in a way that maximizes each resident's well being.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Implement gradual dose reductions(GDR) and non-pharmacological interventions, unless contraindicated, prior to initiating or instead of continuing psychotropic medication; and PRN orders for psychotropic medications are only used when the medication is necessary and PRN use is limited.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Ensure medication error rates are not 5 percent or greater.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Have a plan that describes the process for conducting QAPI and QAA activities.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Set up an ongoing quality assessment and assurance group to review quality deficiencies and develop corrective plans of action.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Have the Quality Assessment and Assurance group have the required members and meet at least quarterly
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Provide and implement an infection prevention and control program.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Implement a program that monitors antibiotic use.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Develop and implement policies and procedures for flu and pneumonia vaccinations.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-05
Type: Health, Deficiency: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Severity: B - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Waiver has been granted on
Each record details specific fire safety deficiencies found during inspections, categorized by type, severity, and whether they were corrected. Below are the severity levels and their implications:
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0271, Version: New
Description: Have exits that are accessible at all times.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0331, Version: New
Description: Construct fire resistant interior walls.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0346, Version: New
Description: Follow proper procedures when the fire alarm was out of service for more than 4 hours.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0351, Version: New
Description: Install an approved automatic sprinkler system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0354, Version: New
Description: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0355, Version: New
Description: Properly select, install, inspect, or maintain portable fire extinguishes.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0511, Version: New
Description: Have properly installed electrical wiring and gas equipment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0741, Version: New
Description: Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0923, Version: New
Description: Have proper medical gas storage and administration areas.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2023-11-09
Type: Fire Safety, Tag: 0015, Version: New
Description: Address subsistence needs for staff and patients.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0030, Version: New
Description: List the names and contact information of those in the facility.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0031, Version: New
Description: Provide emergency officials' contact information.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0039, Version: New
Description: Conduct testing and exercise requirements.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0111, Version: New
Description: Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0291, Version: New
Description: Install emergency lighting that can last at least 1 1/2 hours.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0293, Version: New
Description: Have properly located and lighted "Exit" signs.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0300, Version: New
Description: Meet other general requirements that are deficient.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0331, Version: New
Description: Construct fire resistant interior walls.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0351, Version: New
Description: Install an approved automatic sprinkler system.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0362, Version: New
Description: Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0363, Version: New
Description: Install corridor and hallway doors that block smoke.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0511, Version: New
Description: Have properly installed electrical wiring and gas equipment.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0711, Version: New
Description: Provide a written emergency evacuation plan.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0923, Version: New
Description: Have proper medical gas storage and administration areas.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2022-11-18
Type: Fire Safety, Tag: 0007, Version: New
Description: Address patient/client population and determine types of services needed.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0009, Version: New
Description: Include a process for Emergency Preparedness collaboration.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0015, Version: New
Description: Address subsistence needs for staff and patients.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0018, Version: New
Description: Establish procedures for tracking staff and patients during an emergency.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0030, Version: New
Description: List the names and contact information of those in the facility.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0036, Version: New
Description: Establish emergency prep training and testing.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0037, Version: New
Description: Establish staff and initial training requirements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0039, Version: New
Description: Conduct testing and exercise requirements.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0041, Version: New
Description: Implement emergency and standby power systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0271, Version: New
Description: Have exits that are accessible at all times.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0281, Version: New
Description: Install proper backup exit lighting.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0321, Version: New
Description: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0324, Version: New
Description: Provide properly protected cooking facilities.
Severity: E - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0331, Version: New
Description: Construct fire resistant interior walls.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0343, Version: New
Description: Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0345, Version: New
Description: Have approved installation, maintenance and testing program for fire alarm systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0351, Version: New
Description: Install an approved automatic sprinkler system.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0352, Version: New
Description: Properly install and monitor supervisory attachments on automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0353, Version: New
Description: Inspect, test, and maintain automatic sprinkler systems.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0711, Version: New
Description: Provide a written emergency evacuation plan.
Severity: C - Level 1: No actual harm with potential for minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0712, Version: New
Description: Have simulated fire drills held at unexpected times.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0918, Version: New
Description: Have generator or other power source capable of supplying service within 10 seconds.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0920, Version: New
Description: Ensure proper usage of power strips and extension cords.
Severity: F - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12
Type: Fire Safety, Tag: 0923, Version: New
Description: Have proper medical gas storage and administration areas.
Severity: D - Level 2: No actual harm with potential for more than minimal harm. Plan of Correction required.
Corrected: Deficient, Provider has date of correction on 2020-03-12